Electrical Safety In The Workplace

2

Changing Profession, Changing Attitudes

Accepted test methods circa 1942 Testing for voltage by touch under 250 volts considered safe!!

Testing for low voltage by tasting!!

SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

3

SALISBURY BY HONEYWELL - CONFIDENTIAL

4

Electrical Safety

-

What are the Electrical Hazards?

Electrical Shock –

When electrical current enters and exits the body creating a path.

Arc Flash –

A dangerous condition associated with the release of energy caused by an electric arc. Note that this explosive condition includes a broad spectrum of electromagnetic energy, plasma, fragments and a spray of molten materials.

Arc Blast –

Pressure wave caused by the expansion of gases and conducting materials with flying molten materials.

SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

Shock Illustration Current passage paths through the body

5

(A) Touch Potential (B) Step Potential (C and D) Touch / Step Potential

Current passing through the heart and lungs is the most serious

SALISBURY BY HONEYWELL - CONFIDENTIAL

6

Electrical Safety

Effects of Shock on the body

-

Current, Not Voltage causes Electrical Shock

• • • • • • •

mA 0.5 - 3 3+ 10+ 30+ 60+ 100+ Affect on Person Tingling sensations Shock Muscle contractions and pain Respiratory paralysis Heart Paralysis (may be fatal)

• •

4+ Amps 5+ Amps Ventricular fibrillation (usually fatal) Heart Paralysis Tissue and Organs start to burn

SALISBURY BY HONEYWELL - CONFIDENTIAL

7

Electrical Safety

Statistics Annual U.S. average Annual U.S. average Each Day Electrocutions Every Year 4,000 3,600 1 4 2000+ Electrical contact injuries, non disabling Electrical contact injuries, disabling Person is electrocuted Leading cause of occupational fatalities Workers are sent to burn centers with electrical burns

SALISBURY BY HONEYWELL - CONFIDENTIAL

8

Electrical Safety

Terms and Definitions related to Arc Flash

Arc Rating.

Arc Rating is a protection value assigned to textile materials based on predicting 2 nd degree burn injury based on the Stoll Curve.

Arc Flash hazard.

A dangerous condition associated with the release of energy caused by an electric arc. Note that this explosive condition includes a broad spectrum of electromagnetic energy, plasma, fragments and a spray of molten materials.

Incident Energy

as the amount of energy impressed on a surface, a certain distance from the source, generated during an electric arc event. Incident Energy is measured in calories/cm2.

Cal/cm2. (Calories per Sq. Centimeter)

The total energy on a surface area. It is the unit of measure used for Arc Ratings.

SALISBURY BY HONEYWELL - CONFIDENTIAL

9

Electrical Safety

What causes Arc Flashes?

Electricity will go through the path of least resistance. When the path of electricity is suddenly interrupted, the electricity will try to create a new pathway.

The arc can be generated by: - Mechanical breakdown/failure - Current overload - Accidental contact

SALISBURY BY HONEYWELL - CONFIDENTIAL

10

Electrical Safety Arc Flash Variables

Variables that effect the size and energy of an electric arc flash are:

 Amperage  Voltage  Arc gap  Closure time  Distance away from arc  3 phase v single phase  Confined space  Characteristics of equipment SALISBURY BY HONEYWELL - CONFIDENTIAL

11

Electrical Safety Arc Flash Impacts

As much as 80% of all electrical injuries are burns resulting from an arc-flash and ignition of flammable clothing.

Arc temperature can reach 35,000 °F - this is

four times hotter than the surface of the sun.

Fatal burns can occur at distances over 10 ft.

Over 2000 people are admitted into burn centers each year with severe electrical burns Example of an arcing fault

SALISBURY BY HONEYWELL - CONFIDENTIAL

12

Electrical Safety Arc Blast

Electrical Arc-Flash can create blast in excess of 200 lbs/ft 2 .

Arc-Blast can cause collateral damage and extreme personal damage.

-

Explode switchgear

-

Send molten metal at extreme high velocities.

SALISBURY BY HONEYWELL - CONFIDENTIAL

13

Electrical Safety

Are you in Compliance?

Are your workers Safe?

