`YGFC` FAN COIL UNITS NEW PRODUCTS

Download Report

Transcript `YGFC` FAN COIL UNITS NEW PRODUCTS

‘YGFC’ FAN COIL UNITS

NEW PRODUCTS - 2006

YGFC FAN COIL UNIT

• FACTORY LOCATED IN GUANGZHOU, CHINA

– CAPACITY = 300,000 UNITS/YEAR = 1,000 UNIT/DAY!

• CERTIFICATION

– ISO 9001:2000, GB/T 19002:2000 CERTIFIED FACTORY – GB/T 19232:2003 CERTIFIED TEST LAB (ONLY 2 IN

CHINA)

FEATURES

YGFC FAN COIL UNIT

– CE (TUV) CERTIFIED

– CONFIGURATION: CONCEALED, CABINET, HORIZONTAL,

VERTICAL

– COIL: 2 CHOICES, CONVENTIONAL OR DISTRICT COOLING – 10 SIZES (70-600 L/S, 1-15KW COOLING) – DRAIN PAN: DIE-FORMED, ANTI-RUST PAINTED, INSULATED – MOTORS: DIRECT DRIVE, THERMAL PROTECTION, BALL

BEARING

• TESTING – COIL PRESSURE TESTED AT 2400 KPA – MOTOR TESTED FOR EARTH LEAK AND CURRENT

YGFC FAN COIL UNIT

• SPECIFICATION – 3 OR 4 ROW COIL, WORKING PRESSURE 1600kPa – FILTER: 6mm NYLON – 1mm GALV.STEEL CASING FOR ADDED NOISE

REDUCTION

– INSULATED PAINTED DRAIN PAN – 10mm COATED FIBREGLASS INSULATED FAN DECK &

COIL SECTION

YGFC FAN COIL UNIT

• OPTIONS – CASING: FULLY POWDER COATED – FILTER: 25 MM ALUMINUM – FINS: HYDROPHILIC, EPOXY COAT, COPPER – STAINLESS STEEL DRAIN PAN – MOTORS: IP 23 AS STANDARD, 42 & 54 AS OPTION – 6mm CLOSED CELL INSULATED RETURN PLENUM,

ELECTRIC HEATER

YGFC FAN COIL UNIT

• ADVANTAGES – CHOOSE FROM 10 MODEL SIZES TO MATCH ROOM

NEED

– LOW HEIGHT (250MM) SUITABLE FOR TOWER

BLOCKS

– WHISPER-QUIET OPERATION – RESISTANCE TO CORROSION – ADAPTABILITY TO STANDARD OR DISTRICT

COOLING APPLICATION

YGFC FAN COIL UNIT

• ADVANTAGES – EASE OF MAINTENANCE – LOW RISK OF LEAKS FROM DRAIN PAN AND COIL

CONNECTIONS

– LOW RISK OF BEARING WEAR – LONGER MOTOR LIFE – LONGER UNIT LIFE! – ECONOMICAL LIFE CYCLE

DISTRICT COOLING

• Definition – Produce chilled water at a central plant – Distribute to buildings for AC needs – Charge subscribers based on actual usage • Benefits – Diversity

reduced capacity, reduced cost

– Large size

$/Ton, 11kV, eff systems & eqpt, life

– Containment

maintenance (AC vs WC), noise

– Cogeneration and use of waste energy

DISTRICT COOLING

• WHERE – City Centers: large buildings & loads, premium space – Airports: large buildings & loads, continuous operation – Industrial Centers: many process loads, reliability • DESIGN – Low flow (1.5 gpm/ton)

high ΔT, small pipes & pumps

– Low supply chilled water temperature

smaller AS

– Check for laminar flow in FCU

poor cooling

– Reynolds number > 4000 – Ensure appropriate ΔT on airside of heat exchanger

YGFC FAN COIL UNIT

• POINTS TO NOTE! – THIS IS A ‘HIGH VOLUME’ PRODUCT - SIMPLE

SPECIFICATION ALLOWS LOW COST & SPEEDS UP LEAD TIMES

– TARGET LOW END SPEC. PROJECTS, AND SALES TO

DISTRIBUTORS AND END USERS

– LESS RANGE OF OPTIONS & SQ’S WHEN COMPARED TO

‘EUROPEAN’ FCU’S

– FCU CASING NOT THE MOST ATTRACTIVE! – ARE YOU ABLE TO ORDER & HOLD STOCK UNITS??

YGFC FAN COIL UNIT

• POINTS TO NOTE! – THERMOSTATS & CONTROLS AVAILABLE FROM ASIA

PACIFIC ARE NOT CE CERTIFIED

– VALVES ARE NOT FACTORY FITTED – FILTER REMOVAL ON CEILING CONCEALED UNIT IS

DIFFICULT AS IT REQUIRES SCREW REMOVAL

– EUROVENT CERTIFICATION WILL BE MADE LATE 2006

YGFC SOFTWARE

YORK DESIGNED, INDEPENDENT OF YORKWORKS

YGFC SOFTWARE

- GENERATES TECHNICAL SCHEDULES…

- GENERATES

WORKS ORDER

YGFC SOFTWARE

•ALSO GENERATES… -OPTIMUM FCU

CONTAINERISATION FOR SHIPPING

-CATALOGUE DATA

SHEETS & TECHNICAL SPECIFICATIONS

-PRICE SUMMARY

TECHNICAL DOCUMENTATION PRICING SQ’S & SQ PRICING ORDERS SHIPPING WARRANTY SOFTWARE

WHO TO CONTACT….

James Long ([email protected]), Alan Hinton ([email protected]) Alan Hinton ([email protected]) James Long ([email protected]), c.c. to Alan Hinton ([email protected]) Jackey Que ( [email protected]

), c.c to James Long ([email protected]) Erica Wang ([email protected]) Ding yue ( [email protected]

), c.c to Kevin Lau ([email protected]) Alan Hinton ([email protected])