Applying ASHRAE Standard 62.2 to Existing Buildings

Download Report

Transcript Applying ASHRAE Standard 62.2 to Existing Buildings

Applying ASHRAE
Standard 62.2 to
Existing Buildings
Paul Francisco
Building Research Council
ASHRAE 62.2 Ventilation Requirements

Whole-House ventilation


Bath Fans
Kitchen Fans

Can choose continuous or intermittent

Both CAN count toward
whole-house rate
Intermittent may require greater flow
ASHRAE 62.2 Requirements
Minimum Ventilation Air Requirements, CFM
Floor Area
(ft2)
Bedrooms
0-1
2-3
4-5
6-7
>7
<1500
30
45
60
75
90
1501 – 3000
45
60
75
90
105
3001 – 4500
60
75
90
105
120
4501 – 6000
75
90
105
120
135
6001 – 7500
90
105
120
135
150
>7500
105
120
135
150
165
Whole-House Ventilation

Mechanical rate = 7.5*NP + 0.01*Afloor




NP default is number of bedrooms + 1
Use actual occupancy if higher
Assumes infiltration rate of 0.02*Afloor
No differentiation between mechanical
ventilation system types
Local Exhaust Ventilation

Bathrooms (not half bathrooms)



50 CFM on-demand, or
20 CFM continuous.
Kitchen


100 CFM on-demand, or
5 ACH continuous, based on kitchen volume.
Existing Buildings

Can comply using a single fan through
alternative compliance appendix

Three steps



Base fan flow rate
Adjustment for local exhaust “deficits”
Infiltration credit
Base Fan Flow Rate
Floor Area
(ft2)
Bedrooms
0-1
2-3
4-5
6-7
>7
<1500
30
45
60
75
90
1501 – 3000
45
60
75
90
105
3001 – 4500
60
75
90
105
120
4501 – 6000
75
90
105
120
135
6001 – 7500
90
105
120
135
150
>7500
105
120
135
150
165
or can use 7.5*NP + 0.01*Afloor
Local Exhaust “Deficits”

In each room where local exhaust should be,
determine deficit relative to intermittent rate



How much less than 50 cfm in bathrooms
How much less than 100 cfm in kitchens
For each room with a deficit, reduce room’s
deficit by 20 cfm if that room has an operable
window (not to drop below 0)
Local Exhaust “Deficits”


Add up deficits, divide by 4
Add the result to the whole-house
requirement

This becomes the new whole-house requirement
Local Exhaust “Deficits”


For existing fans being used, sound and
ducting requirements not applicable
Must measure flow if ratings don’t exist or
duct sizing can’t be verified

If only have rating at 0.10 in. wc but not 0.25 in.
wc, can reduce rating at 0.10 in. wc by 25%
Local Exhaust “Deficits”

Example #1
KIT
-100
3 BR, 1500 sq. ft. house
-50
BT
BR
BR
Deficit = 100+50+50 = 200
Add 200/4 = 50
-50
MBT
BR
Whole-house requirement = 45 + 50 = 95 cfm
Local Exhaust “Deficits”

Example #2
KIT
-80
-30
BT
BR
BR
Deficit = 80+30+50 = 160
Add 160/4 = 40
-50
MBT
BR
Whole-house requirement = 45 + 40 = 85 cfm
Local Exhaust “Deficits”

Example #3
KIT
-80
-30
BT
BR
BR
Deficit = 80+30+18 = 128
Add 128/4 = 32
-18
MBT
BR
32 cfm
Whole-house requirement = 45 + 32 = 77 cfm
Local Exhaust “Deficits”

Example #4
KIT
Add whole-house fan here
-0
-80
BR
BR
BT
Deficit = 80+0+18 = 98
Add 98/4 ≈ 25
-18
MBT
BR
32 cfm
Whole-house requirement = 45 + 25 = 70 cfm
Infiltration Credit

IF




House built before adoption of 62.2
Blower door test done
Estimated infiltration using Standard 136 is
greater than 2 cfm/100 sq. ft.
THEN

Reduce whole-house rate by ½ of the excess
above 2 cfm/100 sq. ft.
Infiltration Credit

Example #5
KIT
BR
BR
BT
Std. 136 estimates inf. = 70
BR
½ * (70-30) = 20
MBT
Whole-house requirement = 45 - 20 = 25 cfm
(plus any “deficit” adjustment)
Infiltration Credit

Example #6
KIT
BR
BR
BT
Std. 136 estimates inf. = 120
BR
½ * (120-30) = 45
MBT
Whole-house requirement = 45 - 45 = 0 cfm
(plus any “deficit” adjustment)
Std. 136?

Requires




CFM50
Number of 8-foot stories (e.g. a 12-foot ceiling
counts as 1.5)
Weather factor “w”
Weather factors can be found in BPI-101
standard
Std. 136 Approximation

From Workforce Guidelines Appendix
I CFM  0.0508* w * S * Q50

Assumes that volume = floor area * 8
# stories
1
1.5
2
2.5
3
S
1
1.13
1.23
1.32
1.39
QUESTIONS?