Sofrel LS-LT Range Presentation

Download Report

Transcript Sofrel LS-LT Range Presentation

LS/LT GSM/GPRS Data Logger range

V3.10

Constraints and demands of District Metering

Little water networks installations Man-hole/chambers of water networks Strom overflow sewers Installations without mains power… Demanding environment Flooded or humid plants Sites with no mains power Isolated or hard to reach plants Dedicated Applications Leak detection through sectorisation Detection of Storm water overflow.

Key Customer Meter Remote reading.

Remote control of secondary plants.

# 2

LS/LT GSM/GPRS Data Logger range

V3.10

Hardware for a tough environment

Sofrel Solution : LS-LT Data Loggers range

« Field » tools High performance GSM Antenna GSM Reception level indicator Reenforced watertightness Easy access, by end-user, to SIM and battery Battery Life-time : up to 10 days Commissioning through Bluetooth Alarm SMS Daily historical values collections Data viewing through WEB server On-site data-handling and GSM/GPRS Communications Inputs : Pulse, AI, DI Calculations : flow, thresholds, daily reports. Time-stamping in Data Logger # 3

Physical data

1 to 4 pulse or signalisation inputs

  Pulse : Pulse meter, standard or « two ways» Signalisation : Normaly open or normaly closed.

Appearance and disapearance settable timer.

2 measurements 4-20 mA inputs (option)

 SOFREL sensor very low consumption (8V)  Standard Sensor, powered by LS/LT (12V)

LS/LT GSM/GPRS Data Logger range

V3.10

Available data

m3 / h

Calculated data

 

Meter average flow-rate.

Threshold on average flow-rates

 Two time-windows per day  Threshold Value and logic settable for each time-window Low threshold

Daily reports

Metering

   Index, Volume, min & max Flow-rate Night flow in a settable time-window.

Signalisation (DI, threshold)

  Number of activations.

Duration of active status.

Historical values

Periodic (1, 3, 5, 10, 15, 30 and 60 minutes)

     Index and average flow-rate.

Measurments

Signalisation status changes.

Daily reports Memory extended to 50 000 records

LS/LT GSM/GPRS Data Logger range

V3.10

Data Handling

24 h M ³/H m ³/ h

LS/LT GSM/GPRS Data Logger range

V3.10

On-site data handling

With Softools through Bluetooth connection

« Information » screen

Real-time values of all information

  Meters , flow, measurments, signalisations, thresholds reports, battery,… 

Selection of 10 information for

  Curves Excel Transfert 

Curves

  

Time-frame : Day / Week / Month Y scale adjutment X Zoom

Excel Transfer

LS/LT GSM/GPRS Data Logger range

V3.10

Communication with SCADA

GPRS or SMS (LS) communication

  

1 or 2 Central Stations Automatic clock up-date Transfered data :

 Historical values – daily reports  Diagnostic : power, reception level...

Multiple choices of data transmission

    Scheduled transmission : 1 to 6 daily calls.

Periodic transmission (every 15 minutes to 8 hours (GPRS mode)) Transmition when alarm appears (threshold, DI) Network Diagnostic after on-site visit.

 Periodic transmission for a limited period of time (Max 1 day) 

GPRS Communication

 

SCADA or WEB server with static IP @ « Low –cost » communication

 Optimized volume of data - No roaming

# 7

Alerts to SCADA Central Station

Can be activated on all the Dis and Thresholds

 

On appearance and disappearance Send available data

  Current data status Historical values

LS/LT GSM/GPRS Data Logger range

V3.10

Alerts

Cuurent data status Archiving

Alert to mobile

 

Can be activated on DIs or Thresholds On appearance

A « signaling » SMS is sent immediately.

 Configurable text message

Paris Sector 12 Open manhole cover # 8

High-performance built-in antenna

 

Specifically designed to be used in man-holes Optional watertight External Antenna.

IP68 watertightness

Case with double O-ring seal

 Uniform distribution of sealing pressure

Military type « inputs » connector

LS/LT GSM/GPRS Data Logger range

V3.10

Hardware features

Battery life

 

Ultra low-power technology Standard/high capacity battery :

 Standard battery : Up to 5 years  High-capacity battery : Up to 10 years 

Power consumption Measurement

Transmitted to the SCADA Central Station

# 9

Wall mounting Easy to mount and remove

User access To insert SIM card and change battery

Bluetooth port Local wireless link

4 control LEDs Immediat visual inspection

Local wake-up with key Activation of LED, Bluetooth, SMS

LS/LT GSM/GPRS Data Logger range

V3.10

Hardware features

V B J # 10

Application wizard

For LS application 

Only one configuration screen Direct access to all functions Full view of settings

Remote transfer of configuration Read/Write via Bluetooth

LS/LT ID Card Geographical coordinates Serial number – Versions – Options..

LS/LT GSM/GPRS Data Logger range

V3.10

Configuration through Softools

# 11

4 complementary diagnostic tools

Control LED

 

Softools commands via Bluetooth link SMS commands from a mobile

LS/LT GSM/GPRS Data Logger range

V3.10

Diagnostic tools

# 12

Direct and Integrated diagnostics

 

Data Logger, SIM card, GSM Network status GSM signal strength

LS/LT GSM/GPRS Data Logger range

V3.10

LED Diagnostic

 

Assistance to installation Assistance to maintenance

GSM network logon & SIM card OK

V

Data Logger activated

B

Wake-up GSM signal strength

J # 13

Communication tests

  

Best-operator selection Signal strength Triggering

   Send SMS to mobile Transmitted to the SCADA Central Station

Deferred transmission

 Test in real conditions man-hole cover closed

LS/LT GSM/GPRS Data Logger range

V3.10

SMS & Bluetooth Diagnostic

Input wiring test

Meter indexing

Energy reading

Remaining battery life # 14

LS/LT GSM/GPRS Data Logger range

V3.10

SOFREL LS/LT range

A comprehensive range

Applications

SOFREL LS for Water Netwok District Metering

SOFREL LT for Storm Overflow Sewers

Equipment

SOFREL LS/LT42

  Core part of the range 2 optional AI 

SOFREL LS/LT42-EA

  Version dedicated to tough GSM signal conditions External antenna 

SOFREL LS10

  Simplified version 1 Pulse

# 15

LS/LT GSM/GPRS Data Logger range

V3.10

Sofrel LS

« Leak detection through District Metering » application

« Volume and flow » function

Volume counting

 Mecanical meter –Electromagnetic flow-meter.

Reports

    Average flow-rate.

Night-flow in a settable time-window.

Archiving

  Periodically : index and flow Daily : index, volume, min/max flow, night-flow.

Daily transmission to Central Station

Additional Information

   Handling of two-way meters.

Pressure measurement Signalisation : man-hole cover opening, flow meter default…  Alerts on flow and measurement thresholds

# 16

LS/LT GSM/GPRS Data Logger range

V3.10

Sofrel LT

« Storm overflow sewer » application

« Overflow » function

Connection to an « overflow sensor »

Level measurement

 Ultrasonic 4-20 mA sensor.

 

Calculations

 Number and duration of overflows

Archiving

    Overflow time-stamping Number and duration of daily overflows Variable frequency depending on overflow status (Ultrasnic sensor)

Daily transmission to Central Station

Additional information

 Signalisation : sensor default  Alerts on level threshold

# 17

LS/LT GSM/GPRS Data Logger range

V3.10

Sum-up

LS/LT Range: THE industrial solution for water networks little plants

   

Fully IP68 waterproof High-performance GSM Antenna Up to 10-year battery life-time Field installation « tools »

# 18