“Selecting a Cx Provider”
Committee Proposal
CCC will add 3 sections to its web site:
Section 1: How to select a Cx provider
Section 2: Provider profiles
Section 3: Sample Cx Documents
2
Section 1: How to Select a Cx Provider
A. What to consider when selecting a Cx provider
B. Recommended provider qualifications by project
size/complexity:
• New Building: Abbreviated, Standard, Complex
• Existing Building
C. Information on available certifications
3
Recommended Provider Quals: New Building Cx
CP
Qualifications
1. Current technical knowledge and extensive recent
hands-on field experience regarding:
a. Building System Commissioning including design
review, construction observation, system testing, and
post-occupancy evaluations;
b. Building system performance and interaction with a
focus on the building automation control systems;
c. Common installation, maintenance and operational
pitfalls for the commissioned systems;
d. The building design and construction process
2. Experience troubleshooting commissioned systems
3. CP for at least two (2) other commissioning projects
of a similar nature
4. Contractually, the CP should be able to provide an
objective and unbiased point of view. If the CP will be
from the owner or the contractor's company, they
should not hold other responsibilities related to this
project.
1. Current technical knowledge and extensive recent
hands-on field experience equal to that of a
Professional Engineer regarding:
a. Building System Commissioning including design
review, construction observation, system testing, and
post-occupancy evaluations;
b. Building system performance and interaction with a
focus on the building automation control systems;
c. Common installation, maintenance and operational
pitfalls for the commissioned systems;
d. The building design and construction process
2. Experience troubleshooting commissioned systems;
3. CP for at least four (4) other commissioning
projects of a similar nature
4. Experience in related fields, such as design,
construction, and building operations
5. Contractually, the CP should be able to provide an
objective and unbiased point of view. If the CP will be
from the owner or the contractor's company, they
should not hold other responsibilities related to this
project.
1. Current technical knowledge and extensive recent
hands-on field experience equal to that of a
Professional Engineer regarding:
a. Building System Commissioning including design
review, construction observation, system testing, and
post-occupancy evaluations;
b. Building system performance and interaction with a
focus on the building automation control systems;
c. Common installation, maintenance and operational
pitfalls for the commissioned systems;
d. The building design and construction process
2. Five years experience troubleshooting
commissioned systems;
3. CP for at least four (4) other commissioning
projects of a similar nature
4. Experience in related fields, such as design,
construction, and building operations
5. Contractually, the CP should be able to provide an
objective and unbiased point of view. Unless the
owner or construction manager is particularly skilled in
commissioning HVAC and electrical installations, the
CP should be an independent third party
4
Recommended Provider Quals: Existing Building Cx
CP Qualifications
(Retrocommissioning)
1. Current technical knowledge and extensive recent hands-on field
experience equal to that of a Professional Engineer regarding:
a. Building Retrocommissioning including functional testing,
diagnostics, trending, energy calculations, and implementing
improvements
b. Building system performance and interaction with a focus on the
building automation control systems;
c. Common installation, maintenance and operational pitfalls for the
commissioned systems;
2. Five years experience troubleshooting commissioned systems;
3. CP for at least two (2) other commissioning projects of a similar
nature
4. Experience in related fields, such as design, construction, and
building operations a plus
5
Cx Provider Certification Programs
A. Information about each of the certification programs
B. Contact info/website link for each program
C. Programs to be included:
• AABC Certified Cx Agent
• AEE Certified Building Cx Professional
• BCA Certified Cx Professional
• NEBB Systems Cx Administrator
• UWM Accredited Qualified Cx Provider
6
AABC: Certified Cx Agent
AABC: Certified Cx Agent
Individual and Firm Certification
Prerequisites: 3 Cx Projects
Must be a member of AABC
Must be a Test Balance Engineer
AND either of the two following tracks:
Professional
Field
Degree
PE/RA or BS Engineer No college degree
Experience 3 years TAB technician 10 Years TAB work
References N
N
Exam
Required
Required
• Two candidate tracks: professional and field.
• The firm is certified
7
AEE: Certified Building Cx Professional
AEE: Certified Building Cx Professional
Individual Certification
Prerequisites:
None
Need not join AEE
AND one of the four following tracks:
Professional
PE/RA or BA/BS*
Degree
Building Science
Building Related Experience 3 years
References
N
Certification
N
Exam
Required
Mixed
Tech AA/Nontech BA
5 years
N
N
Required
Field
Certification
N
10 years
N
N
Requried
N
N
N
CEM
Required
• No experience necessary if a Certified Energy
Manager (CEM)
• Building-related education and experience
definitions are broad
• No membership requirement
8
BCA: Certified CX Professional
BCA: Certified Cx Professional
Individual Certification
Prerequisites:
3 Projects as Lead Cx Provider
Need not join BCA
AND one of the three following tracks:
Professional
Mixed
Field
Degree
BA/BS Building SciencesTech AA/Non-tech
N BA
Building Related Experience
3 years
5 years
12 years
Cx Experience
3 years continuous
3 years (same) 3 years (same)
References
Yes: 3+ from clients
Y (same)
Y (same)
Exam
Required
Required
Requried
• Joining BCA not required
• Requires client and project references
9
NEBB: Systems Cx Administrator
NEBB: Systems Cx Administrator
Firm Certification
Prerequisites:
Firm needs to join NEBB
Individual needs to pass TAB exams
AND one of the three following tracks:
Professional
Mixed
Field
Degree
BA/BS Engineering
Tech AA/Non-tech BA
N
Building Related ExperienceN
N
4 years (TAB tech)
Cx Experience
2 years (TAB supervisor)4 years (TAB suprvsr)
4 years (TAB suprvsr)
References
Yes (for firm to join NEBB)
Yes (same)
Yes (same)
Exam
Required
Required
Requried
• Only TAB-related experience required
• Two modules: HVAC and Plumbing
• Adding fire protection module in 2005
10
UWM: Accredited Qualified Cx Process Provider et al.
