ASHRAE Atlanta paper 3 - DOAS
Download
Report
Transcript ASHRAE Atlanta paper 3 - DOAS
Selecting the Supply Air
Conditions for a Dedicated OA
System Working in Parallel with
Distributed Sen. Cooling Equip.
PSU
Kurt M. Shank, M.S. & Stanley A. Mumma, Ph.D., P.E.
College of Engineering
Department of Arch. Engineering
Penn State University @ University Park, PA
A/E
Environment
Building Thermal and Mechanical Systems Laboratory
Presentation Outline
Objective
Present 3 hypotheses, regarding SAT, SADPT, and Terminal Reheat
Load, Energy, and Cost impact of SAT
Load, Energy, and Cost impact of SA-DPT
Terminal Reheat and SAT
Conclusions and Recommendations
Objective
Challenge the current practice of
supplying air from dedicated OA
systems at a neutral temperature (~70F).
Develop a methodology for selecting
the proper supply air conditions.
Hypothesis 1: Load, Energy,
& Cost will decrease with DBT
PW, 1st
& Op $
PW, Op $
LCC
1st $
44F
70F
System Wide Impact of DBT on
Load, Energy, and Cost
Assumptions
–
–
–
–
–
–
–
Atlanta, GA data; 12 hr/day, 6 day/wk.
10,000 scfm of OA
Supply air DPT, 44F
20 scfm of OA/person
Resulting space DPT, 52F
Space condition, 78F, 40% RH
No terminal reheat required, i.e. space not
overcooled with ventilation air (relaxed later)
System Wide Impact of DBT on
Load, Energy, and Cost
Assumptions, Continued
– Constant design sensible load, split between
the DOAS and the parallel system; i.e. reduce
SAT (greater sensible cooling done) and
reduce the load on the parallel system (thereDOAS
fore size).
Parallel
Building Load
– Fan Coil first cost, $6/cfm
– Ceiling Radiant Panel cost, $8/sq. ft.
– Sensible Wheel in DOAS, $2/scfm OA
Load Mix with 10,000 scfm OA
in Atlanta.
SAT
F
70
55
44
DOAS
Parallel Peak Load
CC Load Sys. Load
Ton
Ton
Ton
27
23.4
50.4
39
9
48
47
0
47
Reason Peak Load Increased with
Increasing SAT
Because of less than 100% effectiveness at
the enthalpy wheel, only about 80% of the
sensible cooling done on the return air
(state 5-6) by the supply air (state 3-4) is
able to be recovered by the enthalpy
wheel (state 6-2). Consequently, the more
reheat, the greater the cooling required
when the parallel system is considered.
Illustrated on the next slide.
Reason Peak Load Increased
with Increasing SAT, illustrated
Path from 6-6’ is the
increase in reheat, and the
path 2-2’ is the reduction
in coil load. Since it is
shorter than 6-6’, the
cooling coil load is not
reduced as much as the
cooling capability of the
supply air when reheated.
1
2
2’
6’
6
5
Energy Mix with 10,000 scfm
OA in Atlanta, 3744 hours
SAT
F
70
55
44
DOAS
CC
TH
48,150
83,100
110,700
DOAS
Sen Cool
TH
27,000
77,500
114,600
Parallel Combined
Sys.
TH
TH
87,600
135,750
37,100
120,200
0
110,700
Parallel system 1st cost reduction
with SAT
SAT
FCU
CRCP Sen. Wheel Chiller
F
70 (ref)
$0
$0
$0
$0
55
-$51,200 -$43,200
$0
$0
44
-$85,300 -$72,000 -$20,000
$0
Hypothesis 1 confirmed, low SAT best
Hypothesis 2, Load, Energy,
& Cost will decrease with DPT
Assumptions:
– Atlanta, GA data, 12 hr/day, 6 day/wk.
