Transcript Fan motor amp. draw
Arthur Miller, CMS, RCT HVACR Training Consultant www.kam-associates.com
OUTLINE
1. Air Flow Terminology 2. Classification of Duct Systems 3. Duct Design Methods 4. Fans 5. Ducts 6. Air Flow & Issues with Design of Ducts 7. Filters 8. Conclusion(s) & Solution(s)
A
’
PRACTICAL APPROACH
’
ALONG WITH SOME THEORY
3 ¼ x 12 wall stack
Who is Liable?
A. The contractor – from design to installation to service B. The filter manufacturer C. The building owner D. Nobody
AIR FLOW TERMINOLOGY
CFM
•
Volume or Quantity of air
•
measured in Ft 3 /min
FPM
•
Velocity of the air
•
measured in Ft/min
STATIC
•
Resistance to the air flow
•
measured in inches of water column (
“
w.c.)
Classification of Duct Systems 1.
Low Pressure System - up to 2 ” w.c.
2.
Medium Pressure System - up to 6 ” w.c.
3.
High Pressure System - up to 10 ” w.c.
Duct Design Methods 1. Velocity Method 2. Static Regain Method 3. Equal Friction Method
Velocity Method 1.
Select velocity for main and branch ducts.
2.
Determine duct sizes.
3.
Determine frictional pressure drops.
4.
Select a fan.
Static Regain Method 1.
2.
3.
Select velocity for main ducts.
Velocities are selected so the static pressure at each take-off offsets the pressure loss of the preceding section of ductwork.
Select a fan.
Equal Friction Method 1.
Selection of friction loss.
2.
Volume of air is known.
3.
Duct is sized based on 1 and 2 above.
4.
Select a fan or fan is selected.
FANS The
‘
HEART
’
of the air delivery system
Relationship between
STATIC
and
CFM
in respect to a FAN
Are they
A. a direct relationship B. an indirect relationship C. neither
STATIC CFM
STATIC CFM
two configurations of fans
1. AXIAL 2. CENTRIFUGAL
First, the
Axial Fans
Definition?
What makes an axial fan an axial fan?
ANSWER
Discharge Air Flow PARALLEL to shaft of motor/fan
(NO change in direction)
TYPES
1. tubeaxial 2. vaneaxial 3. propeller
TUBEAXIAL
1.
2.
3.
operates at pressures up to 16 ” wc wheel turns faster than propeller fan efficiency up to 65%
VANEAXIAL
1.
2.
3.
operates at pressures up to 20 ” wc uses guide vanes to improve efficiency and pressure most energy efficient fan
PROPELLER
1.
2.
3.
operates at low speeds handles large volumes of air at low pressure and at free delivery efficiency is usually less than 50%
Performance of
PROPELLOR
Fans
PROPELLOR FAN
What is the LOADING component on a PROPELLOR fan?
A. CFM B. FPM C. STATIC
STATIC
This
‘
LOAD
’
is then imposed on the motor.
How will the motor respond?
STATIC AMPS
STATIC AMPS
APPLICATION(S)
(1) The condenser conditioner is on very What will happen to the: an air dirty.
fan delivery in cfm?
fan motor amp. draw?
Fan delivery in cfm
Increases Decreases Remains the same
Fan delivery in cfm
Increases
Decreases
Remains the same
Fan motor amp. draw
Increases Decreases Remains the same
Fan motor amp. draw
Increases
Decreases Remains the same
(2) What about a filter on an ice machine condenser? What will happen to the: fan delivery in cfm?
fan motor amp. draw?
Fan delivery in cfm
Increases Decreases Remains the same
Fan delivery in cfm
Increases
Decreases
Remains the same
Fan motor amp. draw
Increases Decreases Remains the same
Fan motor amp. draw
Increases
Decreases Remains the same
(3) Consider a window fan. Is ductwork connected to the fan?
1. YES 2. NO
(3) Consider a window fan. Is ductwork connected to the fan?
1. YES 2. NO
Now, the
Centrifugal Fan
Definition?
What makes a centrifugal fan a centrifugal fan?
ANSWER
Discharge Air Flow PERPENDICULAR to shaft of motor/fan
Types of Centrifugal Wheels 1. Backward Inclined (BI) 2. Air Foil Wheels (AF) 3. Forward Curve Wheels (FC) 4. Radial Blade Wheel
Backward Inclined (BI)
Backward Inclined (BI) 1.
2.
3.
4.
used with high pressure systems high flow high efficiency noisy
Air Foil Wheels (AF)
Air Foil Wheels (AF) 1.
2.
3.
4.
used with high pressure systems high flow highest efficiency noisy
Forward Curve Wheels (FC)
Forward Curve Wheels (FC) 1.
2.
3.
4.
used with medium pressure systems high flow best for moving large volumes against low static quiet
Radial Blade Wheel
Radial Blade Wheel 1.
2.
3.
used with high pressure systems medium flow best for moving air against high static and contaminated airstreams
Performance of
CENTRIFUGAL
Fans
CENTRIFUGAL FAN
What is the LOADING component on a CENTRIFUGAL fan?