Industry standards and regulations:

-

OSHA 29 CFR 1910 Subpart S

-

NEC 2011

-

NFPA 70E-2012 Edition

-

Various ASTM Requirements

SALISBURY BY HONEYWELL - CONFIDENTIAL

14

Electrical Safety

NEC 2011 – National Electric Code

110.16 Arc Flash Hazard Warning Switchboards, panel boards, industrial control panels, and motor control centers in other than dwelling units, that are likely to require examination, adjustment, servicing, or maintenance while energized, shall be field marked to warn qualified persons of potential electric arc flash hazards. The marking shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.

FPN No. 1: NFPA 70E-2012,

Electrical Safety Requirements for

Employee Workplaces, provides assistance in determining severity of potential exposure, planning safe work practices, and selecting personal protective equipment.

FPN No. 2: ANSI Z535.4-2007 , Product Safety Signs and Labels, provides guidelines for the design of safety signs and labels for application to products .

SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety Sample NEC Warning Article 110.16

15

SALISBURY BY HONEYWELL - CONFIDENTIAL

16

Electrical Safety NFPA 70E – 2012 Edition Standard

Electrical Safety Requirements for Employee Workplaces

-

This requirement covers all aspects of worker safety associated with electrical hazards in the workplace. Within this standard are recommendations for proper PPE (Personal Protective Equipment)

-

Addresses hazards:

 Shock  Arc Flash -

Requirements for shock and arc flash boundaries Requirements for personal protective equipment

SALISBURY BY HONEYWELL - CONFIDENTIAL

17

Electrical Safety

NFPA 70E 2012 Summary of Significant Changes

• • • • • •

All references to “FR” now changed to “ rating.

Arc Rated ”. This identifies that FR clothing is not necessarily tested to the ASTM test for arc Addition of incident energy tables for direct current (DC) systems.

Terms such as “flash protection boundary”, “flash hazard boundary”, and “flash boundary” changed to new term “ arc flash boundary ”.

The nose was added to the coverage needed from a balaclava.

Retraining shall be performed at intervals not to exceed 3 years.

Electrical safety program shall identify procedures for working :within the limited approach boundary and arc flash boundary to clarify the separation between the two boundaries.

Removal of 2* category. For 2012, all is included in category 2.

• • • •

Arc Blast is now a recognized hazard by NFPA 70E. Inclusion of this hazard may require updated assessments.

Employees must report any perceived contact to supervision.

Employers must inform contractors of any known hazards.

SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

How Do I Protect My Workers???

18

SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

NFPA 70E Approach Boundaries

19

SALISBURY BY HONEYWELL - CONFIDENTIAL

20

Electrical Safety

NFPA 70E provides two choices for selecting the appropriate PPE:

Perform an arc flash hazard analysis, and document the incident energy exposure

-

EasyPower

-

Duke Flux Software (Freeware)

-

ETAP

-

IEEE 1584 Standard

As an alternate, use the “Hazard Risk Category Classifications” table to choose the PPE level required for the task

SALISBURY BY HONEYWELL - CONFIDENTIAL

21

Electrical Safety

Salisbury Assessment Solutions (SAS) A full turn-key solution which provides an arc flash hazard analysis and the necessary PPE recommendations needed to protect workers against those hazards

SALISBURY BY HONEYWELL - CONFIDENTIAL

22

Electrical Safety What Does SAS Provide?

-

SAS will put you into compliance!

-

Engineering service designed to identify hazardous electrical conditions which may exist in commercial or industrial facilities.

-

Proper compliance training of personnel on procedures to help reduce injury/harm to the electrical worker

SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

23

• •

SAS Process Initial Review

-

Our engineers will review your line drawings and based on those drawings, identify potential risks in your work environment.

-

If line drawings are out of date or unavailable, our engineers will be onsite to identify the potential risks. Post Review

-

SAS will provide you with a full summary of the assessment as well as recommend practices to improve your organizations safety practices.

-

SAS provides the training necessary to ensure your staff is educated in safe work practices.

-

SAS will recommend the necessary PPE to provide your staff with essential protective equipment to keep them safe in the event of an arc flash.

Salisbury Assessment Solutions gives you the Tools and Training to provide a Safe Work Environment!!

SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

24

Benefits of SAS – Turn Key Solution Assessment Solutions

-

SAS will complete the Salisbury by Honeywell “One Stop” Arc Flash Solution that our competition cannot offer

 For years, Salisbury by Honeywell has offered all of the electrical PPE needed for an electrical worker.

