Pipes
Single Wall Pipes
Double Wall Pipes
KPS Learning
KPS Learning
Single Wall Pipe
• KPS pipes have a liner that
prevents petrol from
permeating through the pipe
wall
• The liner is chemically
bonded to the inside of the
pipe, no risk of delamination
• Conductive layer dissipates
static electricity
• Diameters 25, 32, 54, 63, 90
and 110 mm
Conductive layer
Polyethylene
Permeation barrier
KPS Learning
Double Wall Pipe
• With the double wall pipe an
interstitial space is created
between the pipes that can be
monitored for leaks.
• Diameters 40/32, 75/63 and
125/110 mm
KPS Learning
Bends and Tees
Single Wall
Double Wall
KPS Learning
Sockets and Fittings – Plastic
•
•
KP CC conductive connector
For conductive pipes, diameters 54-110 mm
•
•
KP 2
For pipe diameters 25, 32, 54, 63, 90 and 110 mm
•
•
KP 2 SC integrated
For pipe diameters 75/63 and 125/110 mm
•
•
KP 2 SC ”anaconda”
For pipe diameters 75/63 and 125/110 mm
KPS Learning
Termination fittings
• KP T
•
For pipe diameters 75/63 and 125/110 mm
•
•
KP T black
KP T75/63B and KP T125/110B
• KP TM
•
For pipe diameters 75/63 and 125/110 mm
KPS Learning
Entry seals
• For tight entry of tubes,
pipes and electrical wiring
into sumps
KP TM125/90
75/54
32/15
KP TM75/63SC
KP TM125/110SC
KP TM125/90W
75/54W
32/15W
KPS Learning
Transition fittings plastic-to-steel
• KP C13 male and female, pipe
diameters 90 to 110 mm
• Conductive
• KP C13 male and female for product
lines, pipe diameters 54 to 63 mm
• Conductive
• KP 5 stub flange, KP 6 DIN flange, KP 7
gasket, pipe diameters 54 to 110 mm
• Conductive
KPS Learning
KPS Learning
Transition fittings plastic-to-steel
• KP C15 male and female, pipe
diameters 54-110 mm
• Conductive
• KP C14, for pipe diameters 32-110
mm
• Conductive
KPS Learning
KPS Learning
Steel fittings and valves
KPS Learning
Tank chambers and covers
• Glass fibre tank chambers
• Covers and skirts
KP MC984D
40 ton
KP TC1400R
Conductive
throughout
KP TC1520RF
KP TC1520SQ
Conductive inside
KP MC928
KP MC977CFC
25 ton
KP MC9946
KPS Learning
KPS Learning
Dispenser chambers
• Glass fiber and polyethylene dispenser chambers
KP DC1000C
Conductive glass fiber
throughout
KP DC1000
Polyethylene
KP DC1000F
KPS Learning
Electrical conduits
• With permeation barrier
• Diameters 32 and 75 mm
KPS Learning
Leak Detection – KP 315
•
•
•
•
•
A liquid sensor that is placed
in the tank sump
Works without pressure or
vacuum
Connected to the test ports
of the pipe work
Any liquid in the interstitial
space will flow into the
sensor unit and trigger the
alarm
Alarm is visual, audible or
connected to additional
remote alarm output/display
KPS Learning
Further features:
->
->
->
->
->
->
->
->
->
->
->
->
25 bar operation pressure
40 bar test pressure
over 100 bar burst pressure
no welding
no isolation neccessary (pipe PE, fitting SS)
no inside corrossion
0 permeation
conductive
short installation time
easier to install than any pipe
cheaper than any other pipe system
CE marked and approved
KPS Learning
LPG
KPS Learning
Installation Equipment
KPS Learning
Test Equipment
• Pressure test gauge with
tubes
• Tank sump pressure test
kit
• Conductivity tester
KPS Learning
30 years warranty
- on plastic pipes and plastic fittings
Conditions:
• Handling, storage and installation must be done
according to the installation manual
• Installation must be done by certified installers
• Installation Checklist
• Do not mix KPS with products of other manufacturer
KPS Learning