Prescient II Extinguishing
Control Panels
• Comprehensive facilities for gaseous
extinguishing systems
• Designed to BS 7273 Part 1
• Complies with EMC and LVD directives
• 1 minute actuator cut off operation
• Monitored actuator / solenoid release
• Zone isolate feature
• Common fire, fault relay facilities
• 1st & 2nd stage relay facilities
• Gas discharged and reset relay facilities
• Intrinsically safe barrier settings
Prescient II Extinguishing
Control Panels
•
Metron or solenoid compatible
•
Single or double knock operation
•
Pre-discharge delay adjustable from 0 to 8.5
minutes
•
Discharge indication with or without pressure
switch
•
Option for inhibit silence alarms when gas
imminent
•
Option for rapid buzzer pulse when gas
imminent
•
Semi-flush bezel and fully-flush cabinet
options
•
Membrane fascia with tactile switches
•
Easily removable chassis
Mechanical Assembly
Multiple earth termination
points located adjacent to
cable entries.
Display and motherboard
chassis are removable for
ease of wall mounting.
24V battery set.
Mounting points for the
Prescient motherboard
chassis.
Detection inputs and Alarm /
Actuator outputs
+
ALARM 1
ALARM
OUTPUTS
ALARM 2
SOUNDER
BELL
PRESCIENTII PANEL TERMINALS
C1657
+
-
-
SOUNDER
BELL
EOL
3k9
+
-
+
-
+
-
EOL
3k9
SOLENOID
1 +
ACT 2 +
-
C1565 SUPPRESSION
BOARD
ACT
ACTUATOR
OUTPUTS
DETECTOR
+
DETECTION
CIRCUITS
ZONE 1
ZONE 2 AUX. ZONE +
+
MANUAL RELEASE BGU
AUX. SUPPLY
+28V
0V
SOLENOID
C1565 SUPPRESSION
BOARD
BGU
EOL
3K9
3K9
EOL
DETECTOR
BGU
DETECTOR
EOL
3K9
MANUAL
RELEASE
SWITCH
3K9
EOL
680R
EXTERNAL SUPPLY
DRIVING BEAM DETECTORS ETC.
LOCK OF
SWITCHE
DISCHARGED
MANUAL
ABORTED
1 +
+
ACT 2 -
C1565 SUPPRESSION
BOARD
ACT
ACTUATOR
OUTPUTS
C1565 SUPPRESSION
BOARD
DETECTOR
+
DETECTION
CIRCUITS
ZONE 1
EOL
3K9
DETECTOR
Remote Connections
ZONE 2 AUX. ZONE +
+
MANUAL RELEASE -
BGU
AUX. SUPPLY
SOLENOID
+28V
0V
BGU
3K9
EOL
BGU
EOL
3K9
MANUAL
RELEASE
SWITCH
3K9
EOL
DETECTOR
680R
EXTERNAL SUPPLY
DRIVING BEAM DETECTORS ETC.
LOCK OFF
SWITCHES
DISCHARGED
MANUAL
ABORTED
AUTO
TIMER HELD
ZONE 1
ZONE 2
AUX. ZONE
MANUAL RELEASE
COMMON FAULT
EVACUATE
REPEATER OUTPUTS
FOR DRIVING REPEATER
INDICATION OR SMALL
RELAYS (100mA MAXIMUM).
680R
REPEATER
OUTPUTS
N/ C
N/ C
N/ C
REMOTE
INPUTS
REPEATER
INPUTS
TIMER
HOLD
SWITCH
SILENCE ALARMS
RESET
EVACUATE
0V
3K9
REMOTE CONTROL INPUTS
0V.
AUX. RESET RELAY CONTACT OPERATES FOR
3K9
3K9
N/ O
680R
N/ O
680R
LOCK OFF
0V
TIMER HOLD
0V
PRESSURE SWITCH
0V
LOW PRESSURE
0V
EMERGENCY ABORT
N/ O
680R
680R
LAMP UNIT
+28V
DISCHARGED
AUTO
MANUAL
TIMER HELD
ABORTED
3K9
LOCK OFF
0V
TIMER HOLD
0V
PRESSURE SWITCH
0V
LOW PRESSURE
0V
EMERGENCY ABORT
REMOTE
INPUTS
3K9
3K9
3K9
3K9
Relay Contacts
SILENCE ALARMS
RESET
EVACUATE
0V
REPEATER
INPUTS
REMOTE CONTROL INPUTS
0V.
