Transcript Slide 1
Proportional Control and Disturbance Changes Chapter 11 From Fig. 11.16 and Eq. 11-29 the closed-loop transfer function for disturbance changes with proportional control is K p / τs 1 H s Q1 s 1 KOL / τs 1 (11-53) H s K2 Q1 s τ1s 1 (11-54) Rearranging gives where τ1 is defined in (11-39) and K2 is given by K2 Kp 1 KOL (11-55) 1 • A comparison of (11-54) and (11-37) indicates that both closedloop transfer functions are first-order and have the same time constant. Chapter 11 • However, the steady-state gains, K1 and K2, are different. • From Eq. 11-54 it follows that the closed-loop response to a step change in disturbance of magnitude M is given by h t K2 M 1 et / τ1 (11-56) 0 The offset can be determined from Eq. 11-56. Now hsp since we are considering disturbance changes and h K 2 M for a step change of magnitude M. Thus, offset 0 h K 2 M K pM 1 KOL (11-57) 2 Chapter 11 Figure 11.19 Load responses for Example 11.3. 3 Chapter 11 PI Control and Disturbance Changes For PI control, Gc s Kc 1 1/ τ I s . The closed-loop transfer function for disturbance changes can then be derived from Fig. 11.16: K p / τs 1 H s (11-58) Q1 s 1 KOL 1 1/ τ I s / τs 1 Clearing terms in the denominator gives K pτ I s H s Q1 s τ I s τs 1 KOL τ I s (11-59) Further rearrangement allows the denominator to be placed in the standard form for a second-order transfer function: H s K3 s 2 2 Q1 s τ3 s 2ζ3τ3s 1 (11-60) 4 Chapter 11 where K3 τ I / K c K v K m (11-61) 1 1 KOL ζ3 2 KOL (11-62) τI τ τ3 ττ I / KOL (11-63) For a unit step change in disturbance, Q1 s 1/ s , and (11-59) becomes K3 H s 2 2 (11-64) τ3 s 2ζ 3τ3 s 1 For 0 ζ 3 1 , the response is a damped oscillation that can be described by h t eζ 3t / τ3 sin 1 ζ 32 t / τ3 1 ζ 32 K3 τ3 (11-65) 5 6 Chapter 11 PI Control of an Integrating Process Consider the liquid-level control system shown in Fig. 11.22. This system differs from the previous example in two ways: Chapter 11 1. the exit line contains a pump and 2. the manipulated variable is the exit flow rate rather than an inlet flow rate. In Section 5.3 we saw that a tank with a pump in the exit stream can act as an integrator with respect to flow rate changes because H s 1 Gp s Q3 s As (11-66) H s 1 Gd s Q1 s As (11-67) 7 Chapter 11 Figure 11.22 Liquid-level control system with pump in exit line. 8 Chapter 11 If the level transmitter and control valve in Eq. 11.22 have negligible dynamics, the Gm(s) = Km and Gv(s) = Kv. For PI control, Gc s Kc 1 1/ τ I s . Substituting these expressions into the closed-loop transfer function for disturbance changes H s Gd Q1 s 1 GcGvG pGm (11-68) and rearranging gives H s K4 s 2 2 Q1 s τ 4 s 2ζ 4 τ 4 s 1 (11-69) K4 τ / Kc Kv K m (11-70) τ 4 τ I / KOL (11-71) ζ 4 0.5 KOL τ I (11-72) where And KOL = KcKvKpKm with Kp = - 1/A. 9 Stability of Closed-Loop Control Systems Chapter 11 Example 11.4 Consider the feedback control system shown in Fig. 11.8 with the following transfer functions: Gc K c 1 G p Gd 5s 1 1 Gv 2s 1 1 Gm s 1 (11-73) (11-74) Show that the closed-loop system produces unstable responses if controller gain Kc is too large. 10 Chapter 11 Figure 11.23. Effect of controller gains on closed-loop response to a unit step change in set point (example 11.1). 11