SYNCHRONOUS MACHINES
Copyright © P. Kundur
This material should not be used without the author's consent
1539pk
Synchronous Machines
Outline
1. Physical Description
2. Mathematical Model
3. Park's "dqo" transportation
4. Steady-state Analysis
phasor representation in d-q coordinates
link with network equations
5. Definition of "rotor angle"
6. Representation of Synchronous Machines in
Stability Studies
neglect of stator transients
magnetic saturation
7. Simplified Models
8. Synchronous Machine Parameters
9. Reactive Capability Limits
SM - 1
1539pk
Physical Description of a
Synchronous Machine
Consists of two sets of windings:
3 phase armature winding on the stator
distributed with centres 120° apart in space
field winding on the rotor supplied by DC
Two basic rotor structures used:
salient or projecting pole structure for hydraulic
units (low speed)
round rotor structure for thermal units (high
speed)
Salient poles have concentrated field windings;
usually also carry damper windings on the pole
face.
Round rotors have solid steel rotors with
distributed windings
Nearly sinusoidal space distribution of flux wave
shape obtained by:
distributing stator windings and field windings in
many slots (round rotor);
shaping pole faces (salient pole)
SM - 2
1539pk
Rotors of Steam Turbine Generators
Traditionally, North American manufacturers normally
did not provide special “damper windings”
solid steel rotors offer paths for eddy currents,
which have effects equivalent to that of
amortisseur currents
European manufacturers tended to provide for
additional damping effects and negative-sequence
current capability
wedges in the slots of field windings
interconnected to form a damper case, or
separate copper rods provided underneath the
wedges
Figure 3.3: Solid round rotor construction
SM - 3
1539pk
Rotors of Hydraulic Units
Normally have damper windings or amortisseurs
non-magnetic material (usually copper) rods
embedded in pole face
connected to end rings to form short-circuited
windings
Damper windings may be either continuous or noncontinuous
Space harmonics of the armature mmf contribute to
surface eddy current
therefore, pole faces are usually laminated
Figure 3.2: Salient pole rotor construction
SM - 4
1539pk
Balanced Steady State Operation
Net mmf wave due to the three phase stator
windings:
travels at synchronous speed
appears stationary with respect to the rotor; and
has a sinusoidal space distribution
mmf wave due to one phase:
Figure 3.7: Spatial mmf wave of phase a
SM - 5
1539pk
Balanced Steady State Operation
The mmf wave due to the three phases are:
MMF
MMF
MMF
a
b
c
Ki a cos
i a I m cos s t
2
Ki b cos
3
2
i b I m cos s t
3
2
Ki c cos
3
2
i a l m cos s t
3
MMF
total
MMF
3
2
a
MMF b MMF
c
KI m cos s t
SM - 6
1539pk
Balanced Steady State Operation
Magnitude of stator mmf wave and its relative
angular position with respect to rotor mmf wave
depend on machine output
for generator action, rotor field leads stator field
due to forward torque of prime mover;
for motor action rotor field lags stator field due
to retarding torque of shaft load
Figure 3.8: Stator and rotor mmf wave shapes
SM - 7
1539pk
Transient Operation
Stator and rotor fields may:
vary in magnitude with respect to time
have different speed
Currents flow not only in the field and stator
windings, but also in:
damper windings (if present); and
solid rotor surface and slot walls of round rotor
machines
Figure 3.4: Current paths in a round rotor
