Transcript IR5500 Open Path Detector
ULTIMA
®
OPIR-5 Open Path Gas Detector
E VERY L IFE H AS A P URPOSE…
Contents
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Product Overview False Alarm Immunity Product Comparison Detector Placement Installation Split Concentration Range Maintenance Fault Conditions HART AMS Device Manager Applications Sales Strategies Conclusion
ULTIMA OPIR-5 Detector
Description
– Open path infrared hydrocarbon gas monitoring system
Expected Customer Benefits
– – – – – Low power consumption Dual analog outputs, ppm Light and compact design Resilient to solar radiation and fog Long detection range • M and LEL • M – – – Available with HART and Modbus Stainless steel construction Integral display
Specifications Response time (T90, s) Repeatability Linearity Path length, max (m) Operating temperature range (
C) Solar blind Fog immunity Combined weight, receiver and source (kg) Supply power, nominal (W) Bidirectional communication Event logging and AMS Device Manager
Performance Specifications
Ultima OPIR-5 < 5 <
5%
5% FS or
10% 150 -55 to +65 All conditions 90% blockage,
10% acc.
11.13 (SS only) 23 HART, Modbus Available
Solar Radiation Rejection
The ULTIMA OPIR-5 has superior immunity to solar radiation and other external IR radiation sources.
Fog Resistance
Path Length (m) Detector Model 50 78 100
ULTIMA OPIR-5 No beam block No beam block Beam block
Performance Certifications
The ULTIMA OPIR 5 Detector is the world’s first and only open path detector to meet agency performance requirements on ppm m scales
both
LEL • m and
Comparison with Competition
The ULTIMA OPIR-5 excels or compares well with other products in the market across several categories: – – – – – Sensors specifications Environmental specifications Regulatory approvals Bidirectional communications Energy efficiency
Sensor, Electrical, and Mechanical Specifications Specifications Accuracy Repeatability Linearity Response time (T90, s) Drift Conc. range (LEL
m) Path length, max. (m) Power consumption (W) Combined weight (kg) Housing material Ultima OPIR-5 <
5% FS <
5%
5% FS or
10% < 5
10% FS or
20% 0 – 5 150 23 11.13 (SS only) 316 SS Det-Tronics OPECL
25% LEL-m or 10% ND ND < 5 ND 0 – 5 120 Dräger Polytron Pulsar Honeywell Searchline Excel ND ND ND < 2 ND 0 – 8 200 ND ND ND < 3 ND 0 – 5 200 11 32* 316 SS 23 (max) 12 SS 16 (max) 7, 10.5** 316 SS Spectrex SafEye Xenon 700 ND ND ND 3
5% FS 0 – 5 140 6 8.8
316L SS
† Also available in 0 – 5,000 ppm-m methane and 0 – 2,000 ppm • m and 0 – 2 LEL • m propane.
‡ ** Aluminum, stainless steel.
* Includes mounting hardware.
Short range unit, medium and long range unit.
Environmental
Specifications
The ULTIMA OPIR-5 has the widest operational temperature range among competing products
-80 -60 Sp ect r ex Saf Eye 70 0 Ho neywel l Sear chl i ne Excel D r äg er Po l yt r o n Pul sar -40 D et - T r o ni cs OPEC L U LT I M A OPI R - 5 -20 0 Tem perature (C) 20 40 60 80
Environmental Specifications (Cont.)
The ULTIMA OPIR 5’s relative humidity and pressure ranges are on par with those of competing products
Honeywell Searchline Excel Dräger Polytron Pulsar Det-Tronics OPECL ULTIMA OPIR-5 0% 20% 40% 60% Relative Humidity 80% 100% Honeywell Searchline Excel Dräger Polytron Pulsar Det-Tronics OPECL ULTIMA OPIR-5 70 80 90 100 Operating Pressure (kPa) 110 120
Regulatory Approvals
Regulatory Approvals ATEX CE Marking CSA FM Approvals GOST HART IECEx IEC 61508 (SIL) OPIR-5
(SIL 3) Det-Tronics OPECL
SAA UL Dräger Polytron Pulsar
Honeywell Searchline Excel
Spectrex SafEye Xenon 700
(SIL 2)
Digital Communication
Regulatory Approvals OPIR-5 Det-Tronics OPECL Dräger Polytron Pulsar
HART LON Modbus
Honeywell Searchline Excel Spectrex SafEye Xenon 700
Detector Placement
Open path detectors should be installed based on several considerations: – – Hazard conditions within the installation area covered Ventilation rates, direction, and presence of recirculation and dead zones – – Sensitivity to low (geometric) sunlight, fog, and reflections Powerful sources of electromagnetic emissions like high powered electrical towers – Structures that may interfere with line of sight * Health and Safety Executive, Offshore Division,” Fire and Explosion Strategy, Issue 1,” 2004.
