Transcript File - Kensa Heat Pumps
Kensa Heat Pumps
Follow on training
Agenda
Introduction
Heat Pump Operation
Application
Design/MCS/ Pricing
Ground Arrays – unrolling and purging
Simple diagnostics and fault finding
Q&A, product viewing
Lunch
www.kensaheatpumps.com
Heat Pump Cycle
www.kensaheatpumps.com
3
Heat Pump Performance
www.kensaheatpumps.com
The efficiency of a
heat pump is
mainly governed
by the outlet
temperature
4
Heat Pump Performance
www.kensaheatpumps.com
Inlet temperature also can have an affect on COP
5
Heat Pump Efficiency
www.kensaheatpumps.com
Real-life efficiency is expressed as a SPF (Seasonal Performance Factor) which is a very
complex calculation and is influenced by numerous factors quite distinct from the heat
pump performance.
Kensa’s heat pumps use Copeland scroll compressors, the most advanced available,
and capable of providing the best available performance.
Branding of the heat pump is not the critical factor in determining performance.
Factors linked to the property and the site are far more influential.
Ability to highlight the impact of some of these factors is helpful in gaining credibility
with the client.
6
6
www.kensaheatpumps.com
Domestic Heat Pumps
R407C
R134a
Size
Compressor
Size
Compressor
4kW
Single
3.5 kW
Single
6kW
Single
4.3kW
Single
8kW
Single
6kW
Single
10kW
Single
7kW
Single
12kW
Single
8.5kW
Single
12kW
Twin
10kW
Single
16kW
Twin
12kW
Twin
20kW
Twin
17kW
Twin
24kW
Twin
20kW
Twin
30kW
Twin
Single Compressor internals
www.kensaheatpumps.com
Twin Compressor Internals
www.kensaheatpumps.com
Hybrid Heat Pumps
www.kensaheatpumps.com
Single Phase Twin Compressor
R407C and R134a
15kW and 21kW
10
Shoebox Heat Pumps
www.kensaheatpumps.com
11
Plant Room Modules
www.kensaheatpumps.com
20 to 75 kW per module.
Combinations up to 1 MW and
beyond
15
Application
Application is critical
If a heat pump fails we can fix it, but if the application is wrong........
www.kensaheatpumps.com
Application - Exercise
Points to consider when installing a GSHP
i.e. Type of fuel replacing
www.kensaheatpumps.com
Application
How well insulated is the building?
What type of heating?
What fuel are we displacing?
Floor Construction.
Amount of glazing.
Noise issues.
Available heat source.
www.kensaheatpumps.com
Insulation
www.kensaheatpumps.com
The better you insulate your building : The lower the flow temperature required by the underfloor heating system to
reach your target temperature
Therefore, the less the heat pump has to raise the temperature
And the more efficient the heat pump!
The better you insulate your building, the more efficiently the heat
pump will operate.
19
The better insulated the building
www.kensaheatpumps.com
Smaller the heat pump required
The less the digging/drilling required
Lower the capital cost
Lower the building’s carbon emissions
Lower the energy bill
20
Heating Distribution Methods
www.kensaheatpumps.com
Underfloor
Ideal, large emitting area therefore low input temperatures.
Beware floor coverings and method of installation which might
require the heat pump to operate at higher temperatures.
21
Heating Distribution Methods
www.kensaheatpumps.com
Radiators
Need a higher temperature than underfloor due to the lower heat
emitting area.
Might need oversized radiators as maximum temperature from
the heat pump is approx. 50C.
22
Mixing radiators and underfloor
www.kensaheatpumps.com
Some want radiators upstairs, and underfloor downstairs
Can this be done?
Yes
Depending on the floor construction, the temperature required by the
radiators can be the same as the underfloor system!
There is a delay between the radiators and underfloor feeling warm.
Zone valves are generally required.
23
DHW Production
www.kensaheatpumps.com
25
Secondary Returns
www.kensaheatpumps.com
Standard secondary returns cause the cylinder
temperature to drop and due to the low
temperature nature of heat pumps this
temperature drop cannot be recovered
26
www.kensaheatpumps.com
DHW Cylinders
Single or Twin Coils
(Coil designed and sized for Heat Pump
applications)
3kW Immersion Heater
Expansion Vessel
G3 Kit
Stainless Steel tanks guaranteed for 25
years against leaks.
27
Inverted houses
www.kensaheatpumps.com
Bedrooms downstairs, living area upstairs.
Depends on floor construction.
Might need to run at higher temperatures and standard
rate electricity.
Glazing
www.kensaheatpumps.com
Beware high areas of glazing.
(even triple glazing only retains 1/3rd of the heat a solid wall does)
Will be cool in winter when cold ambient conditions.
Additional heating such as log burners.
Noise Issues
Keep the heat pump away from noise sensitive
areas.
Similar noise to an oil fired boiler or running
dishwasher.
Can install external to the building at the back of a
garage or in a lean to.
www.kensaheatpumps.com
Buffer Vessels
www.kensaheatpumps.com
Fitted to avoid short-cycling, i.e. which is where the heat
generated during the minimum run time for the heating
appliance (usually several minutes) cannot be absorbed
by the buildings distribution system.
Buffer Vessels
www.kensaheatpumps.com
2 connection buffer vessels are more
efficient
If close control of all
temperature zones is
not required then
‘open’ zones of the
underfloor can be
used as the buffer
vessel.
www.kensaheatpumps.com
Project Example – Sizing The Heat Pump
New Build Four Bedroom Detached Property with Garage
33
Sizing
www.kensaheatpumps.com
Internal area – Ground Floor & First Floor
Total Internal area = 224.6m2
Heat load =
224.6 x 40w/m
(If New Build)
= 8984
= 8.98 kW
34
Budget Pricing
www.kensaheatpumps.com
Budget Pricing
www.kensaheatpumps.com
SAP sizing – Line 37!
SAP Report - Line 37
Heat Loss Coefficient x Temperature Difference
-2°C (Min) to 21°C (Max) = 23°C rise
378.45 x 23 = 8704W = 10kW (39W/m)
www.kensaheatpumps.com