Glass and fire protection
2008
Technical Advisory Service
Thermal
insulation
Acoustic
insulation
Solar
control
Safety
Aesthetic
and decoration
Glass and fire protection
 Introduction
 Standards and tests
 Different sort of fire resistant glazings
 AGC Flat Glass Europe range
 Applications
 Other properties
Intoduction
Glass and fire protection
 Introduction
 Standards and tests
 Different sort of fire resistant glazings
 AGC range
 Applications
 Other properties
Standards and tests
The fire resistance is measured in laboratory
according these standards :
 EN 1363 – Fire resistance test
 EN 1364 – Fire resistance test of the
non-loadbearing elements
Standards and tests
Curve of the temperature increase
T-to°C
1000
1
800
1. Furnace temperature
2. Wired glass temperature
2
3. Pyrobel 12 temperature
600
400
3
200
140
140
15 30 45 60 75 90
Time / min.
Standards and tests
Standards and tests
Classification of the fire resistant glazing :
EN 13501-2 (EN 357)
E: Integrity
W: Reduction of radiation
I: Thermal insulation
Standards and tests
E: Integrity
Fire side
Non-fire side
Criteria :
- a cotton swab should not
flame up after 30 seconds of
exposition
Standards and tests
EW: Integrity & Reduction of the radiation
Fire side
Non-fire side
The irradiated heat is
measured at 1 meter
distance
1 meter
Criteria :
- Radiation < 15 kW/m²
Standards and tests
EI: Integrity & thermal insulation
Fire side
Non-fire side
The temperature of the nonexposed surface to fire is
measured with
thermocouples.
Criteria :
- Dt°max < 180°C
- Dt°aver < 140°C
200 CM
50 CM
10 CM
E
EW
EI
Glass and fire protection
 Introduction
 Standards and tests
 Different sort of fire resistant glazings
 AGC range
 Applications
 Other properties
Different sort of fire resistant glazings
Wired polished glass
Classification:
E 30 to E 90
Example: Pyroshield (Pilkington)
Different sort of fire resistant glazings
Tempered borosilicate glass
Classification:
E 30 to E 90
Example: Pyran S (Schott)
Rem: it is a special quality of tempering
Different sort of fire resistant glazings
Tempered glass
Classification:
E 30 to E 60
Example: Pyroswiss (St Gobain)
Rem: it is a special quality of tempering
Different sort of fire resistant glazings
Coated tempered glass (SG or DG)
Classification:
EW 30 to EW 60
Example: Vetroflam (St Gobain)
Rem: it is a special quality of tempering
Different sort of fire resistant glazings
Multilaminated glass with aqueous gel
Classification:
EW 30-60
Tempered
glazings
EI 30-60-90-120
Aqueous
gel
Example: Contraflam (St Gobain)
Rem: it is a special quality of tempering
Different sort of fire resistant glazings
Multilaminated glass with intumescent interlayer
Classification:
EW 30-60
intumescent
EI 30-60-90-120
spacers
Example: Pyrobel (AGC)
Different sort of fire resistant glazings
Laminated glass with intumescent interlayer: principle
Different sort of fire resistant glazings
Laminated glass with intumescent interlayer: principle
Glass and fire protection
 Introduction
 Standards and tests
 Different sort of fire resistant glazings
 AGC range
 Applications
 Other properties
AGC range – Introduction
HST thermally
toughened glass
Laminated glass
with intumescent
spacer
E
Pyrostar
-
EW
Pyrostar
Pyrobelite
EI
-
Pyrobel
AGC range – Pyrostar
Pyrostar 100
Pyrostar SB 100
Pyrostar 211-44
E30
DH 30
E30/60 – EW30/60
Single glazing
Single glazing
IGU
In / Out
Inside
(smoke barrier)
Outside
AGC range – Pyrostar
Pyrostar 100 E 30
AGC range – Pyrostar
Pyrostar 100 SB 30
AGC range – Pyrostar
Pyrostar 211-440 - E 30/60 - EW 30/60
AGC range – Pyrobel - Pyrobelite
Fire resistance
Pyrobelite 7 / 7 EG
EW 30
Pyrobelite 12 / 12 EG
EI 20
Pyrobel 8 / 8 EG
EI 15 / EW 30
Pyrobel 16 / 16 EG
EI 30 / EW 60
Pyrobel 17 / 17 EG
EI 45
Pyrobel 21 / 21 EG
EI45 / EW 60
Pyrobel 25 / 25 EG
EI 60
Pyrobel 35 / 35 EG
EI 90
Pyrobel 53 / 53 EG
EI 120
Pyrobel 19
EI 30
Pyrobel 23
EI 45
Pyrobel 28
EI 60
AGC range – Pyrobel - Pyrobelite
EW30
Pyrobelite 7
3
Pyrobelite 7 EG
3
Float
Film PVB 0,76 mm
Intumescent interlayer
AGC range – Pyrobel - Pyrobelite
EI 20
EW 60
Pyrobelite 12
