Access Control OnGuard 2010 review

Download Report

Transcript Access Control OnGuard 2010 review

NGP Introduction
Next Generation Enterprise Access Control System with
optional Central Station Burg support
7/7/20151
Company Confidential
NGP Mission Statement
 The purpose of the NGP panel is to offer Lenel VARS
and End Users an alternative enterprise-class
access control panel family
 Adding value by offering,





true central-station intrusion detection
expanded memory
increased reader count
power management feedback
…and future expansion capabilities
NGP - Project Scope
OnGuard
Main controller
Central Station
(Panel)
Location: Electrical Room
Location: Control Room
Door controller
(Peripheral)
Input/Output Modules:
(Peripheral)
Location: Room Ceiling
CCTV system
(Output)
Motion Sensor
(Input)
Door
Intrusion Only
Location: Room Wall
Door
strike
Reader
Reader
Access Control Only
Door
strike
Door
Buzzer R2
Power 14 V R2
Green LED R2
Red LED R2
D1 R2
D0 R2
-V R2
D1 Egress R2
D0 Egress R2
Door Contact 2
Tamper Door2
AUX Door 2
REX Door 2
SOM
Door Strike Relay
Door Contact 1
Tamper Door1
Buzzer R1
Power 14 V R1
Green LED R1
Red LED R1
D1 R1
D0 R1
-V R1
D1 Egress R1
D0 Egress R1
AUX Relay NO R 1
AUX Relay C R 1
AUX Door 1
REX Door 1
Door Strike Relay
NGP and Components
External Primary Secondary USB Host
Battery Ethernet Ethernet
Ports
Connecto
Port
Port
r
VBus
12 VDC Alternate Power
18 VAC / 24VDC
Power
SNAPP Bus 4
SNAPP Bus 3
AUX 14V Supply 1
AUX 14V Supply 2
SNAPP Bus 2
SNAPP Bus 1
Siren Relay
Strobe Relay
Micro SD Card
External Tamper
Circuit 4
Circuit 3
Circuit 2
Circuit 1
Product Components
 NGP Panels (controllers), with enclosure and power
supply, with or without (intrusion, dual doors, dual
path and other options)
 NGP dual reader interfaces, with or without universal
mounting plates (LNL-CTX and LNL-CTX6)
 Input and output modules mounted to universal
mounting plate to fit into current Lenel enclosures
(LNL-CTX and LNL-CTX6)
 LCD keypads, with or without reader interface
 Intelligent power supply module
 Optional world wide modem for intrusion
Final System Level Design
NGP
SIA or ContactID
TCP/IP
Alarm Monitoring
Station
Host Interface
• TCP/IP
4
Downstream Peripherals
Based on Guardall NA I/O
SNAPP
(RS485)
•NGP-13201,2
•NGP-CKGN1
•NGP-CKGE1
•NGP-11001
•NGP-12081
Lenel Access Control Module
Lenel Standard LCD
Lenel LCD (external reader)
Lenel 16 Input Module
Lenel 8 Relay Output Board
Notes:
1. Based upon existing product with new OEM code
2. Includes code revisions to support 245-bit cards
3. Based upon existing product with HW changes
4. NGP will use existing Guardall Worldwide Modem
(WWM), part number 120-3633, for PTSN
communication
Downstream Communication
NGP
Panel
D2[OUT]
500’
D2 IN
4000’ = 1219m
500’ = 152m
4000’
LCD
Keypad
1320
D1 [OUT]
In[Out] Readers
share connections
D1 IN

SNAPP
4000’
R
Enclosure (VBUS)
Bi-directional
4000’ SNAPP Bus
VBUS (Enclosure)
500’ Reader Wire
1100
1208
1208
1208
1208
Value Proposition Summary
 A scalable hardware and software platform
 Reuse existing Guardall peripherals where possible
 Integration with OnGuard Host Software
 Integrated Access and Intrusion

With Central Station Support
 Phased approach to ultimately include:


NGP peripheral devices
Guardall legacy peripherals
NGP Panel Set Conceptual Differences!
 Access and Intrusion!
 Onboard power supply and charger

With enhanced status reporting
 Doors vs. Readers

1 or 2 readers per door [IN/OUT]
 Output boards are “children” of input boards

8 Outputs per Panel instead of 16
 2 Communication ‘Busses’


SNAPP for external
Vbus for internal
NGP panel intrusion functions
 Up to 1024 input points





