Seismic Considerations - Transformer components

Download Report

Transcript Seismic Considerations - Transformer components

ABB Components USA
Seismic Considerations &
Power Bushings
Using IEEE Standards
ABB Components USA
IEEE 693 - 1997
IEEE Recommended Practice for
Seismic Design of Substations
ABB Components USA
IEEE Std 693 - 1997
Electrical Equipment for Sub Stations
 Based on IEEE 693-1984




Three Qualification Levels


Very major revision
Basically a new standard
Low, Moderate & High
User determines Qualification Levels
ABB Components USA
djr 2/00
European Standards
IEC Technical Report 1463
ABB Components USA
IEC Technical Report 1463
Covers seismic qualification of power
bushings
 Based on static coefficient calculations
 Based on cantilever withstand of bushing
 Not widely accepted in North America

ABB Components USA
djr 2/00
IEEE 693-1997
Performance Levels
 Selection of performance Level
 Requirements for bushings
 Test Methods
 Qualification of bushings < 161 kV
 Qualification of bushings  161 kV

ABB Components USA
djr 2/00
Performance Levels (ground acceleration)

Low = 0.1 g, horizontal acceleration peak

Moderate = 0.5 g, horizontal acceleration peak

High = 1.0 g, horizontal acceleration peak

Vertical acceleration = 0.8 x horizontal
ABB Components USA
djr 2/00
Selection of Performance Level
By User of equipment
 Expected ground acceleration by earthquake
hazard method or …
 … by seismic exposure maps and site
conditions
 Select Performance Level to match the
expected ground acceleration

ABB Components USA
djr 2/00
General Requirements for Bushings

Bushings as components of larger equipment

Annex D of IEEE 693 - Transformers

Requirements depend on system voltage
ABB Components USA
djr 2/00
Testing for Seismic Performance Levels

Low: 0.1g, horizontal


Moderate: 0.5 g, horizontal


Equipment testing not required
Testing required (when practical with equipment size)
High: 1.0 g, horizontal

Testing required (when practical with equipment size)
ABB Components USA
djr 2/00
Qualification of Bushings





Less than 161 kV
Static Pull Test
Force = 2 x weight
Applied horizontally
at top of bushing
Duration = 2 seconds




161 kV and Higher
Shake Table test
Time history method
Test by design family
Test most seismically
vulnerable family
member
Pass = no damage & no leaking
ABB Components USA
djr 2/00
Bushing Seismic Considerations
Bushing is not at ground level
 Bushing acceleration is amplified by
transformer structure
 Bushing acceleration = 2x ground acceleration
 Transformer tank:



Amplification factor = 2, or
Super Elevation factor (IEC) = 1.5
ABB Components USA
djr 2/00
2.0 g
Transformer Tank
Amplification Factor = 2
1.0 g
ABB Components USA
djr 2/00
Shake Table Testing of Bushings

Method 1



Test at 1/2 level and
Calculate to demonstrate a 2x safety factor
Method 2

Test at full level
ABB Components USA
djr 2/00
Shake Table Testing of Bushings
1/2 Test + Calculation Method



Only practical method for some large equipment
Good when structure behaves in linear fashion and
is predictable
Not good for bushings because of the non-linearity
of the bushing’s mechanical system, ie, gasket +
porcelain + spring clamps
ABB Components USA
djr 2/00
Shake Table Testing of Bushings
Using 1/2 Level Test Method
For large equipment where not practical to
test at full level.
 Must demonstrate by calculation that
equipment can withstand forces 2 times as
great as test values

ABB Components USA
djr 2/00
Example of 1/2 Test Method
(Power Transformer)

Purpose of test: demonstrate that transformer is
qualified for the High Performance Level where
ground acceleration = 1.0 g

Shake Table set-up at 1/2 value = 0.5 g

Use calculations to show that the test results at
0.5 g can be extended to 1.0 g
ABB Components USA
djr 2/00
Example of 1/2 Test Method
(Transformer Bushings)

Purpose of test:






demonstrate qualification at High Performance Level
ground acceleration = 1.0 g
Bushing acceleration is 2 times ground
acceleration because of tank effect
Bushing must withstand 2 x 1.0 g = 2.0 g
Shake Table set-up at 1/2 value = 1.0 g
Use calculations to show that the test results at
1.0 g can be extended to 2.0 g
ABB Components USA
djr 2/00
Shake Table Testing of Bushings
Using Full Test Method (Full Performance Level Test)

Purpose of test:







demonstrate qualification at High Performance Level
ground acceleration = 1.0 g
Bushing acceleration is 2 times ground acceleration
because of tank effect
Bushing must withstand 2 x 1.0 g = 2.0 g
Shake Table set-up at full value = 2.0 g
Bushing directly qualified by Test
Calculations not required
ABB Components USA
djr 2/00
Shake Table Testing of Bushings
Using Full Test Method (Full Performance Level Test)

Moderate Level (0.5 g)


Bushing tested at 1.0 g
High Level (1.0 g)

Bushing tested at 2.0 g
ABB Components USA
djr 2/00
Bushing Qualification @
High Level by Direct Testing
2g
ABB Components USA
djr 2/00
Bushing Qualification @
Moderate Level by Direct Testing
1g
ABB Components USA
djr 2/00
Shake Table
Test Set-up
ABB Components USA
djr 2/00
ABB Components USA
Qualify bushings based on IEEE 693-1997
 Actual shake table test used for higher
voltage bushings
 ABB full line of ANSI/IEEE bushings has
been tested and qualified according to IEEE
693-1997

ABB Components USA
djr 2/00
ABB Bushing Qualification Summary

Qualified @ High - Static Pull Test


Bushings 25 kV through 138 kV
Qualified @ High - Shake Table

Bushings 161 kV through 196 kV


full test of seismically worse bushing in family
Qualified @ Moderate - Shake Table

Bushings 362 kV

full test of seismically worse bushing in family
ABB Components USA
djr 2/00
ABB Bushing Qualification Summary

500 kV bushing



not qualified at moderate
passed 0.45 g at flange
equivalent to 0.22 g, ground acceleration


(with tank amplification factor = 2)
failure mode (@ 0.50 g at flange)
slight leak at flange during shake test
 re-sealed after test
 no worse after second test

ABB Components USA
djr 2/00