AUX. RESET CONTACT
N/ C
POLE
AUX. RESET RELAY CONTACT OPERATES FOR
7.5 SECONDS AFTER THE PANEL HAS BEEN RESET.
AUX. FAULT
N/ O
POLE
N/ C
COMMON FAULT RELAY CONTACTS (FAIL SAFE)
OPERATE IN ANY FAULT CONDITION
(SHOWN IN ENERGIZED STATE).
CONTACT
AUX. FIRE CONTACT
POLE 1
N/ O 1
N/ C 1
N/ C 2
POLE 2
N/ O 2
COMMON FIRE RELAY
CONTACTS OPERATING
ON ANY FIRE.
DISCHARGE CONTACT
POLE
N/ O
DISCHARGE RELAY
CONTACTS OPERATING
ON DISCHARGE
1st STAGE CONTACT
POLE 1
N/ O 1
N/ C 1
POLE 2
N/ C 2
FIRST STAGE RELAY
CONTACTS OPERATE ON
FIRST STAGE ALARM.
DIL SWITCH DETAILS F
ENGINEER SETTINGS
ALM 1 F/ STAGE, ALM
ALARMS F/ STAGE PU
ALARMS S/ STAGE PU
M/ RELEASE INSTANT
INHIBIT S/ ALARM GA
BUZZER PULSES END
EVAC OPERATES FIR
LATCHING FAULTS
BELL
SUPRESSION
DETAILS
+
-
ONE MAN TEST
SEE MANUAL
ZONE 1 D/ KNOCK
ZONE 2 D/ KNOCK
ZONES I/ SAFE
NO P/ SWITCH
ACT S/ C DISABLE
2 X DELAY
IN4002
2nd STAGE CONTACT
BATTERY
THERMISTOR
POLE 1
N/ O 1
N/ C 1
POLE 2
N/ C 2
+
+28V
I/ P
SECOND STAGE RELAY
CONTACTS OPERATE ON
SECOND STAGE ALARM.
STANDBY BATTERIES
DIL SWITCH DETAILS F
DISCHARGE TIMER
IN4002
TO PANEL
ALARM
CIRCUIT
ONE SECOND DELAY
2 SECOND DELAY
4 SECOND DELAY
8 SECOND DELAY
16 SECOND DELAY
32 SECOND DELAY
64 SECOND DELAY
128 SECOND DELAY
Panel Configuration Options
•
One-Man Test
•
Earth Fault Monitoring Enable/Disable
•
Zone 1 Double Knock
•
Zone 2 Double Knock
•
Zener Barrier Thresholds
•
Pressure Switch Used/Not Used Option
•
Actuator Short Circuit Enable/Disable
•
0 to 8 minutes 30 seconds Timer Delay
•
Manual Release Gives Instant Discharge
•
Inhibit Silence Alarms During Gas Imminent
•
Buzzer Rapid Pulse 15 Seconds Before Discharge
•
Evacuate Operates Aux. Fire Relay
•
Latching Fault Indications
•
Motherboard link to switch off actuator output after 1 minute operation
Alarm Circuit Options
•Alarm1 First Stage, Alarm2 Second Stage
•Either - Alarm Circuit 1 operates for a first stage
alarm condition and a second stage alarm condition.
•Or - Alarm Circuit 2 operates only for a second stage
alarm condition.
•Alarms Continuous in First Stage
•Either - Alarm Circuits 1 and 2 pulse for a first stage
alarm condition
•Or - Alarm Circuits 1 and 2 are continuous for a first
stage alarm condition
•Alarms Continuous in Second Stage
•Either - Alarm Circuits 1 and 2 pulse for a second
stage alarm condition.
•Or - Alarm Circuits 1 and 2 are continuous for a
second stage alarm condition
User Controls
The Prescient panel has clear, unambiguous
fire and extinguishing system status LED
indications.
Fire status LED
indications.
Extinguishing
system LED
indications.
These single-function
user controls are easy
to operate.
Keyswitch to
enable user
controls
Status Indicators
Two types of status indicators are available in small, matching
enclosures.
 status indicator with auto/manual keyswitch
 status indicators with manual release and auto/manual keyswitch,
abort and timer hold
Weatherproof status
indicators are also available
(not illustrated).
LC250 Weight Monitor
The LC250 Weight Monitor is
designed to detect and
indicate leakage from
extinguishant cylinders.
Easy to configure controller
links up to 4 weigh monitors
and may be linked to
extinguishant control panel
to provide fault indication in
the event of extinguishant
leakage.
No need for mechanical
assemblies which take up
space.
Solid state electronic weight
monitors with no moving
parts ensure simple
installation with reliable