Transcript FUSEOLOGY

Sistemas Eléctricos Industriales
Coordinación Selectiva de los elementos de protección
Referencia: http://www.bussmann.com
•Definiciones
•Coordinación con fusibles
•Coordinación con interruptores
•Ejemplo de coordinación en una planta industrial
Presentado por: Jesús A. Baez M.
ITESM, Departamento de Ingeniería Eléctrica
Monterrey, NL
Octubre 2007
© 2001 Cooper Bussmann, Inc.
Selective Coordination
Definition:
The act of isolating a faulted circuit from the
remainder of the electrical system, thereby
eliminating unnecessary power outages. The
faulted circuit is isolated by the selective operation
of only the overcurrent protective device closest to
the overcurrent condition.
© 2001 Cooper Bussmann, Inc.
Selective Coordination: Avoids Blackouts
Without Selective Coordination
With Selective Coordination
OPENS
NOT AFFECTED
OPENS
UNNECESSARY
POWER LOSS
NOT
AFFECTED
Fault
Fault
Selective Coordination: NEC®
240.2 Definitions
Coordination.
The proper localization of a fault condition to
restrict outages to the equipment affected,
accomplished by the choice of selective
fault-protective devices.
© 2001 Cooper Bussmann, Inc.
Selective Coordination: Normal Supply
Normal
Source
Emergency
Source
N
E
ATS
© 2001 Cooper Bussmann, Inc.
Selective Coordination: Normal Supply
Normal
Source
Emergency
Source
Unnecessary Feeder Outage
N
Fault
X1
E
ATS
Opens
Not Affected
Unnecessary
Power Loss
© 2001 Cooper Bussmann, Inc.
Selective Coordination: Normal Supply
Without
Normal
Source
Emergency
Source
Unnecessary Main Outage
N
Fault
X1
E
ATS
Opens
Not Affected
Unnecessary
Power Loss
© 2001 Cooper Bussmann, Inc.
Selective Coordination: Normal Supply
Without
With
Normal
Source
Emergency
Source
N
Fault
X1
E
Normal
Source
Emergency
Source
N
ATS
E
ATS
Opens
Not Affected
Unnecessary
Power Loss
© 2001 Cooper Bussmann, Inc.
Selective Coordination: Normal Supply
Without
With
Normal
Source
Emergency
Source
N
Fault
X1
E
Normal
Source
Emergency
Source
N
ATS
Opens
Not Affected
Unnecessary
Power Loss
E
ATS
Isolated to
Branch Only
Fault
X1
© 2001 Cooper Bussmann, Inc.
Selective Coordination
Circuit Breaker Coordination
© 2001 Cooper Bussmann, Inc.
Coordination - Thermal-Mag Circuit Breakers
Thermal Magnetic Molded
Case Circuit Breaker TimeCurrent Curve

Overload Region
Instantaneous
Region
Interrupting Time
Unlatching Time
Interrupting
Rating
© 2001 Cooper Bussmann, Inc.
Coordination - Thermal-Mag Circuit Breakers (See SPD)
400A
90A
No se tiene selectividad para corrientes
de corto circuito en este rango
© 2001 Cooper Bussmann, Inc.
Selective Coordination
D
Time
C
B
A
4000A Fault
Current
© 2001 Cooper Bussmann, Inc.
Lacking Coordination
OPENS
NOT AFFECTED
UNNECESSARY
POWER LOSS
Fault
© 2001 Cooper Bussmann, Inc.
Selective Coordination - Insulated Case Circuit Breakers (See SPD)
2000A Insulated Case
Circuit Breaker
 STD Is an Option - Allows
breaker to delay opening
 Instantaneous Override
built-in: may be as low as
12X the breaker rating
 Will often result in lack of
coordination

© 2001 Cooper Bussmann, Inc.
Selective Coordination - Insulated Case Circuit Breakers (See SPD)
2000A Insulated Case with STD and
Instantaneous Override and 100A Molded Case
Thermal Magnetic Circuit breaker - NO
Coordination in Short-Circuit Region (above
21,000A)

