© ABB Ltd. - 1
01-04-06 -
PRODUCT
PRESENTATION
VHA PANEL WITH
HPA12 CIRCUIT
BREAKER
ABB
© ABB Ltd - 2
VHA 12 PANEL
Designed and type tested to
meet requirements of IEC 298
& 694 / IS:3427
Air insulated indoor switchgear
Metal clad construction
Internal arc tested
IP4X degree of protection
externally and IP2X between
compartments
Independent exhaust vents for
all HT compartments
ABB
© ABB Ltd - 3
VHA 12 PANEL
Integral Earthing Switch
optional
Normal service conditions: Min
ambient temp:-5oC, Max
ambient temp:+40oC
Up to 3000A in panel without
forced cooling
Quality System CertificationISO 9001
Environmental Management
System- ISO 14001
ABB
© ABB Ltd - 4
BREAKER COMPARTMENT
Cassette mounted breaker
with isolated position on
cubicle front door
Racking in/out of breaker from
test to service position and
vice-versa with cubicle door
closed only
Mechanical interlock to
prevent racking in/out of
breaker, when breaker is in
closed position
Live parts covered by
automatic shutters when
breaker is racked out
ABB
© ABB Ltd - 5
METERING COMPARTMENT
Metering compartment with
numerical/static/electromagnetic relays, indicating
meters, lamp and control
switches
Protection and measuring
apparatus customized as per
requirement
ABB
© ABB Ltd - 6
CABLE AND CT COMPARTMENT
Spacious construction to
accommodate 1 set of CTs
and 2 runs of cables
Option of rear extension to
accommodate extra CTs or
cables
Adequate height for cable
termination
ABB
© ABB Ltd - 7
PT COMPARTMENT
Withdrawable line PT provided
in the breaker panel
Removable fuses mounted on
the PT
Safety shutters between PT &
Cable compartment close
automatically on PT
withdrawal
ABB
© ABB Ltd - 8
BUSBAR COMPARTMENT
Spacious busbar compartment
for adequate air clearances
Option for busbar insulation
available
Option for shrouds on joints
available
ABB
© ABB Ltd - 9
HPA BREAKER
The HPA type circuit breaker is
designed and tested to meet
requirements of IEC 56 / IS :
13118
SF6 gas used as insulation
and arc interruption medium
Arc control and extinction
achieved by puffer principle
Capable of interrupting small
magnetizing and capacitive
currents
ABB
© ABB Ltd - 10
HPA BREAKER
Features of operating
mechanism
O-C-O operation without
recharging
Closing spring charged by
motor in less than 15secs
Electrical anti-pumoing
Provision for manual
recharging
Synchronisation and fast auto
reclosure duty
ABB
HPA BREAKER
The HPA series of CB are designed and type tested to meet the
requirements of IEC-60056 / IS:1318
The HPA series of CB use SF6 gas as insulating and arc
interruption medium
Arc interruption and control are achieved by puffer principle
Short arc duration followed by rapid dielectric recovery
Long electrical life, as the interruption system develops low arc
energy and contact wear is minimal
Long mechanical life with study and proven operating
© ABB Ltd - 11
mechanism
- 10000 operations at no load
- 10000 operations at rated current
ABB
© ABB Ltd - 12
HPA BREAKER
Operationally safe and reliable in wide range of operating
temperature
-5o to +40o c
Capable of interrupting small magnetizing and capacitive currents
Compact design with relatively light weight construction
Features of operating mechanism
O-C-O operation without recharging
closing spring charged by motor in less than 15 secs.
electrical anti-pumping
provision for manual recharging
synchronization and fast auto-reclosure duty
ABB
© ABB Ltd - 13
VHA PANEL CROSS SECTIONAL DWG
ABB
VHA 12 PANEL
© ABB Ltd - 14
TECHNICAL DETAILS
Description
Unit
Rating
Voltage
kV
12
Frequency
Hz
50
Current
A
630, 1250, 1600, 2000,
2500, 3000, 4000
Short time withstand
current (for 3 secs)
kA
40
Peak withstand current
kAp
100
Insulation level
kVrms/kVp
28/75
WidthxDepthxHeight
mm
800x1370x2340
Weight with breaker (approx.) kg
1000
Degree of Protection-Enclosure
IP4X
ABB
HPA12 CIRCUIT BREAKER
TECHNICAL DETAILS
Description
Unit
Rating
Voltage
kV
12
Frequency
Hz
50
Current
A
1250, 1600, 2000, 2500, 3150
Breaking capacity
kA
40
Short time withstand
current (for 3 secs)
kA
40
Peak withstand current
kAp
100
Insulation level
kVrms/kVp
28/75
Operating sequence
© ABB Ltd - 15
Weight (approx.)
O-3min-CO-3min-CO/
O-0.3secs-CO-3min-CO
kg
190-225
ABB
INSTALLATIONS
OVER 25,000 PANELS INSTALLED
MAJOR INSTALLATIONS AT:
POWER PLANTS
DISTRIBUTION UTILITIES
STEEL PLANTS
CEMENT PLANTS
REFINERIES
VARIOUS INDUSTRIES & INFRASTRUCTURE PROJECTS
© ABB Ltd - 16
ABB
SUCCESFULL INSTALLATIONS IN GENEARATIONS
Major installations of VHA 12S +HPA
POWER PLANT LOCATION
SF6 SWGR INSTALLED
MSEB ( CHANDRAPUR UNIT IV V &VII ,KORADI) (1989,95,99)- 593
NTPC ( VINDHYACHAL 500MW)(1995)
- 248
NTPC ( TALCHER 4 X 500MW) (1999)
- 451
APSEB ( RAYALSEEMA 2 X 210 MW) (1998)
- 235
BSES DAHANU ( 2 X 250MW) (1994)
- 163
MPEB SGTPS (1997)
- 179
GIPCL (2 X 125 MW) (1996)
- 110
© ABB Ltd - 17
Total SF6 panels installed in Generations in India - 4100Nos