Define any point as
belonging to any area
System default point type
and custom point type
(future OnGuard support)
False alarm prevention
point type
Delay point type
4 state detection:


NC, NO, Open and short
circuit
Custom EOL values
 Up to 130 independent
areas







Individual Arm/Disarm time
schedule
Manual or Auto
Arm/Disarm
Priority Arm/Disarm
Dual custody Disarm
Area inter-lock Disarm
No activity auto Arm
Time schedule control
perimeter (Stay) or fully
Arm (On)
OnGuard Features NOT available with NGP
 OSDP Reader Support
 Panel-based Biometrics
 Elevator Control
 Schlage Wireless Support
 PIV support is TBD
Panel Feature Set - Licensed
 Feature Set – the capabilities configuration to use
with all panels

Determines the system capacities for Readers, Inputs, Etc.
 Determined by a License file loaded to the panel


Initial license loaded the factory
Upgrades available
 See next slide for more details…
Panel Feature Sets
Panel #
On-Board
Doors
Total
Doors
Badges
Ethernet
Ports
Intrusion
Support
Supported
Inputs
NGP2200i
No
66
249,999
1
Yes
512
NGP2220i
Yes
66
249,999
1
Yes
512
NGP3300i
No
128
499,999
2
Yes
1024
NGP3320i
Yes
130
499,999
2
Yes
1024
NOTE: Panels will be available in a Non-Intrusion version.
Same part numbers w/o the ‘i’ designation.
System On Module (SOM)
 Main application
processing unit




Linux operating system
Root file system
Database (configuration,
users, etc.)
Event storage
 Atmel AT91SAM9G20
ARM (400Mhz)
 Communication ports




6 serial
2 Ethernet (10/100Base-T)
2 USB host
1 USB device
 Memory





Serial dataflash (4MB)
NAND flash (256MB)
SDRAM (512MB)
NVRAM (2MB)
Micro SD card (2GB future)
 Real Time Clock
Controller Base Module with I/O processor
 Freescale MC9S08AC96 (18Mhz)
 18VAC/24VDC/12VDC input
power
 Power Supplies




System regulator: 14DC @ 1.2A
Battery charger 13.7VDC @ 1.2A
5VDC @ 1A
3.3VDC @ 1A
 I/O processing unit



I/O signal conditioning
Field wiring connections
Timing critical functions



A-D conversion
Reader input processing
Power supply monitoring and
diagnostics
Controller Base Module with I/O processor
 Communication interfaces




2, Ethernet RJ45
Dual USB (for Serial Support)
4, SNAPP (RS485)
Vbus for I/O expansion


Future Use
WWM for PTSN alarm reporting
to Central Station
 Outputs





2, 5A @ 24VDC 1-Form-C relays
2, 1A @ 24VDC relays
4 open collector inputs
2, 14V auxiliary supplies
Backup battery disconnect relay
 Inputs

12 supervised inputs



4 Wiegand/Magstripe readers
External tamper input


4 w/ 2 Doors
Off the wall tamper input
Solid state siren/strobe outputs
(optional)
NGP Memory
 Onboard memory will retain specified information
which includes:




Cardholder/Badge – 500,000 MAX
Access levels – 31,199
Timezones – 255 (Holidays – 128)
50,000 Events
 Battery backed memory and Flash storage


Memory is not an issue with the NGP
It was sized based on what we needed to hold
NGP-1320 - 2 Door / 4 Reader Module









Configuration Options
NGP-1320= board only
NGP-1320-UMP (displayed)


2 door, 4 reader access control
Dedicated door status and REX
inputs
Additional input for each door
8 amp Form-C lock relay for
each door
3 amp Form-A aux relay for
each door
Processor Diagnostic LED
5V or 12V selectable reader
power output
12VDC power
RS485 SNAPP bus
communications to controller
Front and rear tamper
(separate switches)
12VDC power
NGP-1100 - Input/Output Module







16 solid-state inputs
2 solid-state outputs
Diagnostic LED for
communications and
each relay
Expansion port for up to
4 downstream vbus
modules
RS485 SNAPP bus
communications to
controller
Front and rear tamper
(separate switches)
12VDC power
NGP-1208 - Output Expansion Board





8 Form-c Relay
outputs
Diagnostic LED for
communications and
each relay
Vbus communications
to NGP-1100
Up to 4 allowed per
NGP-1100
12VDC power
Worldwide Modem 120-3633L
 Worldwide Modem
(Optional)




