Transcript Harmonics (continued)
Applied Harmonics Control of Harmonics
1
Harmonic Distortion Evaluations
IEEE Standard 519-1992
• Limit harmonic current injections from end users so that harmonic voltage distortion is tolerable.
• Limit harmonic voltage (responsibility of utility).
2
utility system PCC other customers I L customer under study utility system PCC I L customer under study other customers 3
• • • End users are limited at PCC in terms of – individual harmonic components and – total demand distortion Utility is mainly responsible for limiting voltage distortion at PCC Evaluations: – Measurement of currents injected by load (over one week period) – Calculation of frequency response of system impedances (using harmonic calculation software) 4
Total harmonic distortion of voltage is normalized with the system nominal rms voltage : T HD V n h 1 V n V h 2 100 % Total demand distortion for current (as before) : TDD h 1 I h 2 I L 100 % 5
Bus Voltage at PCC, Vn [kV,LL] Vn < 69 69 Vn < 69 kV Isc/IL 0-20 h<11 4.0% 11 • I h is rms magnitude of individual harmonic current • I sc is the short-circuit current at PCC • I L is the fundamental component of the maximum demand current (average max demand over 12 months) • Individual limits apply to odd-order harmonics, even order limits are at 25% of indicated value 8 • For power converters with more than 6 pulses, where q = pulse number, multiply limits in table 6.2 by q / 6 For example, if q 12, then multiply by I L kWD kWD pf 3 kV rated average billed demand in kW pf average billed power factor kV rated nominal LL voltage in kV 2 . 9 • Control only when harmonics create a problem. Types of problems: – load harmonic currents are too large – path for harmonic currents is too long electrically (too much impedance) producing voltage distortion or communication-line interference – response of system magnifies one or more harmonics 10 • Reduce magnitude of harmonic currents from load • Add filters to do one or more of these: – short out (siphon off) the harmonic – block harmonic currents from entering part of the system – supply the harmonics locally • Modify the frequency response of the system by filters or other means 11 • Sometimes transformer connections can be changed, for example: – phase shift on some transformers supplying 6-pulse converters – delta windings block triplen currents – zig-zag transformers can supply triplens 12 C A B C B A N Zig-zag transformer N 13 • Place the transformer to supply balanced triplen harmonics (and any other zero sequence currents) to load • This will unload zero sequence currents on circuits upstream of the ZZ transformer, with little or no effect downstream • Fault study results may be affected 14 a b c I 3 n 3I 3 Unloads the neutral conductor upstream 15 • Shunt passive filter: short-circuit harmonic currents close to their source • Series passive filter: block harmonic currents from power delivery system (may cause large load voltage distortion) • Active shunt filter: electronically supply low-order harmonics to a nonlinear load (used with simple passive filters for higher frequency components). 16 • Shunt passive filters are – notch filters, tuned to a specific harmonic frequency, or – high-pass filters notch filter high-pass filter 17 • Add a shunt filter to the system • Add a reactor (e.g., in series with a pf correction capacitor) to de-tune system • Change pf correction capacitor size or placement, or remove capacitor bank entirely 18 • On utility system or end-user facility – utility system is more difficult to filter unless we can move or change the size of or reconnect a capacitor – end-user system may be easier to filter if we can access the feeder(s) where the harmonic currents are being produced 19 • In-line reactors (or chokes) for ASD • Isolation transformers can help • Isolation transformers can be reconnected with different phase shifts X s X t reactor 0-5% on ASD kVA ASD M 20 Isolation transformers X~5% 480 V bus ASD M M ASD Approximates a 12-pulse converter with 6 pulse converters by putting half on Delta Delta transformers and the half on Delta-Y. 12-pulse has I h = 0 for h = 5, 7 21 • Perform harmonic studies when – a problem occurs, to find a solution – planning large capacitor bank installation on either utility or industrial system – planning installation of large nonlinear load such as adjustable speed motor drives (ASD) – designing a harmonic filter or converting a capacitor to a harmonic filter 22Table 6.2 Harmonic current limits
Controlling harmonics
Options for control
Reducing load harmonic current
Zig zag transformer
Placement of ZZ transformer
Filtering
Passive Filters
Modifying system frequency response
Where to control harmonics
Filters
Harmonic studies