Lecture 22: Primary System
Loops in EnergyPlus
Material prepared by GARD Analytics, Inc. and University of Illinois
at Urbana-Champaign under contract to the National Renewable Energy
Laboratory. All material Copyright 2002-2003 U.S.D.O.E. - All rights reserved
Purpose of this Lecture
Gain an understanding of:
Water (fluid) side loop structures in
EnergyPlus
How to control fluid flow rates using the
EnergyPlus pump strategies
2
Defining Loops
Loops define the movement of mass
and energy within an HVAC system
Plant loop
Condenser loop
Heat recovery loop
Systems defined by the order of
branches/components on the HVAC loop
3
Defining Loops (cont’d)
Main loops divided into “sub-loops” or
“semi-loops” for organizational clarity &
simulation logistics
Sub-loops are matched pairs that
consist of half of the main loop.
For example, plant and condenser loops
are broken into supply and demand
sides.
4
Demand- & Supply-Side
Sub-Loops
Plant demand-side sub-loop contains
equipment that creates a load on the
plant.
Plant supply-side sub-loop contains
equipment that meets these loads.
Each supply-side sub-loop must be
connected to a demand-side loop.
5
Demand- & Supply-Side Loops
(cont’d)
Heating Coil
HW Pump Outlet Node
±
Heating Coil
Inlet Node
HW Demand
Outlet Node
Exit Pipe
Heating Coil
Inlet Pipe
Outlet Node
HW Demand Inlet Node
HW Pump
HW Supply inlet Node
Boiler Inlet Node
Boiler
HW Supply Outlet Node
Boiler Outlet Node
HW Supply Outlet Pipe
Demand-Side Loop
Supply-Side Loop
6
Branches for Water-Side
Loops
Maximum Branch Flow Rate (Ignored)
Comp1 Type
Comp1 Name
Comp1 Inlet Node Name
Comp1 Outlet Node Name
Comp1 Branch Control Type
7
Branches for Water-Side
Loops - Example
BRANCH,
Heating Supply Inlet Branch,
!- Branch Name
,
!- Maximum Branch Flow Rate {m3/s}
PUMP:VARIABLE SPEED,
!- Comp1 Type
HW Circ Pump,
!- Comp1 Name
HW Supply Inlet Node,
!- Comp1 Inlet Node Name
HW Pump Outlet Node,
!- Comp1 Outlet Node Name
ACTIVE;
!- Comp1 Branch Control Type
8
Layout for Individual HVAC
Supply or Demand Sub-Loops
A
Elements can be defined in
series, in parallel, or both
with some restrictions
Branches are defined as
individual legs within the
loop structure
Segment between point A &
B is defined as a branch, as
is the section between
points E and F
1 to m
Components
B
n Splitter
C1
Cn
...
1 to i
Components
D1
1 to j
Components
Dn
n Mixer
E
1 to k
Components
F
9
Layout for Individual HVAC
Supply or Demand Sub-Loops
A
The first supply side
component between A & B
must be the loop pump,
which controls the loop flow.
There may be multiple
branches between the
splitter and mixer (between
points C1 & D1 to Cn & Dn).
Each sub-loop may only
have one splitter and one
mixer.
1 to m
Components
B
n Splitter
C1
Cn
...
1 to i
Components
D1
1 to j
Components
Dn
n Mixer
E
1 to k
Components
F
10
Layout for Individual HVAC
Supply or Demand Sub-Loops
A
Equipment may be in
parallel between the mixer
and splitter,
Within any branch, there
can only be elements in
series.
Sub-loops do not require a
splitter or mixer, if all
equipment on the sub-loop
is in series—a single branch
defines the entire sub-loop.
1 to m
Components
B
n Splitter
C1
Cn
...
1 to i
Components
D1
1 to j
Components
Dn
n Mixer
E
1 to k
Components
F
11
Pumping Rules
Supply-Side Sub-Loop
Pumps must be on the
supply side
From DemandSide Sub-Loop
Pumps can operate as
constant or variable flow
Pumps can run
continuously or
intermittently
Loop Pump
Splitter
Components
To DemandSide Sub-Loop
Mixer
12
Pumping Rules (cont’d)
Single boiler/chiller with NO bypass,
PUMP:CONSTANT SPEED
Boiler/chiller should be constant flow
Pump should be intermittent
Single boiler/chiller with NO bypass,
PUMP:VARIABLE SPEED
Boiler/chiller should be variable flow, regardless of
whether pump is intermittent or continuous (runs at
the minimum if demand is less than minimum, this
includes zero.)
