Presentation Title

Download Report

Transcript Presentation Title

Travel Sensor Is Factory Adjusted




The placement of the feedback
arm on the travel sensor is
factory adjusted and sealed with
anti-tamper paint.
This setting has been tested for
functionality successfully several
times before the DVC6000 ships
from the factory.
Do not assume this setting is
wrong.
Check everything else first before
disturbing the anti-tamper paint.
Slide 1
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 1
Anti-Tamper
Paint
DVC6000 – Potentiometer Issues

Potentiometer Components
Slide 2
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 2
Vibration Induced Potentiometer Wear



Some control systems are not grounded
Valve Travels in Higher Resistance Area (80 –
90% travel)
Amplification of travel noise by velocity gain in
the DVC tuning ( Reduce affect by changing to
velocity gain of 0)
Slide 3
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 3
No Potentiometer Wear
Slide 4
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 4
ValveLink Graph with Potentiometer WearThru
Slide 5
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 5
Profile Test

Requires PD Tier
Slide 6
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 6
PD Profile No problems
Slide 7
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 7
PD Profile Test Showing Early Wear
Slide 8
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 8
Increase Reliability with Linkage-less feedback

Best to remove potential
wear points all together

Unique linkage-less
non-contact design
Feedback Arrays
– Feedback components
never touch the instrument
– DVC2000
• Released in 2004
– DVC6200 HART
– DVC6200f FOUNDATION
Fieldbus
No Linkages
Slide 9
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 9
DVC6200 - Product Details

Differences between the DVC6200 & the
DVC6000
–
–
–
–
–
Hall sensor in place of the feedback potentiometer
Terminal box moves to the left side of the housing
New mounting kits (same design as DVC2000 kits)
HART: Firmware 10 required
FOUNDATION fieldbus: new PWB and terminal box
required
Slide 10
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 10
DVC6200 - Mounting Kits


Bolt patterns for DVC2000 and DVC6200 are
identical
Existing DVC2000 mounting kits are being
updated
– 1 standard kit for both DVC6200 and DVC2000
– Stronger brackets will replace the existing brackets
to accommodate additional weight

New curved array
– For use with the existing long stroke cams
– For Fisher rotary actuator window
Rotary Magnet
1”, 2” & 4” array
Curved array
Slide 11
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 11
Long Stroke Mounting
Anti-rotation
Slide 12
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 12
Dual Mounting Bracket
Slide 13
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 13
DVC6205/6215 Remote Mount
Slide 14
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 14
Terminal Boxes
1.
Power 4V to 30V
2.
Feedback 0-.5 V normal
3.
DVC6215 Ground
4.
Status Line
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 15
Slide 15
Design Engineering
Used for Temperature Calibration
-52 to 125 Deg C
Slide 16
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 16
Remote Mount Components
Slide 17
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 17
ValveLink Mobile
ValveLink Mobile
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 19

Bluetooth Communications to a HART modem

Developed for Windows Mobile platform

Very compact, portable platform for local
configuration, calibration, and diagnostics.

Slide 19
Integration
into Emerson 375 / 475 platform
ValveLink Mobile 2.0
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 20

Icon Driven User Interface

Common Tasks Located on Home Screen.

High Contrast for Outdoor Viewing.

Thumb Driven Interface - No Stylus
Required.

Preprogrammed diagnostics. Tests can
beSlide
run,
saved, and uploaded later to
20
ValveLink or AMS.
ValveLink Mobile on 375 / 475

Same interface as on PDA and Smartphone
platforms.

FAST configuration, calibration, and
diagnostics.
Slide 21
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 21
Diagnostics on the 375 / 475
Total Scan
Step Response
PD Diagnostics
Valve Signature
Step Study
1 Button Sweep
Dynamic Error Band
Stroking Speed
PD Traces
Slide 22
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 22
Valve Diagnostic Changes
Slide 23
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 23
PD Diagnostics
Slide 24
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 24
Import Field Data into ValveLink
(Upload to the mother ship)
Slide 25
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 25
ValveLink Support
ValveLink 12 License Changes

Planning on
free
Version with 12.0 targeted for Oct.
– Install on Multiple PC’s
– No additional license key required
– Connect to 1 device at a time
– Database is limited to one tag
– Supports HART & Ff
Slide 27
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 27
ValveLink Support

$405 per year

Includes License Support, New Software CD,
and Web Based FTP Access

ftp://ftp2.emersonprocess.com/
Slide 28
[File Name or Event]
Emerson Confidential