A. CFM B. FPM C. STATIC
CFM
This
‘
LOAD
’
is then imposed on the motor.
How will the motor respond?
CFM AMPS
CFM AMPS
MOVIE TIME
APPLICATION(S)
How would following you questions answer the regarding CENTRIFUGAL fans?
(1) An addition has been added to a building and the duct system has been added onto include this addition. What will be the: A.
fan delivery in cfm?
B.
fan motor amp. draw?
Fan delivery in cfm
Increases Decreases Remains the same
Fan delivery in cfm
Increases
Decreases
Remains the same
Fan motor amp. draw
Increases Decreases Remains the same
Fan motor amp. draw
Increases
Decreases
Remains the same
(2) As the air filter gets contaminated, what will be the: more A.
fan delivery in cfm?
B.
fan motor amp. draw?
Fan delivery in cfm
Increases Decreases Remains the same
Fan delivery in cfm
Increases
Decreases
Remains the same
Fan motor amp. draw
Increases Decreases Remains the same
Fan motor amp. draw
Increases
Decreases
Remains the same
(3) You remove a supply air panel on a
‘
hot
’
day just to cool you off.
What will be the: A.
fan delivery in cfm?
B.
fan motor amp. draw?
Fan delivery in cfm
Increases Decreases Remains the same
Fan delivery in cfm
Increases
Decreases Remains the same
Fan motor amp. draw
Increases Decreases Remains the same
Fan motor amp. draw
Increases
Decreases Remains the same
‘
CENTRIFUGAL
’
FAN PERFORMANCE
Fan Performance depends on (1) CFM (2) Outlet Velocity (3) Static Pressure (4) RPM (5) Brake Horsepower
Determining Fan CFMs (1) Using a Fan Curve (2) Using a Fan Chart (3) Using a Fan Law (4) Using Instruments
(1) Using a Fan Curve
Relationship between
STATIC
and
CFM
in respect to a fan
STATIC CFM
STATIC CFM
Relationship between
STATIC
and
CFM
in respect to the duct system
CFM STATIC
CFM STATIC
1 HP Original Operating Point 5 HP 3 HP New Operating Point
(2) Using a Fan Chart
PSC Motor
ECM Motor
And now, the new kid on the block.
Dec Star
Movie
Using a Fan Law
1. six fan laws 2. HVACR is affected by one of them
The physics of air flow dynamics dictates the following:
•
CFM – varies as the fan speed
•
Static – varies as the SQUARE of the speed
•
HP – varies as the CUBE of the speed
APPLICATION If we increase the cfm
’
s by 20%, what will be required of the motor speed( rpm )?
+ 20%
If we increase the cfm
’
s by 20%, what will happen to the static in the system?
+ 40%
If we increase the cfm
’
s by 20%, what will horsepower motor?
happen required to from the the
+ 80%
Using Instruments
1. Anemometer 2. Velometer 3. Manometer with Pitot Tube 4. Balometer
So why all the fuss about fans ?
Because they must deliver a volume of air that satisfies two requirements:
a. Equipment Efficiency b. Customer Satisfaction
AIR FLOW
So how much CFM can you
‘
shovel
’
into a duct?
That takes us to the
DUCT CALCULATOR
‘Rule of Thumb’ Design Static Pressures .10 (.08) for SUPPLY AIR duct .08 (.06) for RETURN AIR duct .08 (.06) for HEAT PUMP SUPPLY duct .06 (.04) for HEAT PUMP RETURN duct
Furnace Fan External Static Pressure .5
”
w.c.
for the furnace fan, then subtract any external components:
ACCA Manual D Component Static Pressure 1. Air conditioner coil = .25
”
w.c.
2.
Filters = .10
”
w.c.
3. Electric heaters = .10
”
w.c. to .20
”
w.c.
4. Humidifiers = .10
”
w.c.
5. Supply Outlets = .03
”
w.c.
6. Return Inlets = .03
”
w.c.
7. Dampers = .03
”
w.c.
Example #1
• • • • • • •
Furnace fan = less AC coil = less air filter = less return grilles = less dampers = left for duct system = .50
- .25
- .10
less supply registers = - .03
”
w.c.
- .03
- .03
.06
” ” ” ” ” ”
w.c.
w.c.
w.c.
w.c.
w.c.
w.c.
Example #2
• • • • • • •
Furnace fan = less AC coil = less air filter = less return grilles = less dampers = left for duct system = .50
- .00
- .10
less supply registers = - .03
”
w.c.
- .03
- .03
.31
” ” ” ” ” ”
w.c.
w.c.
w.c.
w.c.
w.c.
w.c.
Designing the Duct System
Length of duct - measured
Fittings - Equivalent Length tables
Velocity Factor - Equivalent Length tables
Supply and Return Plenums
Take-off fittings
Fitting Velocity Factor EL Values 0 35 1 45 2 55 3 65 4 70 5 or more 80 20 30 35 40 45 50 65 75 85 95 100 110
Fitting Velocity Factor EL Values 0 35 1 45 2 55 3 65 4 70 5 or more 80 20 30 35 40 45 50 65 75 85 95 100 110
CONCLUSION
The equivalent length(EL) of the duct system has a direct relationship to the
STATIC
FILTERS
Filters
in relation to the
SYSTEM
STUDY
•
ASHRAE
•
Published October 2012
•
by John Proctor, P.E.