13
Pumping Rules (cont’d)
Single boiler/chiller with bypass,
PUMP:CONSTANT SPEED
Boiler/chiller can be constant or variable
flow
Pump may be intermittent or continuous as
long as the bypass can handle the entire
pump volume when the boiler is not
operating
14
Pumping Rules (cont’d)
Multiple branches add more complexity, but it
is nothing more than continuity.
If the pump is putting out flow then it has to
have a branch to flow down whether it is a
chiller or a bypass.
15
Pumping Rules (cont’d)
You are always safer adding the bypass for a
simulation. If the active machines require the
flow the bypass will be dry
Thermodynamically it does not make any
difference if the flow goes through a machine
that is OFF or it flows down the bypass.
There is no pressure simulation and flow
losses are not accounted for.
16
Summary of Loop Limitations
Each sub-loop allowed one splitter and one
mixer
One bypass on each sub-loop optional
No other components may be in series with a
bypass
Equipment may be in parallel only between
the splitter and mixer
Equipment may be in series in each branch
17
3-Zone VAV System
We are going to look at this system input Loop by Loop
Outside Air
Plant Supply Side
Cooling Loop
Supply Fan
CW Pump
Bypass
CC Plant Demand Side
Cooling Loop
Mixed Outside
Air Box
Bypass
Chiller
Relief Air
East
North
Zone
VAV Box: ReHeat
Return Hot
VAV Box: ReHeat
Cond . Demand
Side Loop
Boiler
Cond . Pump
HW Pump
Zone
Water Mixer
Return Air Mixer
Hot Water
Splitter
VAV Box: ReHeat
Zone Air Splitter
Zone
Plant Demand Side
Heating Loop
Resistive
Condenser
Bypass
Condenser
Bypass
Plant Supply Side
Heating Loop
Bypass
Cooling
Tower
Cond . Supply Side Loop
18
Cooling Coil & Chilled Water
Demand Side
Outside Air
Plant Supply Side
Cooling Loop
Supply Fan
CW Pump
CC Plant Demand Side
Cooling Loop
Bypass
Mixed Outside
Air Box
Bypass
Chiller
Relief Air
Boiler
Cond . Pump
Zone
VAV Box: ReHeat
Return Hot
VAV Box: ReHeat
North
Cond . Demand
Side Loop
HW Pump
Water Mixer
Return Air Mixer
Splitter
East
Zone
Hot Water
VAV Box: ReHeat
Zone Air Splitter
Zone
Plant Demand Side
Heating Loop
Resistive
Condenser
Bypass
Condenser
Bypass
Plant Supply Side
Heating Loop
Bypass
Cooling
Tower
Cond . Supply Side Loop
19
Cooling Coil & Chilled Water
Demand Side
CC
Cooling Coil
Chilled Water Demand -Side Outlet Node
Bypass
Chilled Water Demand -Side Inlet Note
Objects required:
BRANCH LIST
CONNECTOR LIST
SPLITTER
MIXER
BRANCH, VAV Sys 1 ChW-Branch
COIL:Water:DetailedFlatCooling, VAV SYS 1 Cooling Coil
20
Cooling Coil & Chilled Water
Demand Side (cont’d)
CC
Cooling Coil
Chilled Water Demand -Side Outlet Node
Bypass
Chilled Water Demand -Side Inlet Note
Objects required (cont’d):
BRANCH, Chilled Water Loop 1 CHW Inlet Branch
PIPE
BRANCH, Chilled Water Loop 1 CHW Outlet Branch
PIPE
BRANCH, Chilled Water Loop 1 CHW Bypass Branch
PIPE
21
Hot Water Demand Side
Outside Air
Plant Supply Side
Cooling Loop
Supply Fan
CW Pump
CC Plant Demand Side
