Pump Operational Flexibility & Optimization

Download Report

Transcript Pump Operational Flexibility & Optimization

Pump Operational Flexibility &
Optimization
Pat Carney
Flow-Technics Inc.
Flow-Technics Inc
1
Topics of Discussion
 Evaluations/Considerations
 Flexibility & Optimization Options
 Examples
 Conclusions
Flow-Technics Inc
2
Evaluations/Considerations
 Characteristics of System Head Curve
 Operational Considerations
 Pump Characteristics
Flow-Technics Inc
3
System Head Characteristics
 Components
 Static Head
 Frictional Head
 Velocity Head
 Characteristics


Flat
Steep
Flow-Technics Inc
4
System Head Curve
Flat Curve
Steep Curve
Flow-Technics Inc
5
Operational Considerations
 Electrical Cost/Efficiency
 Flow Rate Flexibility
 Controllability
 All of the above
Flow-Technics Inc
6
Pump Characteristics
 Shape of the Curve
 Efficiency
 NPSHr
Flow-Technics Inc
7
Pump Curve – Flat Curve
Flow-Technics Inc
8
Pump Curve - Steep
Flow-Technics Inc
9
Operational & Optimization Options
 Single Pump vs. Multi-Pump Consideration
 Constant Speed vs. Multi-Speed
 Combination of Both
 Single vs. Multi Pump
 Constant vs. Variable Speed
Flow-Technics Inc
10
Single Pump vs. Multi-Pump
Single Pump
Multi - Pump
Flow-Technics Inc
11
Single vs. Multi Pump Evaluation
 Single Pump
 Flow: 3500 GPM
 Head: 65’
 Eff: 68.8.%
 Rated Hp: 85.5
 NPSHr: 17.1’
 Connected Hp: 115
Flow-Technics Inc
Two Pumps
Flow: 3500 GPM total
Head: 65’
Eff: 81%
Rated Hp: 68.8(total)
NPSHr: 9.6’
Connected Hp: 94(total)
12
Constant vs. Variable Speed
Constant Speed
Flow-Technics Inc
Variable Speed
13
Constant vs. Variable Evaluation
 Constant Speed
 Flow: 2100 GPM
 Head: 45
 Eff: 80.8%
 Rated Hp: 29.3
Variable Speed
Flow: 2100 GPM
Head: 45
Eff: 64.2%
Rated Hp: 36.8
Max Daily: 17 hp for variable operation
Ave Day: 15 hp
Low Flow: 10 hp
Flow-Technics Inc
14
Constant vs. Variable (Example #1)
Constant vs. Variable (Example #2)
 Flat System Curve
 Steep Pump Curve
 Limited Operating Range
 VFD vs. Cost Evaluation
Optimization Review - Unacceptable
Spec Requirement
2250 GPM @ 65’ TDH
(2 Pumps Running)
Submittal Review
Single Pump Operation
Static Head 28’
Unacceptable
Flow-Technics Inc
17
Optimization Review - Acceptable
Spec Requirement:
2250 GPM @ 65’ TDH
(2 Pumps Running)
Static Head: 58’
Submittal Review:
Single Pump Operation
Static Head: 28’
Acceptable
Flow-Technics Inc
18
Theoretical vs. Actual
Flow-Technics Inc
19
Field Modifications
With use of VFD, reduce speed to match actual system
requirements.
Evaluate 2 Pumps at reduced speed vs. 1 pump running
Resize and replace Impeller
Flow-Technics Inc
20
2 Pumps Reduced Speed
Flow-Technics Inc
21
Conclusions
 Understand System Characteristics
 Design Criteria
 Operational Criteria
 Communication!!
Flow-Technics Inc