Transcript Document

REFRIGERATION, COMPRESSED AIR SYSTEMS & EFFICIENT USE OF ENERGY

1

Principles of Refrigeration

Refrigeration means to COOL AN OBJECT BELOW ITS SURROUNDING TEMPERATURE 2

Vapour Compression Cycle

Basic Components of the vapour compression refrigeration system

3 CONDENSER • Compressor • Condenser • Throttling Device • Evaporator EXPANSION VALVE 4 EVAPORATOR 2 COMPRESSOR 1 3

PRESSUR KN/m2 E

Vapour Compression Cycle

CONDENSER HEAT REJECTION Pd Pe 4 3 THROTTLING CONDENSATION EVAPORATION COMPRESSION 2 1 3 CONDENSER 2 EXPANSION VALVE 4 EVAPORATOR COMPRESSOR 1 ENTHALPY KJ/Kg REFRIGERATION EFFECT WORK DONE 4

VAPOUR COMPRESSION CYCLE COMPONENTS

5

REFRIGERANTS

CHLOROFLUOROCARBONS (CFC)

R-11

R-12 HYDROCHLOROFLUOROCARBONS (HCFC) R- 22 R-123 HYDROFLUOROCARBONS (HFC) R-32 R-125 R-134a R-143a INORGANIC COMPOUNDS R- 717 R- 718 R- 729

6

Unit of Refrigeration The unit of refrigeration is

TON OF REFRIGERATION ( TR )

1 TR = 12’000 Btu/hr

BRITISH UNITS

1 TR = 3.517 KW

SI UNITS 7

Refrigeration Cycle Efficiency

The refrigeration cycle efficiency is known as

COEFFICIENT OF PERFORMANCE (COP REF ) (COP REF )

= Refrigeration Effect Work Done KJ/Kg KJ/Kg

(COP HP )

= Condenser Heat Rejection KJ/Kg Work Done KJ/Kg 8

Refrigeration Equipment Efficiency

The equipment efficiency is given as EER or kW/TR

ENERGY EFFICIENCY RATIO (EER) Use for smaller capacity equipment such as Window type & Split type equipment (EER)

= Capacity Btu/hr Power Input Watts

kW/TR Use for large capacity equipment such as Chillers (kW/TR)

= Power Input Capacity TR kW 9

P-h DIAGRAM FOR REFRIGERANT 134a

10

MONTRÉAL PROTOCOL OBLIGATIONS 1.

2.

3.

Face-out of CFC in year 2005 Introduction of Quota for HCFC in year 2015 Face-out of HCFC in year 2040

11

ASHRAE Standard 34-1992 Refrigerant Safety Classifications

Higher Flammability Lower Flammability No Flame Propagation

Group A3 Group B3 Group A2 Group B2 Group A1 Group B1

Lower Toxicity

INCREASING TOXICITY

Higher Toxicity

12

Refrigerant Data & Safety Classifications REFRIGERANT CHEMICAL FORMULA CHEMICAL NAME

R-11 R-12 R-22 R-134a R-717 CCl 3 CCl 2 F 2 CHClF 2 CH 2 FCF 3 NH 3 Trichlorofluoromethane Dichlorodifluoromethane Chlorodifluoromethane 1,1,1,2-tetrafluoroethane Ammonia

REFRIGERANT SAFETY CLASSIFICATION

A1 A1 A1 A1

AMOUNT OF REFRIGERANT PER OCCUPIED SPACE (ppm)

4’000 40’000 42’000 60’000

TLV-TWA (ppm)

C1’000 1’000 1’000 1’000 B2 500 25 13

AMMONIA (NH3) R-717

• • • •

In-expensive Refrigerant best suited for industrial use Higher refrigeration effect 474 Btu/lb, comparison; R-12 = 50 Btu/lb , R-22 = 70 Btu/lb, R-134a = 64 Btu/lb, R-404A = 48 Btu/lb

7- times higher refrigeration effect!!!

Specific volume of suction gas is high 8 ft 3 /lb compare to 1.2 ft 3 /lb of R-22, needs larger pipes, compressors Higher delivery temperatures 210 ºF, needs water cooled heads for compressor

14

COOLING TOWER (CT)

INDUCED DRAUGHT

15

COOLING TOWER (CT)

CROSS FLOW

16

COOLING TOWER (CT)

FORCED DRAUGHT

17

WATER PUMPS

VERTICAL IN-LINE

18

FAILURES

DETECTION OF SIMPLE FAILURES

 Refrigeration Plant should function properly, if the following checks are OK.

  At a glance • Suction sweat • • • Warm liquid line & clear sight glass from bubbles Condenser outlet air warm Condenser water in & out has significant feel of temp deference Using measuring equipment • Manifold Gauge Set - measure the pressure of refrigerant • Clip-on Ammeter - measure the current flow and voltage • Sling Psychrometer - measure the dry bulb & wet bulb temp.

• Anemometer - measure the air flow 19

FAILURES

DETECTION OF SIMPLE FAILURES …cont.

Detection by observation - A/C unit malfunction if the following observations are found • Sweating down stream of the Filter/dryer – Filter Block • • Ice build up at compressor comp. valves – Over Charge, damaged Ice build up at evaporator – Under charge, gas leak, air filter clogged, cooling coil blocked, fan belts are loose • Bubbles in the sight glass filter/drier lack of refrigerant or blocked • Oil drops near refrigerant pipe fittings, components etc. – Refrigerant leaks in the system.

• Condenser shell cooler & evaporator shell warmer (Centrifugal Chiller) – at low condensing temperatures, refrigerant migrates to evaporator 20

COMPRESSED AIR SYSTEMS

21

Compressed air system provides……..

    Provides air under compression to pneumatic drives Use reciprocating or screw compressors with storage receiver Use pressure regulators at the air user point to reduce the air pressure Use water separators to prevent water vapour entering the air user equipment 22

ROTARY SCREW COMPRESSORS

 Pulsation free air  100% continuous duty  Quiet operation  Energy efficient at full load  Extended service intervals  Reliable long life  Improved air quality 23

TIPS FOR COMPRESSED AIR SYSTEMS

 Locate the compressor closest to the largest air user to reduce pressure drop through the air line  Ventilate the compressor well   Keep 3 feet around the compressor unit Surrounding temperature should be below 115 ºF  Avoid extreme humidity  Keep air filters clean all the time  Use refrigerated and desiccant dryers to reduce water vapour concentration 24

EFFICIENT USE OF ENERGY

Resources are limited and conserve energy Refrigeration   Reduce heat transfer Select energy efficient equipments Compressed air systems      Fix all leaks in the piping Regulate lowest pressure at air user Reduce blow-offs Shut-off air supply to off-line air users Consider multi staged compressors 25

THANK

26