Cooling Loop
Bypass
Mixed Outside
Air Box
Bypass
Chiller
Relief Air
Cond . Pump
HW Pump
Zone
VAV Box: ReHeat
Return Hot
VAV Box: ReHeat
North
Cond . Demand
Side Loop
Boiler
Zone
Water Mixer
Return Air Mixer
Splitter
East
Hot Water
VAV Box: ReHeat
Zone Air Splitter
Zone
Plant Demand Side
Heating Loop
Resistive
Condenser
Bypass
Condenser
Bypass
Plant Supply Side
Heating Loop
Bypass
Cooling
Tower
Cond . Supply Side Loop
22
Hot Water Coils & Demand
Side
COIL:Water:SimpleHeating(3)
BRANCH, HW Outlet Branch
HW Splitter
VAV Box:
Reheat
VAV Box:
Reheat
BRANCH, HW Inlet Branch
BRANCH, HW Bypass Branch
VAV Box:
Reheat
Bypass
PIPE
Return HW Mixer
PIPE
Zone Air Splitter
BRANCH LIST
CONNECTOR LIST
SPLITTER
MIXER
BRANCH,Zone X Reheat
Branch (3)
Plant Demand Side
Heating Loop
Objects required:
PIPE
23
Hot Water Loop Supply Side
Outside Air
Plant Supply Side
Cooling Loop
Supply Fan
CW Pump
CC Plant Demand Side
Cooling Loop
Bypass
Mixed Outside
Air Box
Bypass
Chiller
Relief Air
VAV Box: ReHeat
North
Cond . Demand
Side Loop
Boiler
Cond . Pump
HW Pump
Return Hot
Water Mixer
Return Air Mixer
East
Zone
Heating Loop
Hot Water
Splitter
VAV Box: ReHeat
Zone Air Splitter
Zone
Plant Demand Side
Resistive
Condenser
Bypass
Condenser
Bypass
Plant Supply Side
Heating Loop
Bypass
Cooling
Tower
Zone
VAV Box: ReHeat
Cond . Supply Side Loop
24
Hot
Water
Loop
Supply
Side
Hot Water Loop Supply Side
PLANT LOOP
BRANCH LIST
CONNECTOR LIST
SPLITTER
MIXER
BRANCH, Supply Inlet Branch
PUMP:VARIABLE SPEED
HW Supply
Outlet Node
Boiler
Outlet Node
Bypass
Plant Demand Side
Heating Loop
Objects required:
Boiler
Boiler
Inlet Node
HW Supply
Inlet Node
HW Pump
HW Pump
Outlet Node
25
Hot Water Loop Supply Side
(cont’d)
BRANCH, Boiler Branch
BOILER:SIMPLE
BRANCH, Supply Bypass Branch
PIPE
BRANCH, Supply Outlet Branch
HW Supply
Outlet Node
Boiler
Boiler
Inlet Node
HW Supply
Inlet Node
PIPE
Boiler
Outlet Node
Bypass
Plant Demand Side
Heating Loop
Objects required:
PLANT OPERATION SCHEME
HW Pump
HW Pump
Outlet Node
HEATING LOAD RANGE BASED OPERATION
HEATING LOAD RANGE EQUIPMENT LIST
26
Chilled Water Supply Side
Outside Air
Plant Supply Side
Cooling Loop
Supply Fan
CW Pump
CC Plant Demand Side
Cooling Loop
Bypass
Mixed Outside
Air Box
Bypass
Chiller
Relief Air
VAV Box: ReHeat
North
Cond . Demand
Side Loop
Boiler
Cond . Pump
HW Pump
Return Hot
Water Mixer
Return Air Mixer
East
Zone
Plant Demand Side
Hot Water
Splitter
VAV Box: ReHeat
Zone Air Splitter
Zone
Heating Loop
Resistive
Condenser
Bypass
Condenser
Bypass
Plant Supply Side
Heating Loop
Bypass
Cooling
Tower
Zone
VAV Box: ReHeat
Cond . Supply Side Loop
27
Chilled Water Supply Side
Plant Supply Side
Cooling Loop
CW Pump
Bypass
Plant Demand Side
Cooling Loop
Chiller
Objects required:
PLANT LOOP, Chiller Plant Chilled Water Loop
BRANCH LIST
CONNECTOR LIST
SPLITTER
MIXER
28
Chilled Water Supply Side
(cont’d)
Plant Supply Side
Cooling Loop
CW Pump
Bypass
Plant Demand Side
Cooling Loop
Chiller
Objects required (cont’d):