 Now with Salisbury Assessment Solutions, Salisbury by Honeywell can offer electrical assessments and training!

SAS Consumer Promise

SAS will continue to provide the worker with the same quality in its SAS service as the industry has come to expect from the products that Salisbury by Honeywell has provided since 1855.

SALISBURY BY HONEYWELL - CONFIDENTIAL

25

Electrical Safety

Who Could Use SAS?

• Institutional • Government • Manufacturing • Hospitals • Warehousing • Marine • Military • All Non Residential Facilities With Electrical Power Requirements SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

Getting Started With Your SAS Assessment!!

26

SALISBURY BY HONEYWELL - CONFIDENTIAL

27

Electrical Safety

What Is Electrical Safety PPE?

The Term “Electrical Safety PPE” Includes All Products Available To The Worker To Ensure a Safe Work Environment

SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

Who Needs Electrical Safety PPE?

OSHA/NFPA 70E states: “For energized circuits over 50 volts or more, safety tools and personal protective equipment must be used.”

28

SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

Hazard Risk 2

29

Maximum Exposure 8 cal/cm² Minimal Protection Level 8 cal/cm² SALISBURY BY HONEYWELL - CONFIDENTIAL

30

Electrical Safety

Hazard Risk 3

Maximum exposure 25 cal/cm² Required Protection Level 25 cal/cm² SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety Hazard Risk 4

Maximum Exposure 40 cal/cm² Required Protection Level 40 cal/cm²

31

SALISBURY BY HONEYWELL - CONFIDENTIAL

32

Electrical Safety

NFPA 70E:

-

Does Not Recognize a Hazard Above 40 cal/cm ²

-

Suits With Higher Values Are Available But Are Not Recognized by NFPA 70E

May Be Needed When Using Software Method

SALISBURY BY HONEYWELL - CONFIDENTIAL

33

Electrical Safety

Make the Right Choice

Uniforms

-

HRC 1 & 2 Solution

Coveralls

3 Piece System

-

Additional Layer Do Not Use Over 11 cal/cm2 Bib Overalls / Jacket / Hood

 Higher Risk Categories •

Lab Coats

-

Unsafe

 Additional Leg Protection Needed / Leggings SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

Face Shields

Must Meet ASTM F2178-02 Must Meet ANSI Z87.1

Meet Same Criteria for ATPV Rating Given to Garments Based on ASTM F1958

34

SALISBURY BY HONEYWELL - CONFIDENTIAL

35

Electrical Safety

Face Shields

Proper Storage Will Prolong Life of Face Shield Clean With Mild Soap and Warm Water DO NOT USE Cleaners with Abrasives Dish Soap with Scents Petroleum Based Cleaners SALISBURY BY HONEYWELL - CONFIDENTIAL

36

Electrical Safety

Insulating Gloves OSHA 1910.333(a)(1) Rubber Insulating Gloves are among the most important articles of personal protective equipment for electrical workers. They are the first line of defense for contact with any energized components or lines .

SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

ASTM Labeling Chart

37

SALISBURY BY HONEYWELL - CONFIDENTIAL

38

Electrical Safety

Types of Rubber

Two Types of Rubber

-

Type I

 Flexible  Corona Cutting  UV -

Type II

 Less Flexible  Only Available in CL00 and CL0  Very Durable SALISBURY BY HONEYWELL - CONFIDENTIAL

39

Electrical Safety

Glove Inspection

• • •

Working around sharp object, in close proximity to energized parts Gloves must be inspected prior to each use There are two ways to inspect gloves

-

Manual

-

Portable glove inflator

SALISBURY BY HONEYWELL - CONFIDENTIAL

40

Electrical Safety

Gloves Reject Criteria Rejection of Gloves

-

Cuts

-

Punctures

-

Ozone checking

-

Corona Cutting

-

Embedded foreign materials

-

Oil markings

-

Gloves that leak air.

SALISBURY BY HONEYWELL - CONFIDENTIAL

41

Electrical Safety

Gloves Testing The interval between electrical retest for issued Rubber Gloves shall not exceed six months Gloves that have been electrically tested but not issued shall not be placed into service unless they have been electrically tested within previous twelve months

SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

42

Gloves Storage

Rubber gloves should be stored in glove bags

Do not store more than one pair of gloves in each bag

Do not store on or in front of truck heaters.