– 10,000 scfm OA
– Building Sensible Load, 75 Tons
(representative of a 60,000 sq ft building,
served by an all air system with a design
supply air flow rate of 0.6 scfm/sq.ft. at
55F)
System Wide Impact of DPT on
Load, Energy, and Cost
Assumptions, continued:
– Allowable space RH range, 40-60% for
acceptable IAQ. (Sterling and Sterling)
– Chiller capacity drops 10% when the
chilled water temp. drops from 45 to 40F.
– Chiller kW/ton increases by 10% when the
chilled water temp. drops from 45 to 40F.
– Chiller kW/ton @ 45F CHWT: 0.79
System Wide Impact of DPT on
Load, Energy, and Cost
30
Assumptions, continued:
– Fan Coil and CRCP performance as below
Key:
CRCP, Btu/hr per ft2
FCU, Btu/hr per cfm
HT
10
55F
CHWT
65
System Wide Impact of DPT on
Load, Energy, and Cost
Assumptions, continued:
– FCU fan efficiency, 74% and 2”TP
– FCU & CRCP pumps, 80% eff., water temp
rise 5F, and pressure drop 30 ft water.
– Chiller installed 1st cost, $1000/ton
– Energy costs, $0.09/kWh
System Wide Impact of DPT on
1st and energy Costs
SA
Chiller Chiller
DB/ DP 1st k$ Op. k$
55/ 55
93
13.3
55/ 44
103
15.8
44/ 44
101
15
FCU
1st k$
354
204.6
168
FCU
Op. k$
6.3
3.6
3
CRCP CRCP
1st k$ Op. k$
518
.6
173
.6
141
.5
Hypothesis 2 confirmed, low SA-DPT best
Hypothesis 3, Terminal Reheat
will be needed sparingly if at all
Issues:
– Terminal Reheat is permitted where it is
required to meet Std. 62--Which is why so
many all air VAV systems use terminal reheat
– VAV box minimums are set to meet the
ventilation requirements. The minimum
setting will always be at or above that required
by the DOAS system since “zc “ in Eq. 6.1 will
always be less than or equal to 1.
Hypothesis 3: Terminal Reheat
Issues continued:
– If “zc “ = 0.4 and a space needs 200 scfm of OA,
then the box minimum must be 500 scfm. “zc “
for a dedicated OA system is always 1, so it
will deliver the 200 scfm.
– A room served by a VAV box with a minimum
setting of 500 scfm at 55F is prone to overcool
the space sooner than the dedicated OA system
supplying 200 scfm of air at either 55 or 44F.
(500*[78-55] >200*[78-44]) or (11,500>6,800)
Overcooling potential
with the DOAS
Assumptions:
–
–
–
–
–
–
Envelope UA, 0.09 Btu/hr-F/ft2 of floor area
Summer OA, 90F
Winter OA, 20F
Ventilation, 15 or 20 scfm/person
Occupancy Density, 0-90/1000 ft2
Internal generation, Lights, equipment; 0-15
W/ft2
Overcooling with the DOAS,
the energy balance/person
44-55F
OA, 15-20 scfm
Qenv
IG/ft2
Floor area
/person
Balance Point IG/ft2=QDOAS/ ft2 + Qenv/ ft2 -Qsen/ ft2
Overcooling with the DOAS
Graphic from the energy bal.
Example:
20 people per 1000 ft2 ,
4 W/ft2, If the IG less
than 4 W/ft2 with an
occupancy density of
20, the DOAS will
overcool; if more, need
parallel cooling.
15
20
Summer
4
IG, W/ft2
0
Winter
0
Occupancy/1000 ft2
90
Conclusion:
The 3 hypothesis verified
For many building applications,
terminal reheat is seldom if ever needed
with 55F or even 44F SAT from the
DOAS.
Old Paradigm of supplying the air at a
neutral temperature, in dedicated OA
applications, should be abandoned.
Recommendation
The supply air DPT should be low
enough to maintain the space RH no
higher than 40%, about 44F in many
cases.
The supply air dry bulb temperature
should be at 55F or below.
Where Occupancy densities are very
high, and terminal reheat is frequently
required, use recovered heat.