3200 Calibration - Insulation Testers

Download Report

Transcript 3200 Calibration - Insulation Testers

INSULATION TESTER CALIBRATION
Using the 3200 Electrical Test Calibrator
INSULATION TESTER CALIBRATION
Overview
The 3200 has five functions for calibrating insulation testers :
1.
2.
3.
4.
5.
High value resistance output for insulation testing
(0 MOhms to 2,000MOhms)
Measurement of the insulation test voltage
Low value resistance for continuity testing
(0.1 Ohm to 20.0 Ohms Variable, 100 Ohms & 1kOhm Fixed Ranges)
Insulation test current measurement
A.C. voltage output at 100V, 200V, 240V, 300V and 400V
Dedicated inputs and test buttons for
Insulation Testers provides safe, convenient
connection & operation
INSULATION TESTER CALIBRATION
Continuity Resistance
1.
CONNECT TESTER TO INSULATION
TESTER TERMINALS
2.
SET CONTINUITY RANGE ON TESTER
3.
SET CONTINUITY RESISTANCE ON
3200, EG. 1 OHM
4.
MEASURE RESISTANCE USING TESTER
INSULATION TESTER CALIBRATION
Continuity Current
1.
2.
3.
CONNECT TESTER TO INSULATION TESTER TERMINALS
SET CONTINUITY RANGE ON TESTER
MEASURE CONTINUITY CURRENT FROM TESTER
NOTE : 1 OHM RANGE MUST BE SET ON 3200 TO ENABLE
CURRENT MEASUREMENT
CURRENT MEASUREMENT
MODE ENABLED BY USING
1 OHM CONTINUITY RANGE
INSULATION TESTER CALIBRATION
Insulation Resistance
1.
CONNECT TESTER TO INSULATION
TESTER TERMINALS
2.
SET INSULATION RANGE ON TESTER
3.
SET INSULATION RESISTANCE ON
3200, EG. 10 MOHM
4.
MEASURE RESISTANCE USING TESTER
INSULATION TESTER CALIBRATION
Insulation Test Voltage
1.
2.
3.
CONNECT TESTER TO INSULATION TESTER TERMINALS
SET INSULATION TEST VOLTAGE RANGE ON TESTER
MEASURE INSULATION TEST VOLTAGE & CURRENT FROM TESTER
BY SELECTING THE VOLTAGE MEASUREMENT FUNCTION USING
THE SOFT KEY (SHOWN BELOW)
VOLTAGE / CURRENT
MEASUREMENT ENABLED
BY USING THE SOFT KEY