Rated Data
Operating voltages
s
V
System / Product
230 ... 415 AC
208 ... 690 AC
(-15% / +10%)
Sales
Communication
Service & Support
Annex
Gliederungspunkt 10
200 ... 460 AC
400 ... 600 AC
400 ... 690 AC
400 ... 1,000 AC
(-15% / +10%)
Control supply voltages
V
110 ... 230 AC
220 ... 400 AC
115 AC
230 AC
(-15% / +10%)
(-15% / +10%)
Frequencies
Hz
50 / 60
50 ... 60
Currents (at 40° C)
Power
A
17 ... 1,200
29 ... 1,214
kW
7.5 ... 630
15 ... 710
15 ... 710
22 ... 1,200
(with 400 V)
(-5% / +5%)
(standard circuit)
(-10% / +10%)
(standard circuit)
(inside-the-delta circuit) (inside-the-delta circuit)
Number of sizes
Market Introduction Concept
5
5
CC PM4 / MM2
07/2004
2
Automation and Drives
ATS 48 - 3RW44
MarCom Concept
SIRIUS
Sirius
Softstarter
Soft
Starters
3RW4
Price Comparison
Introduction
Situation
Market
Basic Functions
System / Product
Soft start-up / soft run-down
Bridging contact system
Device self-protection
Motor overload protection
Adjustable current limiting
Sales
Communication
Service & Support
Annex
Gliederungspunkt 10
Inside-the-delta circuit
Breakaway impulse
Power semiconductors (thyristors)
Integration in modular system
Market Introduction Concept
s
X
X
-
X
X
X
X
X
X
X
only up to 415 V
X
X
X
in 3 phases
in 3 phases
-
X
CC PM4 / MM2
07/2004
3
Automation and Drives
ATS 48 - 3RW44
MarCom Concept
SIRIUS
Sirius
Softstarter
Soft
Starters
3RW4
Price Comparison
Introduction
Situation
s
Market
Extended Functions
System / Product
Display
Tightening torque control
Communication
External display/operating module
Pump run-down
X
X
X
X
X
X
X
X
X
X
Braking
X
X
Creep speed / positioning
Programmable inputs/outputs
Measured operating values display
-
X
3/2
4/3
X
X
Sales
Communication
Service & Support
Annex
Gliederungspunkt 10
Market Introduction Concept
CC PM4 / MM2
07/2004
4
Automation and Drives
ATS 48 - 3RW44
MarCom Concept
SIRIUS
Sirius
Softstarter
Soft
Starters
3RW4
Price Comparison
Introduction
Situation
Market
System / Product
Sales
Communication
Service & Support
Annex
Gliederungspunkt 10
Advantages
/ Disadvantages
Analog output
s
Via Profibus DP
No bridging contact system
Smaller size, lower costs
Only 2 of 3 relay outputs
are programmable
Only 2-phase current measuring
(no ground fault detection)
Only 2 parameter sets
No positioning mode
No tightening torque
limiting possible
Alphanumeric LC display
3 of 4 relay outputs
are programmable
3-phase current measuring
(ground fault detection)
3 parameter sets
Positioning, creep speed
Tightening torque limiting
Market Introduction Concept
Graphical LC display
CC PM4 / MM2
07/2004