Automation and Drives
Applications with
IE/PB Link
outside ‘PROFInet‘
 Verticale integration using engineering tools like
SIMATIC PDM or Drive ES
 Remote diagnostic / remote information with
OPC
Automation and Drives
Vertical Integration with IE/PB Link
Network Transition from Industrial Ethernet to PROFIBUS
SIMATIC NET Networking for Industry
(C) Siemens Energy&Automation, 2003, AMD
K. Reese Page 2
Automation and Drives
Customer Benefits with Verticale Integration
Access to PROFIBUS devices via Industrial Ethernet
and worldwide via Internet
 Central Engineering
Parametrization and diagnsotic of all PROFIBUS devices
 Drives via the engineering software Drives ES
 PROFIBUS PA devices via SIMATIC PDM, etc.
Central and consistent data management
Optimization of a plant from a central control station
 Additional benefits using SIMATIC S7 PLCs within TIA
Remote access to the SIMATIC S7 PLC (on PROFIBUS, Ethernet)
 All STEP7 online functions are supported
 Download of STEP 7-Programs from central control station
 Remote diagnsotic to keep plant downtime to a minimum
Centrale Visualization
 Via S7 OPC server, access to process data of a SIMATIC S7 PLC on PROFIBUS; e.g. ET200S
with IM151-CPU as DP-Slave
SIMATIC NET Networking for Industry
(C) Siemens Energy&Automation, 2003, AMD
K. Reese Page 3
Automation and Drives
Sample Configuration
 How is it possible to reconfigure or optimize a
drive on PROFIBUS with Drive ES ?
Automation and Drives
Configuration in Motion Control applications, using a SIMATIC S7 as DP-Master
Sample configuration with SIMATIC S7
Data access to
process data via
S7 function
STEP7 program
download, diagnostic
etc. via S7 function
HMI System
z.B. ProTool Pro
mit OPC-Server
PG with
STEP7
Central engineering
with Drive ES
PC with
Drive ES*)
Ind. Ethernet
Note:
PG w/ STEP7 and PC w/
Drives ES can be one
Station / PC
CP 343-1
S7-300
e.g. CPU 315-2
DP-Master cl.1
*) Drive ES with STEP7
because Drive ES does
not provide an
Ethernet access
+
PROFIBUS (w/Motion Control)
Isochron drives solution
ET200S
with CPU
SIMATIC NET Networking for Industry
(C) Siemens Energy&Automation, 2003, AMD
ET200S
with CPU
K. Reese Page 5
Automation and Drives
Configuration in Motion Control applications, using a NON - SIMATIC S7 as DPMaster
Sample configuration: Drives in a NON-SIMATIC S7 invironment
Data access to
process data via
S7 function
HMI System
e.g. ProTool Pro
with OPC-Server
PG with
STEP7
STEP7 program
download, diagnostic
etc. via S7 function
PC with
Drive ES
Central engineering
with Drive ES
Ind. Ethernet
DP-Master Cl.1 e.g.:
 SIMATIC S5
 PC solution
 3rd party controller
*) Drive ES with STEP7
because Drive ES does
not provide an
Ethernet access
Note:
PG w/ STEP7 and PC w/
Drives ES can be one
Station / PC
PROFInet
IE/PB Link
(DP-M Cl.2)
PROFIBUS (w/Motion Control)
Isochron drives solution
ET200S
with CPU
SIMATIC NET Networking for Industry
(C) Siemens Energy&Automation, 2003, AMD
ET200S
with CPU
K. Reese Page 6
Automation and Drives
Configuration in Motion Control applications, using a NON - SIMATIC S7 as DPMaster
Sample configuration for worldwide access
Data access to
process data via
S7 function
STEP7 program
download, diagnostic
etc. via S7 function
ES
HMI System
e.g. ProTool Pro
with OPC-Server
Central engineering
with Drive ES
Intranet /
Internet
ES
WAN /
Telephon
PG with
STEP7
PC with
Drive ES
Ind. Ethernet
DP-Master Cl.1
PROFInet
IE/PB Link
(DP-M Cl.2)
PROFIBUS (w/Motion Control)
*) Drive ES with STEP7
because Drive ES does
not provide an
Ethernet access
Isochron drives solution
ET200S
with CPU
SIMATIC NET Networking for Industry
(C) Siemens Energy&Automation, 2003, AMD
ET200S
with CPU
Note:
PG w/ STEP7 and PC w/
Drives ES can be one
Station / PC
K. Reese Page 7
Automation and Drives
Notes, how to use the IE/PB link in Motion Control applications
Installations with S7-300 as DP master the CP343-1 is the most cost effective solution providing
equal functionality
 Central engineering with Drive ES on Ethernet – Routing via Ethernet CP through the S7 CPU as
DP master to PROFIBUS
With S5, WinAC, PC or 3rd party solution as DP master a central engineering is possible
using the IE/PB link
 Routing for engineering systems – like Drive ES - is supported
 Required is STEP7 and Drives ES Basic as option package
 Configuration of the IE/PB link is done with STEP7
Central engineering from Ethernet to multiple PROFIBUS sub-networks possible
The IE/PB link receives the required routing information out of
a STEP7 project ! Using a DP master, which does not require a STEP7 configuration, the PROFIBUS
devices e.g. drives that shall be reached need to be configured in a STEP7 ‘Dummy Project‘.