3
3
Pyrobelite 12 EG
3
Float
Film PVB 0,76 mm
Intumescent interlayer
AGC range – Pyrobel - Pyrobelite
EI 15
EW 30
Pyrobel 8
3
Pyrobel 8 EG
3
Float
Film PVB 0,76 mm
Intumescent interlayer
AGC range – Pyrobel - Pyrobelite
EI30
EW60
Pyrobel 16
3
8
Pyrobel 16 EG
3
Float
Film PVB 0,76 mm
Intumescent interlayer
AGC range – Pyrobel - Pyrobelite
Pyrobel 17
EI45
2
2
3
2
Pyrobel 17 EG
2
Float
Film PVB 0,76 mm
Intumescent interlayer
AGC range – Pyrobel - Pyrobelite
EI45/EW60
3
Pyrobel 21 EG
Pyrobel 21
3
3
3
3
Float
Film PVB 0,76 mm
Intumescent interlayer
AGC range – Pyrobel - Pyrobelite
Pyrobel 25 EG
Pyrobel 25
EI60
3
3
8
3
3
Float
Film PVB 0,76 mm
Intumescent interlayer
AGC range – Pyrobel - Pyrobelite
EI90
Pyrobel 35 (et Pyrobel 35 EG)
Pyrobel 17
Pyrobel 17
Float
Film PVB 0,76 mm
Intumescent interlayer
AGC range – Pyrobel - Pyrobelite
EI120
Pyrobel 53 (et Pyrobel 53 EG)
Pyrobel 17
3
3
3
3
Float
Film PVB 0,76 mm
Intumescent interlayer
Pyrobel 17
AGC range – Pyrobel - Pyrobelite
Pyrobel 19
EI 30
6
3
3
3
Float
Film PVB 0,76 mm
Intumescent interlayer
AGC range – Pyrobel - Pyrobelite
Pyrobel 23
EI 45
6
3
3
3
3
Float
Film PVB 0,76 mm
Intumescent interlayer
AGC range – Pyrobel - Pyrobelite
Pyrobel 28
EI 60
6
3
3
3
3
Float
Film PVB 0,76 mm
Intumescent interlayer
3
Glass and fire protection
 Introduction
 Standards and tests
 Different sort of fire resistant glazings
 AGC range
 Applications
 Other properties
Applications
Basic principles :
 Pyrobel/Pyrostar must always be used in an
approved frame
 The maximum dimensions of using are
mentionned in the test report for each
glazing / frame
Applications
Frame :
 For glazings of class E / EW:
wood – aluminium – steel
 For glazings of class class EI:
wood – insulated aluminium - insulated steel
Applications – Pyrobel 12
1
35
8
6
2
1
6
1
25
4
2
80
8
23
25
2
3
25
6
3
70
55
45
3
7
4
7
8
19
25
65
19
70
STEEL FRAME WITH
CALCIUM SILICATE BOARD
1
2
3
4
FORSTER FUEGO
Neutral silicone
5
Foam tape with closed cells 6
Setting blocks
7
Hardwood
8
HARDWOOD FRAME
Steel angle 20 x 10 x 2 mm
Steel tube 25 x 25 x 3 mm
Calcium silicate
Rockwool
Applications – Pyrobel 21
3
32
25
21
25
1
5
1
5
55
6
3
15
2
23
2
40
5
30
6
10
19
30
60
81
JANSEN AG JANISOL 3
HARDWOOD FRAME
19
STEEL FRAME WITH
CALCIUM SILICATE BOARD
1
2
3
Neutral silicone
4
Foam tape with closed cells 5
Setting blocks
6
Hardwood
Steel tube 30 x 30 x 3 mm
Calcium silicate
Applications – Pyrobel 52
Applications – Glass partitions
Applications – Smoke barrier – Pyrostar 100 SB 30
Applications
Limitations of using of Pyrobel :
 Maximum temperature : 40°C
 Protection against moisture (via tape)
 Protection against direct UV (via PVB)
Applications
Pyrobel: Outside use
 protection against UV
Float
Film PVB 0,76 mm
intumescent interlayer
Outside
Inside
Applications
Pyrobel: Outside use
 protection against UV
Float
Film PVB 0,76 mm
intumescent interlayer
Spacer
Outside
Inside
Glass and fire protection
 Introduction
 Standards and tests
 Different sort of fire resistant glazings
 AGC range
 Applications
 Other properties
Other performances
Impact resistance – EN 12600
Pyrobelite 7
3B3
Pyrobelite 7 EG (11)
1B1
Pyrobelite 12
2B2
Pyrobelite 12 EG
1B1
Pyrobel 8 EG
1B1
Pyrobel 8
-
Pyrobel 16
2B2
Pyrobel 16 EG
1B1
Pyrobel 17
2B2
Pyrobel 17 EG
1B1
Pyrobel 21
1B1
Pyrobel 21 EB
1B1
Pyrobel 25
1B1
Pyrobel 25 EG
1B1
Pyrobel 35
1B1
Pyrobel 35 EG
1B1
Pyrobel 53
1B1
Pyrobel 53 EG
1B1
Pyrobel 19
1B1
Pyrobel 23
1B1
Pyrobel 28
1B1
Other performances
Acoustic insulation
Rw
Rw + C
Rw + Ctr
Pyrobelite 7
34
34
31
Pyrobelite 7EG
35
34
33
Pyrobelite 12
36
35
33
Pyrobelite 12 EG
38
37
35
Pyrobel 8
34
33
31
Pyrobel 8EG
36
35
33
Pyrobel 16
39
38
36
Pyrobel 16 EG
39
38
36
Pyrobel 17
37
36
34
Pyrobel 17EG
38
38
35
Other performances
Rw
Rw + C
Rw + Ctr
Pyrobel 21
38
38
35
Pyrobel 21 EG
40
39
37
Pyrobel 25
40
39
37
Pyrobel 25 EG
43
42
39
Pyrobel 35
41
40
37
Pyrobel 35 EG
42
41
38
Pyrobel 53
45
44
41
Pyrobel 53 EG
46
44
41
Pyrobel 19
38
37
35
Pyrobel 23
39
39
36
Pyrobel 28
41
41
38
Thermal
insulation
Acoustic
insulation
Solar
control
Safety
Aesthetic
and decoration