Installation
When installing an ULTIMA OPIR-5 detector, it is useful to consider the following: – – – – Vibration can create issues Solid foundation improves alignment integrity The longer the line of sight path, the more solid the foundation required Maintain a 6” to 12” radius around the line of site beam to avoid reflective interference from piping and supports – – For outdoor installations, consider maximum snow levels Good immunity to fog, steam, and rain but immunity degrades over longer distances – – Avoid pedestrian traffic or overhead cranes Keep beam low and down wind for heavy gases like propane and high for light gases like methane
Ultima OPIR-5 Receiver
Wiring
9 10 11 12 13 14 15 16 3 2 5 4 8
MOD1 Modbus 1 Modbus1+
7 6
MOD1 + A2
1
AC A1 W2 L WC L W1 L Alarm NO/NC Alarm C Alarm NC/NO Warn NO/NC Warn C Warn NC/NO Modbus 2 Modbus 2+ Fault NO MOD2 MOD2 + FLT1 Fault C Fault NC FLTC FLT2
17 18 19 20 21
Warn NC/NO Warn C Warn NC/NO W2 P WC P W1 P
22 23 24
Split Concentration Range
With the split range function, users can monitor the entire span of gas concentration with a single analog signal – Reduces wiring and commissioning costs
5,000 ppm-m (0.1 LEL•m) 5 LEL•m 0 4 12 AO (mA) 20
Alignment
Simple alignment process – Arm or base mounts available Display – – Menus activated by magnet Enables easy alignment, setup & diagnostics
Maintenance
As with other combustible sensors, the ULTIMA OPIR-5 should be included in the plant maintenance schedule* – Gas check frequency depends on operating conditions (ex. dusty, corrosive, or damp environment) – Before repair or maintenance, the gas detector should be removed to a safe place outside the area being protected If the hazard is still potentially present, it will be necessary to use a replacement gas detector in the area until the original detector is reinstated * BS EN 50073:1999 “Guide for the selection, installation, use and maintenance of apparatus for the detection and measurement of combustible gases or oxygen.”
Diagnostics
The ULTIMA OPIR-5 has self-diagnostics that inform users when certain types of device failures have occurred Fault Code
F0
Description
Excessive negative drift or high IR F1 F2 F3 F5 F6 F7 F8 F9 F10 F11 tF7 Partial beam block or dirty lens Alignment Beam block Setup menu not exited Low supply voltage Heater error Failed zeroing Gas left (timeout) Reset short Unit overheating Source internal error
HART
The ULTIMA OPIR-5 is available with HART for better efficiency with remote communication
– Only the primary scale, LEL
•
m or split range, connects through HART
Benefits of the HART-equipped ULTIMA OPIR-5:
– – Better diagnostics of problems Improved management of maintenance history and event logging – – Flexible and accurate digital transmission Effective cost control of devices in the field – Installation savings due to fewer wires
HART – Analog Signal for Faults
Because HART requires a minimum current for operation, the ULTIMA OPIR 5’s fault conditions use 3.5 mA as minimum analog output
Function Fault Test Gas Setup Mode Beam Block Startup Zero Reading Gas Concentration Over-range Analog Output (Standard) 0 1.5
1.5
2.0
0 4.04
4 – 20 21.7
Current Level (mA) Modbus HART (Default) 0 3.5
1.5
1.5
3.5
3.5
2.0
0 4.04
4 – 20 21.7
3.5
3.5
4.04
4 – 20 21.7
HART-modified Analog Output 1.25
1.5
1.5
2.0
1.25
4.04
4 – 20 21.7
On HART-equipped unit, user must select the HART-modified AO in order use AO values below 3.5 mA
AMS Device Manager
Asset management and process improvement – Check compliance to calibration schedule – Coordinate calibrations so as to reduce labor cost – Aggregate calibration to a control room – – Track gas level remotely Read fault conditions from control room; before sending technician to the field
Applications
Area monitoring where there is a clear line of sight – – – – Perimeters Processing modules Process segregation Tunnels
Offshore Oil and Gas
Drilling and production operations Separation Compression HVAC inlets
Pipeline and Storage Operations
Compressor stations Valve manifolds Tank farms
Bus Garages Train Stations Tunnels
HVAC and Wastewater
Sales Strategies
The ULTIMA OPIR-5 is a product with all time firsts: – First and only open path detector to meet agency performance requirements on
both
LEL and ppm scales – First among major open path models to be certified to FM Approvals, EN, and IECEx performance standards – First to offer split range scale for ppm-m and LEL-m monitoring – First to be certified for operation at -55 C
Sales Strategies (Continued)
No tools required for alignment at any range – It is possible to align the open path detector without a scope at 100 m or more Integral display – Reduces installation time and total cost to own
Conclusion
The Ultima OPIR-5 compares well with other open path detectors in the market • • • Repeatability Linearity Operating temperature range
Conclusion (Continued)
The instrument’s dual concentration range and integral display are differentiators – No other detector offers a performance-certified dual range – Most commercial models require a handheld or controller to read gas concentrations or perform maintenance The Ultima OPIR-5 open path detector is well positioned to meet users’ demands for enhanced safety and longevity