SIMATIC NET Networking for Industry
(C) Siemens Energy&Automation, 2003, AMD
K. Reese Page 8
Automation and Drives
Sample Configuration
 How is it possible to reconfigure or optimize a
process automation device on PROFIBUS PA
with SIMATIC PDM ?
Automation and Drives
Configuration in the process industry – PCS7
Sample confirguration for a PCS7 installation
Data access to
process data via
S7 function
WinCC
OS
SIMATIC PDM *)
ES
OS
STEP7 program
download, diagnostic
etc. via S7 function
PG
Central engineering
with SIMATIC PDM
Data block routing
Ind. Ethernet
Sub-Installation 1
S7-400
with CP443-1
and CP443-5
Sub-Installation n
PROFIBUS
DP/PA Link
DP/PA Link
PA-Geräte
ET200M
PA-Geräte
PROFIBUS-PA
SIMATIC NET Networking for Industry
(C) Siemens Energy&Automation, 2003, AMD
*) SIMATIC PDM with
STEP7 because SIMATIC
PDM does not provide an
Ethernet access
Note:
PG w/ STEP7 and PC w/
SIMATIC PDM can be one
Station / PC
K. Reese Page 10
Automation and Drives
Configuration with SIMATIC PDM in
Not PCS7 Installations
Sample configuration process industry
HMI
Data access to
process data via
S7 function
STEP7 program
download, diagnostic
etc. via S7 function
SIMATIC PDM *)
PG
WinCC
Ind. Ethernet
S7-300
e.g. CPU 315-2
DP-Master Cl.1
PROFInet
IE/PB Link
(DP-M Cl.2)
Central engineering
with SIMATIC PDM
Data block routing
SIMATIC PDM wo/ PCS7
 SIMATIC S7-300, S5
 PC solution
 3rd party e.g. Delta V
PROFIBUS
DP/PA Link
DP/PA Link
ET200M
PA-Geräte
PROFIBUS-PA
PA-Geräte
SIMATIC NET Networking for Industry
(C) Siemens Energy&Automation, 2003, AMD
*) SIMATIC PDM with
STEP7 because SIMATIC
PDM does not provide an
Ethernet access
Note:
PG w/ STEP7 and PC w/
SIMATIC PDM can be one
Station / PC
K. Reese Page 11
Automation and Drives
Notes, how to use the IE/PB link in Process Automation Applications
“ Standard“ gateway in PCS7 installations is a SIMATIC
S7-400 with CP443-1 and CP443-5
 Central Engineering with SIMATIC PDM on Ethernet – data block routing through both CPs in
the S7-400
Plants, with S7-300, S5 or 3rd party solution as DP master, a central engineering is only
possible using a IE/PB link
 For PDM, equal functionality is supported like in PCS7 !
 Required is STEP7 and SIMATIC PDM with the options ‘STEP7 integration‘ and ‘S7 routing‘
 Configuration of the IE/PB link is done with STEP7
Extention of existing plants with central engineering, if the S7-400 does not support data block
routing
 E.g. PROFIBUS connectivity direct via S7-400 CPU
The IE/PB link receives the required routing information out of
a STEP7 project ! Using a DP master, which does not require a STEP7 configuration, the PROFIBUS
PA devices that shall be reached need to be configured in a STEP7 ‘Dummy Project‘.
SIMATIC NET Networking for Industry
(C) Siemens Energy&Automation, 2003, AMD
K. Reese Page 12
Automation and Drives
Sample Configuration
 How is it possible to display all necessary plant
data – from controller on PROFIBUS or Ethernet
– on a central visualization station on Ethernet
?
Automation and Drives
Configuration with central HMI on Ethernet
Central visualization on Ethernet
HMI
z.B. ProTool Pro
with OPC-Server
S7-300
S7-400
PG with
STEP7
Ind. Ethernet
PROFInet
IE/PB Link
Data exchange between PLCs
S7 functions, Send/Receive, etc.
PROFIBUS
S7-300
Data access to process data
via S7 function and OPC
ET200S
with
IM151-CPU
STEP7 programe download,
diagnostic, etc.
Sub-Network with multiple PLCs, connected via PROFIBUS
SIMATIC NET Networking for Industry
(C) Siemens Energy&Automation, 2003, AMD
K. Reese Page 14
Automation and Drives
Notes, how to use the IE/PB link for
Central Visualization
Which devices / data on PROFIBUS can be accessed from a visualization station on Ethernet
using S7 functions ?
 All devices that support S7 functions (Put, Get, ...) as server
 SIMATIC S7-300/400 with integrated PROFIBUS interface or
PROFIBUS CP
 ET200S with IM 151 CPU or ET200X with BM 147 CPU
 Access to all data on the CPUs, e.g. Data blocks, etc.
Requirements on the PC side:
 Application with OPC client interface
 Software ‚S7-1613‘ or ‚SOFTNET S7 for Industrial Ethernet‘
 S7 OPC-Server is included
Today, no direct data access to DP slaves possible !
 Process data of a DP slave can be read or write only ‘indirectly‘ via the DP master
 Exception – DP slaves that support S7 server functionality
SIMATIC NET Networking for Industry
(C) Siemens Energy&Automation, 2003, AMD
K. Reese Page 15