SM - 8
1539pk
Direct and Quadrature Axes
The rotor has two axes of symmetry
For the purpose of describing synchronous
machine characteristics, two axes are defined:
the direct (d) axis, centered magnetically in the
centre of the north pole
The quadrature (q) axis, 90 electrical degrees
ahead of the d-axis
Figure 3.1: Schematic diagram of a 3-phase synchronous
machine
SM - 9
1539pk
Mathematical Descriptions of a
Synchronous Machine
For purposes of analysis, the induced currents in
the solid rotor and/or damper windings may be
assumed to flow in two sets of closed circuits
one set whose flux is in line with the d-axis; and
the other set whose flux is along the q-axis
The following figure shows the circuits involved
Figure 3.9: Stator and rotor circuits
SM - 10
1539pk
Review of Magnetic Circuit Equations
(Single Excited Circuit)
Consider the elementary circuit of Figure 3.10
ei
d
e1
dt
d
dt
ri
Li
The inductance, by definition, is equal to flux linkage
per unit current
L N
i
N P
2
where
P = permeance of magnetic path
> = flux = (mmf) P = NiP
Figure 3.10: Single excited magnetic circuit
SM - 11
1539pk
Review of Magnetic Circuit Equations
(Coupled Circuits)
Consider the circuit shown in Figure 3.11
e1
e2
d 1
dt
d2
dt
r1i 1
r2 i 2
1 L 11 i 1 L 21 i 2
2 L 21 i 1 L 22 i 2
with L11 = self inductance of winding 1
L22 = self inductance of winding 2
L21 = mutual inductance between winding 1 and 2
Figure 3.11: Magnetically coupled circuit
SM - 12
1539pk
Basic Equations of a Synchronous Machine
The equations are complicated by the fact that the
inductances are functions of rotor position and
hence vary with time
The self and mutual inductances of stator circuits
vary with rotor position since the permeance to flux
paths vary
I aa L al I gaa
L aa 0 L aa 2 cos 2
2
I ab Iba L ab 0 L ab 2 cos 2
3
L ab 0 L ab 2 cos 2
3
The mutual inductances between stator and rotor
circuits vary due to relative motion between the
windings
I afd L afd cos
I akd L akd cos
I akq L akq cos L akq sin
2
SM - 13
1539pk
Basic Equations of a Synchronous Machine
Dynamics of a synchronous machine is given by the
equations of the coupled stator and rotor circuits
Stator voltage and flux linkage equations for phase a
(similar equations apply to phase b and phase c)
ea
da
dt
R aia p a R aia
a l aa i a l ab i b l ac i c l afd i fd l akd i kd l akq i kq
Rotor circuit voltage and flux linkage equations
e fd p fd R fd i fd
0 p kd R kd i kd
0 p kq R kq i kq
fd L ffd i fd L fkd i kd
2
2
L afd i a cos i b cos
i c cos
3
3
kd L fkd i fd L kkd i kd
2
2
L afd i a cos i b cos
i c cos
3
3
kq L kkd i kq
2
2
L akq i a sin i b sin
i c sin
3
3
SM - 14
1539pk
The dqo Transformation
The dqo transformation, also called Park's
transformation, transforms stator phase quantities from
the stationary abc reference frame to the dqo reference
frame which rotates with the rotor
cos
i d
2
i
sin
q
3
i0
1
2
2
cos
3
2
sin
3
1
2
cos
sin
2
3
2
3
1
2
i a
i
b
i
c
The above transformation also applies to stator flux
linkages and voltages
With the stator quantities expressed in the dqo
reference frame
all inductances are independent of rotor position
(except for the effects of magnetic saturation)
under balanced steady state operation, the stator
quantities appear as dc quantities
during electromechanical transient conditions,
stator quantities vary slowly with frequencies in
the range of 1.0 to 3.0 Hz
The above simplify computation and analysis of results.
