Knowledge is Power Belimo Energy Valve*

Download Report

Transcript Knowledge is Power Belimo Energy Valve*

Belimo Energy Valve™

Delta T Manager™

Energy Valve Delta T Manager 1

Presentation Agenda

• • • • •

Low Delta T at the Coil Some of Low Delta T Causes Low Delta T

• • • • Cost of Overflowing Coil Cost of Chiller Staging Cost of Over Pumping Occupant Comfort

Does it Really Work?

Benefits

Energy Valve Delta T Manager 2

Low Delta T

at the Coil

Low Coil Delta T = Inefficient Heat Transfer Increase GPM >> No Increase in Energy output More Pump HP >> Reduction in Plant Efficiency Energy Valve Delta T Manager 3

Low Delta T

Some of Low Delta T Causes

Low Control Set Point

Fouled Coils

Low Valve Authority

Energy Valve Delta T Manager 4

Low Delta T

Coil Power vs Delta T Behavior

Energy Valve Delta T Manager 5

Low Delta T

Cost of Overflowing the Coil …

400000 350000

335000 330000

300000 250000

Coil Power Curve 2 1

35 30 25 20 200000 150000 100000 50000

Delta T Curve

0 0 5 10 15 20 25 30 35 40

GPM

45 50 55 60

55 GPM

65 70

65 GPM

75 80 0 15 10

12 °F 10.5

°F

5 Energy Valve Delta T Manager 6

Low Delta T

Cost of Overflowing the Coil …

BTUh GPM Pump hp

1

330,000

2

335,000 55 GPM 65 GPM Hp increase = (65/55) 3

Δ

1.5% 18% 65%

HP

2

HP

1  ?

 

GPM

2

GPM

1   3 Energy Valve Delta T Manager 7

Delta T Manager™

Cost of Chiller Staging Chiller Plant Efficiency Design Condition

• Design ΔT=12 o F (54 o F - 42 o F) • 360 GPM • 1 Chiller, 90% Load (180 Ton)

360 GPM Loop flow

Energy Valve Delta T Manager 8

Delta T Manager™

Cost of Chiller Staging Chiller Plant Efficiency Low ΔT

• • • ΔT=

10.4

o F

(52.4

o F - 42 o F)

415 GPM 2 Chillers

, 45% Load (180 Ton)

415 GPM Loop flow

No change to the load, but a 2 nd Pump and 2 nd Chiller are started.

Energy Valve Delta T Manager 9

Low Delta T

Cost of Over Pumping Delta T Manager Signal DDC Signal Wasted Pumping Delta T Manager On Delta T Manager On

Energy Valve Delta T Manager 10

Delta T Manager™

Occupant Comfort

“How can I let the Delta T Manager limit flow if it doesn’t measure discharge air temperature?

What about occupant comfort?!?”

11

Delta T Manager™

Occupant Comfort

400000 Delta T Manager adjusts the valve if the ΔT drops below the set point in order to maintain peak coil efficiency 35

335000 325000

350000 300000

Virtually No Power Reduction Delta T Curve

30 25 250000

Power Saturation

20 200000

Power Curve

150000 15 10

Delta T Set Point

100000 5 50000 0 0 5 10 15 20 25 30 35 40

GPM

45 50 55 60

55 GPM

65 70

65 GPM

75 80 0 Energy Valve Delta T Manager 12

Delta T Manager™ Does it really work?

Energy Valve Delta T Manager 13

Case Study

Large Tech Company in North Carolina D T Management

Flow Control Position Control

96 GPM

144 GPM 240 GPM Energy Valve Delta T Manager 14

Case Study

MIT University Hayden Library - Boston, MA

• •

Building and Project Details 150,000 sq. ft. on 3 floors 6 AHU provide majority of the cooling

Results Aug 9 - Oct 9, 2010

D

T = 6.15

°F

Aug 9 - Oct 9, 2011

D

T = 12.14

°F

Energy Valve Delta T Manager 15

Case Study

University of Miami Hospital

• • • •

Building and Project Details

Rosenstiel Building 11 AHUs 2600 Tons of Cooling

Over 10,000 GPM

• • • •

Results

Delta T raised from

5.5

°F

to 10.5

°F Flow ~

5600 GPM

Estimated $66,000/yr savings Estimated 2.9 year payback Energy Valve Delta T Manager 16

Delta T Manager™

Benefits

Coil

• • ΔT Managing for peak coil efficiency Optimization in retro-fit applications •

Chiller Plant

• Improved chilled water plant efficiency • Released chiller capacity •

Pump

• Reduced pump energy •

Occupant Comfort

• No reduction in supplied energy Belimo Americas Danbury, Connecticut 17

Thank You !

Visit ( www.EnergyValve.com

) or Contact Belimo (800) 543-9038

Thank You

Energy Valve Delta T Manager 18