Operates at 2400 Baud
SIA/CID reporting formats
HSC/IP (High Security
Communications)
Direct plug in module to
NGP
LCD Keypad (NGP-CKXX Gray & White)

Large character 2x16 screen




Allows the user to view and control the system
Cover tamper and wall tamper
detection (single switch)
Available with or w/o External Reader
Interface
Future Keypad Features (TBD)


Dedicated keys used for panic, fire, and medical
emergencies
Function (f) keys allow the system administrator
to program up to 10 specific output functions of
their choice per area
Model Cross Reference
Existing Product
New Product
(Base)
New Product (alternative)
LNL-2220
NGP-2220UL
NGP-2220CE, NGP-2220Ixx s/intrusion
LNL-3300
NGP-3300UL
NGP-3300CE, NGP-3300Ixx s/intrusion
Not available
NGP-3320UL
NGP-3320CE, NGP-3320Ixx s/intrusion
LNL-1320
NGP-1320
NGP-1320-UMP
LNL-1100
NGP-1100
NGP-1108K-UMP = (1) 1100 & (1) 1208
LNL-1200
NGP-1200 x2
NGP-1216K-UMP = (2) 1208
LNL-8000
N/A
LNL-500b, LNL-500w
N/A
N/A
120-3633L
World Wide Modem
N/A
120-3650(1)L
Intelligent Power Supply
LNL-CK
NGP-CKWE
W= White, G= Gray, E=w/reader
interface, N=no reader interface
Key differences
Requires a NGP-1100, 2x
to get 16 outputs
Configuration Examples
Configuring the Panel
 NGP Access Panel Configuration


Typical configuration tabs
NGP specific tabs (Power, SIA/CID, Intrusion, etc.)
NGP Panel Options
 Options control the functions available on the panel

‘Model:’ sets the feature set of the panel
Power Tab on NGP
Specifies settings
for the battery
testing and use by
the panel

Brownout Mode




Send alarm on low
voltage
Check for Battery
Cutoff Voltage
Warning Voltage
Capacity Tab on NGP
 Display Panel Capacities





Doors
Alarm Panels
Inputs/Outputs
Downstream Devices
Badges
Adding an NGP-1100 Input Panel
 Adding an Input Panel requires the board serial
number

You also need to specify the number of Inputs and Outputs
supported by the panel (groups of 4)

Include any VBUS connected NGP-1208s in the count of Outputs
Input/Output Addressing
 The inputs and outputs in the system are selected by
their association to an Alarm Panel

Main NGP Panel Inputs/Outputs




4 Inputs and 2 Outputs (w/ Onboard Readers)
12 Inputs and 2 Outputs (w/o Onboard Readers
NGP-1100 Panels have 16 Inputs
NGP-1208 Panels have 8 Outputs

4 can be connected to a single NGP-1100
 Using techniques familiar to OnGuard users we can
allow management of large numbers of points
Configuring the Inputs
 Select the Alarm Panel the Inputs are connected to
on the left


Supervision and Point Type
Area and Buffer Area
Point Types
 16 Pre-defined Input Point Types

Means that the installer can quickly program how a point
behaves


Standard (Basic On/Off Point for Access Only Systems)
Entry doors (triggers), route points (followers), perimeter points, supervisory points, fire
points and panic (hold up) points can be quickly defined
 Easy to Use; configures commonly used inputs




Burglary
Life Safety
Supervisory groups
False Alarm Prevention Points

Typically used with Motion Detectors, it will only report if active for 10 seconds or if 2
separate sensors in the same area activate within 20 minuntes
NGP Reader Settings
 Specific settings for the NGP Readers



Assume Door Used / Time and Attendance
Turnstile Behavior / Request to Exit behavior
“Man-Trap” - Interlock Support
NGP Door Modes
 Credential Required
 Unlocked
 Pending First User (First Card Unlock)
 Area is Disarmed (Stay/Disarmed)

Door is unlocked when the area is…
In/Out Readers
 Reader Mode
 Card Only, Card and PIN, PIN or Card, PIN Only

PIN Only requires a setting at the panel
 Reader Policy
 Normal, Dual Custody, Escort, Toggle Lock (Authorized)
 Lockout (locks the reader)
 During or Outside the schedule only
Areas
 Areas in NGP can be used for various reasons




Anti-passback
User Counting
Activity Detection
Intrusion Detection




Delay Times
Exit Settings
Common / Priority Areas
Arm/Disarm Settings


Schedule
Options