Introduction
What is the PCIMS ?
PCIMS :Process Control Information Management System
Each plant as an individual process area shall
consist of an integrated production control system
and the main units of integrated production system
consist of :
UCB : Unit Control Building which is the central
location for controlling , PCB: process control
building
RIB which will house all I/O’s and the controllers
What is the DCS ?
DCS is Distribution Control System
Vendor ,Yokogawa centum CS3000
which consist of two main parts :
HIS : Human Interface Station
- it is operator station that is used to monitor and control the
process .
FCS : Field Control Station
FCS is a stand alone unite capable of performing a full data
acquisition control ,and all control function are executed
there with all I/O’s analog & digital signal.
What is the PESS ?
PESS : Programmable electronic safety system
Vendor : ( Triconex )
which is used for emergency shutdown (ESD) function
and other equipment tripping function .
What is the PLC ?
PLC is Programmable Logic Control
Vendor: Modicon (PLC ) used for control of some packaged
mechanical equipment like Demain package & Flare system .
What is MMS ?
MMS : Machine Monitoring system Vendor : ( Bentlt Nevada )
Machine Motoring System , the Bently Nevada system is
used to monitor the vibration of the shaft and the baring
shaft temperature , and to send a signal as hard wire to the
shut down system “ PESS” to trip the machine . Which is
used in Comp package & critical big Pump..etc.
Third party Equipment
Like :Tank gauging ,Flow computer for custody meter
and Vibration monitoring “ System 1”
What is RIB ?
RIB is Remote Instrument Building
The Remote Instrument Building RIB, which will house, the
DCS controller as FCS ,HIS ,PESS / PLC controller and their
cabinets and all other 3rd party equipment like Tank gauging
,Vibration monitoring , Flow computer , Power supply
distribution panel ,Fire and Gas panel and Uninterruptible
power supplies (UPS ) .
What is inside RIB’s
- DCS filed control station “ FCS “ Cabinets
- Programmable electronic shut down system “PESS Cabinets
- Machine monitoring system “ MMS Cabinets
- Programmable logic control “PLC” Cabinets
- Other equipment such as Tank Gauging , Custody metering
Cabinets
- Air unit
- Fire and gas panel
- All field instruments , wiring signals
- Marshaling panels
-Terminal blocks
-Servers cabinets
RIB
One pair copper
cable
Serial communication link
V-net cable 10 base 5
FCS
JB
B/N
TMR
FOPP
PLC
FCU
YNT
Optical converter
Copper multi core
shielded cable
TB
F TA
Hard wire
FIO
Black box
HIS
FTA or I/O's cable
twisted multi core ,as TEL cable
V-net cable 10 base 2
coaxial cable
FOPP
YNT
HIS
HIS
Control Room
V-net converter 10 base 5 to 10 base 10
HIS
Fiber optic cable
Fiber optic cable
RIB YNT
V-Net cable 10
base 5
Control room YNT
V-Net 10 Base
5 cable
FCS
FIO
V-net 10 Base 2
cable
DCS OPC server
HIS
To do down loading , Tag
equalizing between the
HIS,s,Trending , and
viewing DCS logic
RIB
Control Room
Fiber
Fiber optic
100 MP/S
PLC, PESS
Fiber optic
1GP/S
copper
PESS – PLC OPC
server
One jacket fiber optic cable consist of 6
orange cable which consist of 4 wire
2
The total is 12 pare wire inside one jacket
DCS OPC
server