eVD4 - The Smart Evolution - Primary distribution

Download Report

Transcript eVD4 - The Smart Evolution - Primary distribution

eVD4 - The Smart eVolution
Primary distribution circuit-breaker with
integrated protection, control and sensors
© ABB Group
13. April 2015 | Slide 1
eVD4: The Smart eVolution
Complete integration in a single device
HMI
(panel
interface)
Current and
voltage sensor
in each pole
© ABB Group
April 13, 2015 | Slide 2

Measuring

Protection and control

Communication
Equipped with Relion®
technology: protection
and control unit RBX615
with IEC61850 and Goose
eVD4: The Smart eVolution
Medium voltage vacuum circuit-breaker
Innovation and a sound foundation
of proven technology:
 Since 1987, over 550,000 VD4 circuit
breakers have been successfully
installed in a wide range of applications,
worldwide
 Based on Relion technology
.
© ABB Group
April 13, 2015 | Slide 3
eVD4: The Smart eVolution
Reduce time from purchase to commissioning
Standard panel
© ABB Group
April 13, 2015 | Slide 4
Version with eVD4
eVD4: The Smart eVolution
Versions, specifications, standards
Versions:
Fixed / Withdrawable for UniGear ZS1
switchgear and PowerCube units
Specifications:

Up to 17.5 kV rated voltage

Up to 2,500 A rated current

Up to 40 kA (3 s) breaking capacity
Standards:

IEC 62271, EMC EN 50263 (2000),
EN60255-26 (2007)
www.abb.com/mediumvoltage
© ABB Group
April 13, 2015 | Slide 5
eVD4 - The Smart eVolution
Components
© ABB Group
13. April 2015 | Slide 6
eVD4: The Smart eVolution
Sensors
Current
sensor
Sensor converts primary circuit current
and voltage into a signal
Rogowski coil measures current
Capacitive divider measures voltage
Voltage
sensor
© ABB Group
April 13, 2015 | Slide 7
Measurements are in class 1:
 1/5P Rogowski coil
 1/3P capacitive divider
eVD4: The Smart eVolution
Sensors
Advantages:
© ABB Group
April 13, 2015 | Slide 8

Absolutely linear voltage and current
signals

Low potential signal is safer for people
and auxiliary equipment

Extremely low energy usage

Fewer raw materials used

Automatic sensor selection, depending
on relay configuration
eVD4: The Smart eVolution
RBX615 unit based on Relion® technology
The integrated unit provides protection,
control, measuring and monitoring
functions for substations. It also protects
overhead lines, cable lines and motors.
Protection functions adapt to any radial
and meshed network, regardless of
earthing layout.
IEC 61850 compliant; supports
communication between substation
equipment and messaging system
(GOOSE) in native mode.
Dedicated automatic configuration tool
(PCM600)
© ABB Group
April 13, 2015 | Slide 9
eVD4: The Smart eVolution
RBX615 unit based on Relion® technology
GOOSE: Generic Object Oriented
Substation Event
Units based on Relion® technology
installed in switchgear communicate with
each other and, through a network switch,
with the substation’s control system.
Communication board:

Ethernet, two channels
Communication protocols:
© ABB Group
April 13, 2015 | Slide 10

Native IEC 61850 (including GOOSE)

TCP/IP Modbus®
eVD4: The Smart eVolution
RBX615 unit based on Relion® technology
Pre-configurations:
© ABB Group
April 13, 2015 | Slide 11

Feeder 1: Non-directional overcurrent protection and non-directional
earth fault protection (current only)

Feeder 2: Non-directional overcurrent protection and directional earth
fault protection based on measurement of phase voltage values
(current and voltage)

Feeder 3: Directional overcurrent protection and directional earth fault
protection based on measurement of phase voltage values and
overvoltage and undervoltage protection (current and voltage)

Motor 1: Motor protection with measurement and protection functions
based on current (current only)

Motor 2: Motor protection with measurement and protection functions
based on current and voltage (current and voltage)
eVD4: The Smart eVolution
Human-machine interface (HMI)
HMI allows the integrated unit to be
parameterized, and displays the
mimic diagram and certain values
Large, multi-page double display:
Single-line diagram (SLD) page (left)
+ Standard menu (right)
8 LEDs
Power supply: 48 ... 250 V dc/ac
© ABB Group
April 13, 2015 | Slide 12
eVD4: The Smart eVolution
Specific connector for eVD4
Connects auxiliary circuit of the circuitbreaker and integrated unit with auxiliary
switchgear circuits
Two Ethernet ports transmit digital and
communication signals
© ABB Group
April 13, 2015 | Slide 13
eVD4 - The Smart eVolution
Advantages
© ABB Group
13. April 2015 | Slide 14
eVD4: The Smart eVolution
Performance improvements and integration advantages
Performance improvements by
component harmonization and
optimization leading to a MV system
simplification and to an increase of the
overall reliability.