UWM Certification Title
Highest


Lowest
Entrylevel?
Accredited Cx Process Authority Professional N
(CxAP)
Accredited Cx Process Manager (CXM)
N
Accredited Cx Process Technical Support
N
Provider (CxTS)
Accredited Qualified Cx Process Provider
Y
(QCP)
Conditi Advan
onal?
ced?
Y
Y
Y
Y
Y
Y
N
N
• Entry-level accreditation (QCP) is available for those
without experience.
• As one passes from CxTS through CxAP, requirements
increase
• Conditional certifications until experience level is met
11
UWM: Accredited Qualified Cx Process Provider et al.
UWM: Accredited Qualified Cx Process Provider et al.
Individual Certification
Prerequisites:
2 Projects as Lead Cx Provider
Must attend 5-day classes
No membership requirement
Choose one of the four certification paths:
QCP
CxTS
CXM
CxP
Proof of practice as Cx authority N
Per ASHRAE Guideline 0 Per ASHRAE
Per ASHRAE
Proof of primary Cx authority
N
2 projects
2 projects
2 projects
Owners' project letters
N
2 letters
2 letters
2 letters
Cx process
N
N
1 plan
1 plan
CxP report
N
N
1 report
1 report
Owner's workshop
N
N
Project intent
Project intent
Owner's workshop
N
N
Lessons learned Lessons learned
Endorsement by Cx professionals N
N
N
2 letters
Examination
Required Required
Required
Required
• QCPs need only take course and exam to qualify
• CxTS and CxTM similar to CxP, but less exhaustive
• Candidates passing exam but not meeting all reqs
are given conditional status
12
Section 2: Provider Profiles
Providers submit:
A. Form with basic information
• Will be used to help users compare firms and
easily seek further information
B. Link to Cx Provider website
C. The following six documents (some will be optional):
• Scope of work
• Design Intent Document
• Cx Plan
• Issues Log
• Cx Final Report • Systems Manual
13
2. Form for providers
In addition to contact info and a URL, the form requests:
A. Firm description
• # of employees
• # years offering Cx services
• Average # of Cx projects/year
B. Commissioning activities
• Cx and/or RCx
• Systems or technologies
• Building types
14
Section 3: Sample Documents
CCC will also post to its web site:
A. Samples of each of six requested documents
B. Sample Cx and RCx RfQ and RfP
15
Sample Cx Documents
A. PECI has compiled an initial list of sample
documents.
• Sources include EDR, DSA, PECI
B. A committee is needed to evaluate sample
documents and make final decisions
16
Sample Cx Documents
Cx
Scope of
Work
Cx Plan
Design
Intent
Issues Log
Final Report
Systems
Manual
Document
“Statement of Work: Commissioning Authority Services”
for a 65,000 sq ft. government laboratory in CO, 2002
“Model Commissioning Phase Plan,” 1998
“Commissioning Plan – Construction Phase: A Healthcare
Facility”
“Commissioning Plan Outline Template”
“CUSD Administrative Facility: Basis of Design,” 2002
Attribution
PECI/NREL
Type
Sample
MP&GS
EDR
Sample
Sample
EDR
DSA
Template
Sample
“CUSD Administrative Facility: Project Intent,” 2002
“Design Intent and Basis of Design of Energy and Comfort
Related Systems,” 1998
“Owner’s Operating Requirements,” 2004
“Design Issues Log” for a 20,000 sq. ft. administrative and
morgue space in TN, 2002
“Final Commissioning Report” for an admin/morgue space
Kaiser Salmon Creek
Kaiser Interstate South
“Systems Manual”
DSA
MP&GS
Sample
Template
PECI RCx Program
PECI
Template
Sample
PECI
PECI
PECI
PG&E
Sample
Sample
Sample
Sample
“Sequence of operations”
Functional Test
Guide, PIER
Design Guide,
PIER
DSA
DSA
Sample
EDR
EDR
Template
Template
“Points list”
RFQ
RFP
“System Manual Scope of Work,” 2002
“Commissioning Authority Services Request for Quals,”
2002
“Request for Proposal – Long form”
“Request for Proposal – Short form”
Sample
Sample
Sample
17
Sample RCx Documents
RCx
Scope of
Work
Cx Plan
Issues Log
Final
Report
Systems
Manual
RFQ
RFP
Document
“Scope of Work,” 2004
Attribution
PECI/SDRCx Program
Type
Sample
“Sample Retrocommissioning Plan,” 1998
“Existing Building Commissioning”
“Issues Log,” 2004
“Final Retrocommissioning Report” for a
commercial building in San Diego, 2002
As above
MP&GS
PECI
PECI/SDRCx Program
PECI/Allied Plaza
Sample
Sample
Template
Sample
“Request for Commissioning Provider
Qualifications,” 2004
“Request for Proposal Checklist for
Retrocommissioning Services,” 2003
PECI/SDRCx Program
Sample
NYSERDA
Template
18