SM - 15
1539pk
Physical Interpretation of dqo
Transformation
The dqo transformation may be viewed as a means
of referring the stator quantities to the rotor side
In effect, the stator circuits are represented by two
fictitious armature windings which rotate at the
same speed as the rotor; such that:
the axis of one winding coincides with the d-axis
and that of the other winding with the q-axis
The currents id and iq flowing in these circuits
result in the same mmf's on the d- and q-axis as
do the actual phase currents
The mmf due to id and iq are stationary with respect
to the rotor, and hence:
act on paths of constant permeance, resulting in
constant self inductances (Ld, Lq) of stator
windings
maintain fixed orientation with rotor circuits,
resulting in constant mutual inductances
SM - 16
1539pk
Per Unit Representation
The per unit system is chosen so as to further
simplify the model
The stator base quantities are chosen equal to the
rated values
The rotor base quantities are chosen so that:
the mutual inductances between different
circuits are reciprocal (e.g. Lafd = Lfda)
the mutual inductances between the rotor and
stator circuits in each axis are equal (e.g., Lafd =
Lakd)
The P.U. system is referred to as the "Lad
base reciprocal P.U. system"
One of the advantages of having a P.U. system with
reciprocal mutual inductances is that it allows the
use of equivalent circuits to represent the
synchronous machine characteristics
SM - 17
1539pk
P.U. Machine Equations in
dqo reference frame
The equations are written with the following
assumptions and notations:
t is time in radians
p = d/dt
positive direction of stator current is out of the
machine
each axis has 2 rotor circuits
Stator voltage equations
e d p d q r R aid
e q p q d r R aiq
e 0 p 0 R ai0
Rotor voltage equations
e fd p fd R fd i fd
0 p 1d R 1d i 1d
0 p 1q R 1q i 1q
0 p 2 q R 2 qi 2 q
SM - 18
1539pk
P.U. Machine Equations in dqo Reference
Frame (cont'd)
Stator flux linkage equations
d L ad L l i d L ad i fd L ad i1 d
q L aq L l i q L aq i1 q L aq i 2 q
0 L0 i 0
Rotor flux linkage equations
fd L ffd i fd L f 1d i 1d L ad i d
1d L f 1d i fd L 11 d i 1d L ad i d
1q L 11 q i 1q L aq i 2 q L aq i q
1q L aq i 1q L 22 q L 2 q L aq i q
Air-gap torque
T e di q qi d
SM - 19
1539pk
Steady State Analysis Phasor
Representation
For balanced, steady state operation, the stator voltages may
be written as:
e a E m cos t
e b E m cos t 2 3
e c E m cos t 2 3
with
ω = angular velocity = 2πf
α = phase angle of ea at t=0
Applying the d,q transformation,
e d E m cos t
e q E m sin t
At synchronous speed, the angle θ is given by θ = ωt + θ0
with θ = value of θ at t = 0
Substituting for θ in the expressions for ed and eq,
e d E m cos 0
e q E m sin 0
SM - 20
1539pk
Steady State Analysis Phasor
Representation (cont'd)
The components ed and eq are not a function of t because
rotor speed ω is the same as the angular frequency ω
of the stator voltage. Therefore, ed and eq are constant
under steady state.
In p.u. peak value Em is equal to the RMS value of terminal
voltage Et. Hence,
e d E t cos 0
e q E t sin 0
The above quantities can be represented as phasors with
d-axis as real axis and q-axis as imaginary axis
Denoting δi, as the angle by which q-axis leads E
e d E t sin i
e q E t cos i
SM - 21
1539pk
Steady State Analysis Phasor
Representation (cont'd)
The phasor terminal voltage is given by
~
E t e d je q
E R jE l
in the d-q coordinates
in the R-I coordinates
This provides the link between d,q components in a
reference frame rotating with the rotor and R, I
components associated with the a.c. circuit theory
Under balanced, steady state conditions, the d,q,o
transformation is equivalent to
the use of phasors for analyzing alternating
quantities, varying sinusoidally with respect to
time
The same transformation with θ = ωt applies to both
in the case of machines, ω = rotor speed
in the case of a.c. circuits, ω = angular frequency
SM - 22
1539pk
Internal Rotor Angle
Under steady state
e d
q
i dR a
L qi q i dR a X qi q i dR a
Similarly
e q
d
i qR a
X d i d X ad i fd i q R a
Under no load, id=iq=0. Therefore,
q L qi q 0
d L ad i fd
ed 0
e q L ad i fd
~
E
and t e d je q jL ad i fd
Under no load, Et has only the q-axis component
and δi=0. As the machine is loaded, δi increases.
Therefore, δi is referred to as the load angle or
internal rotor angle.