Member ASHRAE
•
California Energy Commission field research
•
Two year old homes
•
Most common replacement filter used is a 1 in. pleated filter
•
Air Conditioning Contractors of America ’s Manual D
•
assumes pressure drop through a filter to be approx. 0.10 in. w.c.
Field installations showed PD far in excess of 0.10 in. w.c.
Static pressures for 34 split AC/furnaces
Static pressures for 34 split AC/furnaces Metric Mean: in. w.c.
Range: in. w.c.
Filter PD Return P S Total ESP 0.282
0.275 – 0.792
- 0.417
- 0.143 – - 0.928
0.887
0.533 – 1.21
Static pressures for 34 split AC/furnaces Metric Mean: in. w.c.
Range: in. w.c.
Filter PD Return P S Total ESP 0.282
0.275 – 0.792
- 0.417
- 0.143 – - 0.928
0.887
0.533 – 1.21
Static pressures for 34 split AC/furnaces Metric Mean: in. w.c.
Range: in. w.c.
Filter PD Return P S Total ESP 0.282
0.275 – 0.792
- 0.417
- 0.143 – - 0.928
0.887
0.533 – 1.21
Static pressures for 34 split AC/furnaces Metric Mean: in. w.c.
Range: in. w.c.
Filter PD Return P S Total ESP 0.282
0.275 – 0.792
- 0.417
- 0.143 – - 0.928
0.887
0.533 – 1.21
Research results of PD for 53 ducted systems.
Filter face area required for 0.05
”w.c. PD at 400 cfm/ton for one manufacturer ’s line of filters 16 x 25 = 400 in 2
Filter face area required for 0.05
”w.c. PD at 400 cfm/ton for one manufacturer ’s line of filters
•
The following two charts are tests performed by Kevin O ’Neill.
•
HVAC Service Manager
•
Carolina Clg. & Plbg.
•
Surfside Beach, SC
Filter Pressure Drop Table 20 in. x 20 in. x 1 in. – clean except as noted FILTER NAME Air flow hood and egg crate filter grille PRESSURE DROP (IN. W.C.) .03 in. Standard fiber glass filter Brand A Standard fiber glass filter Brand B Very dirty Brand A 1 in. thick pleated Brand C - clean .075 in. .08 in. .15 in. .2 in. 1 in. thick pleated Brand D - clean .2 in. Dirty 1 in. thick pleated Brand C @ 1 month .24 in. Dirty 1 in. thick pleated Brand C @ 3 months .32 in. AIRFLOW 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm
Filter Pressure Drop Table 20 in. x 20 in. x 1 in. – clean except as noted FILTER NAME Air flow hood and egg crate filter grille PRESSURE DROP (IN. W.C.) .03 in. Standard fiber glass filter Brand A Standard fiber glass filter Brand B Very dirty Brand A 1 in. thick pleated Brand C - clean .075 in. .08 in. .15 in. .2 in. 1 in. thick pleated Brand D - clean .2 in. Dirty 1 in. thick pleated Brand C @ 1 month .24 in. Dirty 1 in. thick pleated Brand C @ 3 months .32 in. AIRFLOW 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm
Filter Pressure Drop Table 20 in. x 20 in. x 1 in. – clean except as noted FILTER NAME Electrostatic filter Brand E Electrostatic filter Brand F Electrostatic filter Brand G PRESSURE DROP (IN. W.C.) .125 in. .14 in. .29 in. Electrostatic filter Brand H .35 in. Combination electronic, charcoal & fiber glass - clean .18 in. Same filter after 1 month of use Same filter after 3 months of use .34 in. .45 in. AIRFLOW 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm
Filter Pressure Drop Table 20 in. x 20 in. x 1 in. – clean except as noted FILTER NAME Electrostatic filter Brand E Electrostatic filter Brand F Electrostatic filter Brand G PRESSURE DROP (IN. W.C.) .125 in. .14 in. .29 in. Electrostatic filter Brand H .35 in. Combination electronic, charcoal & fiber glass - clean .18 in. Same filter after 1 month of use Same filter after 3 months of use .34 in. .45 in. AIRFLOW 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm 800 cfm
CONCLUSION
every
system has air flow issues
CONCLUSION
Unfortunately there will always be those who: 1.
2.
3.
4.
will not keep up with technology.
have always done it this way.
don ’t need to know that.
will do it the least expensive way.
SOLUTIONS
All designers of air flow systems need to check the manufacturer ’s specs.
of equipment designing a system.
before
SOLUTIONS
Filters may be a point of interest for poor performance of equipment and comfort.
SOLUTIONS
The consumer is getting smarter about our industry and making demands on us.
SOLUTIONS
Professionalism has to be promoted inside and outside the industry.
SOLUTIONS
Continuing Education