Transcript Document

2.0 ANALYSIS AND DESIGN
2.2 STRUCTURAL ELEMENT
Reinforced Concrete
Column
Rearrangement by :NOR AZAH BINTI AIZIZ
KOLEJ MATRIKULASI TEKNIKAL KEDAH
INTRODUCTION



Column is defined as a
structural members
subjected to compressive
force.
Strut – a small compressive
member in a framed
structure.
Column – a larger member,
such as the main support
for a beam in a building.
INTRODUCTION

Axially loaded compressive
member can fail in two
principal ways:
- short fat member fail by
crushing or splitting of the
material.
- long thin members fail
by sideways buckling.
Types of column
i) Braced column(tiang dirembat)
– the lateral loads are resisted by wall
or some other form of bracing
ii) Unbraced column(tiang tidak dirembat)
– the lateral loads are resisted by the
bending of the column
iii) Short Column (tiang pendek)
lex/h and ley/b < 15 for a braced column
● l /h and l /b < 10 for an unbraced column
ex
ey
iv) Slender(Long) Column ( tiang langsing)
●
●
●
lex/h @ ley/b >15 for a braced column
lex/h @ ley/b >10 for an unbraced column
Failure Mode



Short column (p> pcr)usually fail by crushing
when the material achieved its ultimate strength.
Slender column is liable to fail by buckling
The end moment on slender column cause
it to deflect sideways exceed a critical
values until the column buckles.
Failure Mode

Slender Column
- fails by sideways buckling
- The load at which a slender column buckles, is
known as its critical buckling load, P crit.
P crit. = ΩEI / L2
Where; E = Modulus of Elasticity
I = second moment of area
L = length between pins
Column detail
Reinforcement detail
Longitudinal steel bar
-
-
A minimum of 4 bars is required in a rectangular column and
6 bars in a circular column.
The size of the bars should be not less
than 10mm
Links
- Minimum size = ¼ x size of the largest compression bar
but not less than 6mm
- Maximum spacing = 12 x size of the smallest
compression bar
Types of Reinforced
Concrete Column
Rectangular
column
Circular
column
Load transfer on column for design
Factored Axial Load (N) for Column Design
Interior Column – 1.25
●Edge/face column – 1.5
●Corner column – 2
●
Corner
column
Edge /face
column
Interior
column
Short Axially Loaded
Column Design
Equation
N = 0.4 fcu Aconc+0.8 fy Asc
Where
N – Ultimate Axial load
fcu – Characteristic of concrete strength
Aconc – area of concrete cross section
fy – Characteristic of reinforcement strength
Asc – area of reinforcement cross section
N
Example:
A column with 200 mm x 200 mm resists a
factored axial load 500kN.
Calculate the area of steel required if
fy = 460 N/mm2 and fcu = 30 N/mm2
Table 1
Bar dia.(mm)
C/s area (mm2)
Diameters and areas of reinforcing bars
6 8 10 12 16 20 25 32
40
28 50 79 113 201 314 491 804 1256
Formula for design column
N = 0.4 fcu Aconc + 0.8 fy Asc
500x103 = 0.4 (30) (40000 - Asc) + 0.8 (460) Asc
= 480000 – 12 Asc + 368 Asc
= 480000 + 356 Asc
Asc = 56.18mm2
Asc (for each bar) = 56.18mm2/4 = 14mm2
Asc = Πj2= ΠD2/4=14mm2
D = 14 x 4 / Π
= 4.22mm
Standard required 4 number of steel reinforcement bars
size 10mm minimum) . So size column = 4 T 10
4T10