BRANCH, Chiller Plant Cooling Supply Inlet Branch
PUMP:VARIABLE SPEED
BRANCH, Chiller Plant Chiller Branch
CHILLER:Electric
BRANCH, Chiller Plant Cooling Supply Bypass Branch
PIPE
29
Chilled Water Supply Side
(cont’d)
Plant Supply Side
Cooling Loop
CW Pump
Bypass
Plant Demand Side
Cooling Loop
Chiller
Objects required (cont’d):
BRANCH, Chiller Plant Cooling Supply Outlet Branch
PIPE
PLANT OPERATION SCHEMES
COOLING LOAD RANGE BASED OPERATION
COOLING LOAD RANGE EQUIPMENT LIST
30
Condenser Loop Demand Side
Outside Air
Plant Supply Side
Cooling Loop
Supply Fan
CW Pump
CC Plant Demand Side
Cooling Loop
Bypass
Mixed Outside
Air Box
Bypass
Chiller
Relief Air
Cond . Pump
HW Pump
VAV Box: ReHeat
North
Cond . Demand
Side Loop
Boiler
Zone
Return Hot
Water Mixer
Return Air Mixer
East
Plant Demand Side
Hot Water
Splitter
VAV Box: ReHeat
Zone Air Splitter
Zone
Heating Loop
Resistive
Condenser
Bypass
Condenser
Bypass
Plant Supply Side
Heating Loop
Bypass
Cooling
Tower
Zone
VAV Box: ReHeat
Cond . Supply Side Loop
31
Condenser Loop Demand Side
Objects required:
BRANCH LIST
CONNECTOR LIST
SPLITTER
MIXER
BRANCH, Condenser Demand Inlet Branch
PIPE
BRANCH, Chiller Condenser Branch
Plant Supply Side
Cooling Loop
Chiller
Condenser
Bypass
CHILLER:Electric
BRANCH, Cond. Demand Bypass Branch
PIPE
BRANCH, Cond. Demand Outlet Branch
PIPE
Condenser Supply
Side Loop
32
Condenser Supply Side
Outside Air
Plant Supply Side
Cooling Loop
Supply Fan
CW Pump
CC Plant Demand Side
Cooling Loop
Bypass
Mixed Outside
Air Box
Bypass
Chiller
Relief Air
Cond . Pump
HW Pump
VAV Box: ReHeat
North
Cond . Demand
Side Loop
Boiler
Zone
Return Hot
Water Mixer
Return Air Mixer
East
Heating Loop
Hot Water
Splitter
VAV Box: ReHeat
Zone Air Splitter
Zone
Plant Demand Side
Resistive
Condenser
Bypass
Condenser
Bypass
Plant Supply Side
Heating Loop
Bypass
Cooling
Tower
Zone
VAV Box: ReHeat
Cond . Supply Side Loop
33
Condenser
Supply
Side
Condenser Loop Supply Side
Objects required:
CONDENSER LOOP
BRANCH LIST
CONNECTOR LIST
SPLITTER
MIXER
BRANCH, Supply Inlet Branch
Condenser Demand
Side Loop
Condenser
Pump
Condenser
Bypass
PIPE
BRANCH, Condenser Branch
COOLING TOWER:Single Speed
Cooling
Tower
34
Condenser
Loop
Supply
Side
Condenser
Supply
Side
(cont’d)
Objects required (cont’d):
BRANCH, Cond. Supply Bypass Branch
PIPE
BRANCH, Supply Output Branch
PIPE
Condenser Demand
Side Loop
CONDENSER OPERATION SCHEMES
Condenser
Pump
Condenser
Bypass
COOLING LOAD RANGE BASED
OPERATION
LOAD RANGE EQUIPMENT LIST
Cooling
Tower
35
Summary
Loops are backbone of HVAC simulation
all equipment attached to air or fluid loops
Loop structure permits assembly of any
system through input—not hardwired
Primary system may consist of four different
loops: plant supply and demand, condenser
supply and demand
Pumps regulate flow while attempting to
meet requests on both sides of each loop pair
Individual loops may have components in
series and parallel with some limitations
36