IQ Analyzer 6400/6600 Series

Cutler-Hammer Power Management Products High End Metering Capabilities

Power Quality Monitoring

• Over 150 metered parameters for comprehensive diagnostics • Assess trends, harmonics and waveforms to prevent process disruptions and equipment damage • Isolate and diagnose power quality problems by analyzing historical metered data • Control energy usage and costs via measurement, on-board data storage and time-of-use registers

IQ Analyzer

Overview

      Revenue metering accuracy  ANSI C12.16 ( 1% )  ANSI C12.20 ( 0.5% )  IEC 687 / Canada ( 0.5% )  Independent certification Time Of Use Registers Expanded event storage UL/CUL/CE/CSA New Display & Faceplate 4 Custom Display Screens

IQ Analyzer Key Features

• High-speed waveform capture – Programmable event triggers – 2 cycles @ 128 samples/cycle & 6 cycles @ 32 samples/cycle – 11 channels of voltage & current information are saved – Local display of waveform (6600 series only) • Measures current and voltage through 50th harmonic – Display harmonic spectrum on local display (6600 series only)

Sample Waveforms

Sample Waveforms

Sample Waveforms

IQ Analyzer Key Features

• CBEMA/ITIC event display via PowerNet • dv/dt trigger captures subcycle voltage disturbances (6600 series only) • Communication flexibility: – INCOM via IPONI – Ethernet via EPONI & EPONIF – Web Pages via WebPONI – Modbus via MPONI (Coming Soon!)

IQ Analyzer Key Features

• The IQ Analyzer stores 44 different minimum & maximum values including: – Current – Voltage – Power – Power Factor – Frequency – THD

IQ Analyzer Key Features

• On-board event data logging • Auxiliary I/O capabilities – Analog Outputs (4) 0-20mA/4-20mA 1% accuracy • Added 4th output at the end of 2001 – Analog Input (1) 0-20mA/4-20mA 1% accuracy – Digital Inputs (3) optically isolated +30Vdc – Digital Outputs (4) Form C contacts 10A @ 240Vac

IQ Analyzer Key Features

• Monitors L-L, L-N, L-G and N-G voltage – PT ratios from 1:1 to 5,000:1 • Monitors phase, neutral and ground current – CT ratios from 5:5 to 10,000:5 – Up to 40A continuous, 300A for 1 second • Measures % Total Harmonic Distortion (THD) for current and voltage

New Features

• New Trending Capabilities – 4 Independent trends – Up to 6 parameters per trend – Can chose from over 94 parameters – Total of 90K bytes of storage • Single parameter every 15 min. for 234 days – Independent memory allocation for each trend – Used with PowerNet for CBEMA/ITIC curve plotting utility

CBEMA Curve Utility

New Features

• New Trending Capabilities – Sampling rate can be set from 8 cycles to 5040 minutes (3 1/2 days) – Trend 1-3 can save data on a discrete input – Trend 4 can save data on an event – If the time period is set for an integer divisor of 60 the period starts at the next full hour.

New Features

• Data Logging Features – Time & Reason for last 504 Events – Any meter event is saved – New Status Change Indicators • Time of Alarms • Power Up • Resets • Setting Changes • INCOM Connection

New Features

• In addition to the data logging of the last 504 events last 10 Waveform Events are also stored • The real time clock can be synchronized to the line to correct for long term errors (w/o PowerNet) • Programmable CT Polarity Setting – Change CT polarity from calibration menu – Last event under “Power Factor”

New Features

• Time Of Use (TOU) Energy Registers – 32 Schedules • 8 Weekday • 8 Saturday • 8 Sunday - 8 Holiday - 8 Seasons – Each schedule can change 9 times a day – 4 Different utility rates – Watt-hours, VAR-hours, VA-hours recorded

New Features

• TOU Demands – Amps, Watts, VARS & VA

Improvements

• New Case – Polycarbonate for higher durability & temperature – Rugged outer edge – Reset button changed from red to blue • New Display – Reverse mode, LED backlit LCD – Yellow on black – High reliability

Improvements

• Custom Screen Enhancements – Allows programming of 7 parameters per screen – Now 4 custom screens – List of programmable items extended • Clock • Min/Max Values since last trend • Magnitude THD (V and A) – Displays each screen for 5 seconds

New IQ Analyzer

• Old IQA6000/6200 catalog numbers replaced with new 6400/6600 series – IQA6410 - Separate Source PS – IQA6420 - DC PS – IQA6430 - Self Powered Three Phase PS – IQA6610 - Separate Source PS w/waveform – IQA6620 - DC PS w/waveform – IQA6630 - Three Phase PS w/waveform

Documentation

• Color Brochure – B.17C.01.S.E

• Technical Data Sheet – TD.17.02A.T.E

• Sales Notes – SN.17C.03A.S.E

• Instruction Book – TD17530D

IQ Analyzer 6600 Portable

New Portable IQ Analyzer

• New portable will be based upon the IQ Analyzer 6600 • Waveform capture • On board data trending – New CT connectors – Both INCOM & RS-232 communications – New battery power supply – New heavy duty case with lead storage – Can be used with PowerPort – Optional clamp on CT’s

Portable IQ Analyzer

Portable IQ Analyzer

• Three new optional multi-ratio clamp-on CT’s: – 150/300/600 Amp – 500/1000/1500 Amp – 1000/2000/3000 Amp