The eVD4 offers specific advantages
compared with a standard MV solution
in all stages of the panel life cycle

© ABB Group
April 13, 2015 | Slide 15
Advantages along the panel life cycle
Specification and ordering
Specification and flexibility:

No need to define any parameters for
the sensors

RBX615 pre-configuration can be
customized
Supply management:

© ABB Group
April 13, 2015 | Slide 16
A complete MV solution (CB, Relay and
Sensor) can be obtained with just one
single order and one single reference
Advantages along the panel life cycle
Installation, Less wiring, Flexibility
Installation:
 The eVD4 is a ready to install solution.
The components are internally wired. All
the wiring is instantaneously connected
to the switchgear through the CB plug.
Less effort for engineering and wiring:
 The switchgear is highly standardized
 Less risk of errors and increased safety
and reliability
 Easier and faster engineering
 Shorter and reliable connections
Flexibility for last minute modification:
 The integrated solution is more versatile
and flexible.
© ABB Group
April 13, 2015 | Slide 17
Advantages along the panel life cycle
Installation, Less wiring, Flexibility – Low Voltage
Compartment
Standard circuit breakers
© ABB Group
April 13, 2015 | Slide 18
eVD4
Advantages along the panel life cycle
Testing, Maintenance, Spare parts
Easy and complete testing of the whole
measurements chain by primary injection:
 It is possible to test the whole measurement
chain by a primary injection in the CB
contacts, easily accessible without any
modification in the panel.
Easy maintenance, reduced Mean Time To
Repair (MTTR):
 Standard accessories with few variances,
readily available for easy maintenance.
© ABB Group
April 13, 2015 | Slide 19

Self-diagnostic functions

System quickly repaired in case of failure (no
stops in production)

Optimization of the spare parts in stock
Advantages along the panel life cycle
Testing, Maintenance, Spare parts
Easy removable integrated protection and control unit:
© ABB Group
April 13, 2015 | Slide 20

The unit is fixed in a docking unit by means of screws

Facilitates easy access and service
Advantages along the panel life cycle
Retrofit and revamping
Extremely simple and straightforward
solution for retrofitting and revamping:

Faster and easier revamping process
Flexibility thanks to sensors high range
of linearity and RBX615 programmability

No need to act on CTs and VTs as they
come with the eVD4


© ABB Group
April 13, 2015 | Slide 21
Reduced effort for wiring and retesting
Advantages along the panel life cycle
Switchgear simplification and easy operation
© ABB Group
April 13, 2015 | Slide 22

Specification

Ordering

Easy to install

Less effort for engineering and wiring

Less effort for Factory Acceptance
Test (FAT) while increasing safety and
reliability

Flexibility and easier last minute
modifications

Extremely simple and straight forward
solution for retrofitting and revamping

Easy maintenance and reduced Mean
Time To Repair (MTTR)

Optimization of the spare parts in
stock
eVD4 - The Smart eVolution
More than a product
© ABB Group
13. April 2015 | Slide 23
eVD4: The Smart eVolution
Not only a product: Training
Our specialized team helps you get the most out of the integrated circuit
breaker:
eVD4

Level 1 (Basic): circuit-breaker and basic maintenance

Level 2 (Advanced): advanced maintenance

Level 3 (Specialist): service activities
Integrated protection and control unit (RBX615)

© ABB Group
April 13, 2015 | Slide 24
Programming control and protection functions (communication,
GOOSE, etc.)
eVD4: The Smart eVolution
Not only a product: Customer support
1.
Complete set of documentation and marketing material:
All the information you may need on the eVD4 documentation
2.
A specific eVD4 support line is available
Email : [email protected]
3.
© ABB Group
April 13, 2015 | Slide 25
Technical drawings and electrical diagrams available in electronic
version
eVD4 - The Smart eVolution
What is coming next
© ABB Group
13. April 2015 | Slide 26
eVD4: The Smart eVolution
Integrated protection and control unit RBX615
New Features for the release 2.0:
© ABB Group
April 13, 2015 | Slide 27

RS485 CommCard and Modbus RTU

Optical Ethernet COM card

HMI function keys

Automatic relay configuration recovery by the HMI (a backup of
the application will be stored in the HMI)

Automatic parameterization of the CB condition monitoring
function for an effective diagnostic of the CB.

eVD4 used with RIO600 to have flexibility in the number of I/Os
© ABB Group
AprilApril
13.
13, 2015 | Slide 28
eVD4 - The Smart eVolution
Protection Functions
© ABB Group
13. April 2015 | Slide 29
eVD4: The Smart eVolution
Protection Functions
© ABB Group
April 13, 2015 | Slide 30
eVD4: The Smart eVolution
Protection Functions
© ABB Group
April 13, 2015 | Slide 31
eVD4: The Smart eVolution
Protection Functions
© ABB Group
April 13, 2015 | Slide 32
eVD4 - The Smart eVolution
Digital I/Os
© ABB Group
13. April 2015 | Slide 33
eVD4: The Smart eVolution
Digital Inputs
© ABB Group
April 13, 2015 | Slide 34
eVD4: The Smart eVolution
Digital Outputs
© ABB Group
April 13, 2015 | Slide 35