Do not roll , fold or tape

SALISBURY BY HONEYWELL - CONFIDENTIAL

43

Electrical Safety Glove Liner

Glove liners made from stretch fabric accommodate a range of hand sizes, absorb perspiration and improve wearer comfort and dexterity.

SALISBURY BY HONEYWELL - CONFIDENTIAL

44

Electrical Safety

Typical Products Containing Petroleum Products

• • •

Washing detergents

-

Safe Alternative Salisbury’s Salco Cleaner.

Hand soaps Use Salisbury’s Rub-Out hand cleaner.

Baby powder Use Salisbury’s 10-4 Glove Dust.

SALISBURY BY HONEYWELL - CONFIDENTIAL

45

Electrical Safety Application

Sizing of Rubber Gloves

-

To determine the proper size, measure the distance around the palm of the hand between the thumb and forefinger

SALISBURY BY HONEYWELL - CONFIDENTIAL

46

Electrical Safety Leather Protector Gloves

Leather Protector Gloves should always be worn over electrical insulating gloves to provide needed mechanical protection against abrasion or cuts. Leather protectors should never be used as work gloves and work gloves should never be used as protectors.

SALISBURY BY HONEYWELL - CONFIDENTIAL

47

Electrical Safety Arc Flash & Gloves

• NFPA 70E Requires that Voltage Rated Gloves and Protectors Must Be Worn in the Presence Of Voltage But Does Not Discuss Arc Ratings for Gloves.

• NFPA 70E Does Say That Leather Gloves Offer Good Arc Flash Protection SALISBURY BY HONEYWELL - CONFIDENTIAL

48

Electrical Safety Insulated Tools

• NFPA 70E 130.7(D)(1) • Employees Shall Use Insulated Tools and/or Handling Equipment When Working Inside the Limited Approach Boundary of Exposed Live Parts Where Tools or Handling Equipment Might Make Accidental Contact…..

• Both NFPA 70E and OSHA Require Insulated Tools When Working On or Near 50V or More While Energized SALISBURY BY HONEYWELL - CONFIDENTIAL

49

Electrical Safety Insulated Tools

• • • • •

ASTM F1505 OSHA 1910.333(c)(2) Tested to 10,000V Max Use 1000V Must Have Two Color Coating if Coated Tool

Must Show Symbol For Use in Live Voltage Situation

SALISBURY BY HONEYWELL - CONFIDENTIAL

Electrical Safety

Blankets

50

• • •

Blankets, as all other insulating products (except rubber gloves, used with leather protectors) are designed to provide protection against accidental contact with energized parts Salisbury Insulating Blankets, compliant with ASTM D1048 specification, are flexible and feature a reinforced beaded edge and eyelets for added strength and tear resistance Salisbury insulating blankets are available in Type I – natural rubber and Type II SALCOR ® rubber

SALISBURY BY HONEYWELL - CONFIDENTIAL

51

Electrical Safety Roll Blankets

Salisbury is offering insulating blanket material on a roll. Salisbury’s insulating Roll Blankets, made from a high strength fabric-reinforced TYPE II rubber or PVC clear blankets, allow workers to custom cut the blanket to fit each job assignment. The product is available in three classes: Class 00 (500v), Class 0 (1,000v) and Class 1 (7,500v). PVC is class 1 only

SALISBURY BY HONEYWELL - CONFIDENTIAL

52

Electrical Safety Insulated Rescue Hooks

An invaluable tool for any workplace, Salisbury’s rescue hook is used to withdraw an injured worker from a hazardous area. Confined spaces, vaults and the vicinities of electrical cabinets and switch gear are some of the places where the Salisbury Insulated Rescue Hook is a must.

SALISBURY BY HONEYWELL - CONFIDENTIAL

53

Electrical Safety

Newest Electrical Safety Products Premium Light Weight 40 Calorie Arc Flash Suit Universal Weight Balancing Shield Non Spark/Non Magnetic Insulate Tools

SALISBURY BY HONEYWELL - CONFIDENTIAL

54

Electrical Safety

Thank You!!

For More Information, Please Visit Us At: SalisburyByHoneywell.com

SALISBURY BY HONEYWELL - CONFIDENTIAL