2000A
100A
© 2001 Cooper Bussmann, Inc.
Selective Coordination - LV Air Power Circuit Breakers (See SPD)
Short
Time Delay - Allows the fault
current to flow for up to 30 cycles.
Used
to coordinate with downstream
Subjects
equipment to high
mechanical and thermal stresses, often
violating 110.10
Arc
Flash/ Blast Risks Much
Higher
High
Cost, Larger Equipment
© 2001 Cooper Bussmann, Inc.
Selective Coordination: Fuses
© 2001 Cooper Bussmann, Inc.
Selective Coordination:Fuses (See SPD)
Time Current
Curves
© 2001 Cooper Bussmann, Inc.
Selective Coordination:Fuses (See SPD)
Selectivity Ratio
Guide Based on
Thermal Principle
Based on I2t
Not Melt
Clear
I2t melting > I2t Clearing
1200 A
600 A
© 2001 Cooper Bussmann, Inc.
Selective Coordination (See SPD )
Line Side Fuse
Load Side Fuse
LOW-PEAK® : LOW-PEAK®
2:1 Line:Load Ratio
Selectivity Ratio Table Assures Coordination!
No Plotting required!
© 2001 Cooper Bussmann, Inc.
Selective Coordination - Fuses
480V, 3 phase
Example:
Main: KRP-C 1200 SP
Feeder: LPS-RK 200 SP
Branch: LPS-RK-30 SP
1200 A
MS
B
GFP
200 A
MCC
30 A
© 2001 Cooper Bussmann, Inc.
Selective Coordination - Fuses
Use Selectivity Table
Main
KRP-C 1200 SP
Feeder
LPS-RK 200 SP
Branch
LPS-RK 30 SP
What happens: Branch Circuit Isca = 5000 A or
50,000A or 300,000A ?
© 2001 Cooper Bussmann, Inc.
Selective Coordination- Fuses
Lineside KRP-C 1200SP to Loadside LPS-RK 200SP
1200/200 = 6:1
Table only need 2:1
Selective Coordination
Lineside LPS-RK 200SP to Loadside LPS-RK 30SP
200/30= 6.67:1
Table only need 2:1
Selective Coordination
© 2001 Cooper Bussmann, Inc.
Selective Coordination
NOT
AFFECTED
OPENS
Fault
© 2001 Cooper Bussmann, Inc.
Are These Selectively
Coordinated?
Low Peak
KRP-C 1000 SP
Low Peak
LPJ 200 SP
Low Peak
LPJ 20 SP
Fault
10000 Amps
© 2001 Cooper Bussmann, Inc.
Are These Selectively
Coordinated?
Selectively Coordinated
Low Peak
KRP-C 1000 SP
Low Peak
KRP-C 1000 SP
Low Peak
LPJ 200 SP
Low Peak
LPJ 20 SP
Fault
10000 Amps
Low Peak
LPJ 200 SP
NOT
AFFECTED
Low Peak
LPJ 20 SP
OPENS
Fault
10000 Amps
© 2001 Cooper Bussmann, Inc.
Are These Selectively
Coordinated?
1000 A. CB
IT @ 10 X
200 A. CB
IT @ 10 X
20 A. CB
IT @ 10X
Fault
10000 Amps
© 2001 Cooper Bussmann, Inc.
Are These Selectively
Coordinated?
Not Coordinated
1000 A. CB
IT @ 10 X
1000 A. CB
IT @ 10 X
200 A. CB
IT @ 10 X
200 A. CB
IT @ 10 X
20 A. CB
IT @ 10X
NOT
AFFECTED
20 A. CB
IT @ 10X
OPENS
Fault
10000 Amps
Fault
10000 Amps
© 2001 Cooper Bussmann, Inc.
The Issue:
Lack of coordination
takes out other loads
1000 A. CB
IT @ 10 X
200 A. CB
IT @ 10 X
Unnecessary
Blackout
OPENS
20 A. CB
IT @ 10X
Fault
10000 Amps
© 2001 Cooper Bussmann, Inc.
Ejemplo de coordinación mostrando protección de los cables
© 2001 Cooper Bussmann, Inc.