It is the angle by which q-axis leads the phasor Et
SM - 23
1539pk
Electrical Transient Performance
To understand the nature of electrical transients, let
us first consider the RL circuit shown in Figure 3.24
with e = Emsin (ωt+α). If switch "S" is closed at t=0,
the current is given by
e L
di
solving
i Ke
Lt
R
Em
Z
iR
dt
sin t
The first term is the dc component. The presence of
the dc component ensures that the current does not
change instantaneously. The dc component decays
to zero with a time constant of L/R
Figure 3.24: RL Circuit
SM - 24
1539pk
Short Circuit Currents of a Synchronous
Machine
If a bolted three-phase fault is suddenly applied to
a synchronous machine, the three phase currents
are shown in Figure 3.25.
Figure 3.25: Three-phase short-circuit currents
SM - 25
1539pk
Short Circuit Currents of a Synchronous
Machine (cont'd)
In general, fault current has two distinct
components:
a) a fundamental frequency component which
decays initially very rapidly (a few cycles) and
then relatively slowly (several seconds) to a
steady state value
b) a dc component which decays exponentially in
several cycles
This is similar to the short circuit current in the case
of the simple RL circuit. However, the amplitude of
the ac component is not constant
internal voltage, which is a function of rotor flux
linkages, is not constant
the initial rapid decay is due to the decay of flux
linking the subtransient circuits (high resistance)
the slowly decaying part of the ac component is
due to the transient circuit (low resistance)
The dc components have different magnitudes in
the three phases
SM - 26
1539pk
Elimination of dc Component by
Neglecting Stator Transients
For many classes of problems, considerable
computational simplicity results if the effects of ac
and dc components are treated separately
Consider the stator voltage equations
e d p d q i dR a
e q p q d i qR a
transformer voltage terms: pψd, pψq
speed voltage terms: q , d
The transformer voltage terms represent stator
transients:
stator flux linkages (ψd, ψq) cannot change
instantaneously
result in dc offset in stator phasor current
If only fundamental frequency stator currents are of
interest, stator transients (pψd, pψq) may be
neglected.
SM - 27
1539pk
Short Circuit Currents with Stator Transients
Neglected
The resulting stator phase currents following a
disturbance has the wave shape shown in Figure
3.27
The short circuit has only the ac component whose
amplitude decays
Regions of subtransient, transient and steady state
periods can be readily identified from the wave shape
of phase current
Figure 3.27: Fundamental frequency component of short
circuit armature current
SM - 28
1539pk
Synchronous Machine Representation in
System Stability Studies
Stator Transients (pψd, pψq) are usually neglected
accounts for only fundamental frequency
components of stator quantities
dc offset either neglected or treated separately
allows the use of steady-state relationships for
representing the transmission network
Another simplifying assumption normally made is
setting 1 in the stator voltage equations
counter balances the effect of neglecting stator
transients so far as the low-frequency rotor
oscillations are concerned
with this assumption, in per unit air-gap power
is equal to air-gap torque
(See section 5.1 of book for details)
SM - 29
1539pk
Equation of Motion (Swing Equation)
The combined inertia of the generator and primemover is accelerated by the accelerating torque:
J
dm
dt
T a Tm T e
where
Tm =
mechanical torque in N-M
Te =
electromagnetic torque in N-m
J
combined moment of inertia of generator
and turbine, kg•m2
=
am =
angular velocity of the rotor in mech. rad/s
t
time in seconds
=
SM - 30
1539pk
Equation of Motion (cont'd)
The above equation can be normalized in terms of
per unit inertia constant H
1 J 0m
2
H
2 VA base
where
a0m = rated angular velocity of the rotor in
mechanical radians per second
Equation of motion in per unit form is
2H
d r
dt
Tm T e
where
r
Tm
Te
m
0m
Tm 0 m
VA
= per unit mechanical torque
base
Te 0 m
VA
= per unit rotor angular velocity
= per unit electromechanical torque
base
Often inertia constant M = 2H used
SM - 31
1539pk
Magnetic Saturation
Basic equations of synchronous machines
developed so far ignored effects of saturation
analysis simple and manageable
rigorous treat a futile exercise
Practical approach must be based on semiheuristic reasoning and judiciously chosen
approximations
consideration to simplicity, data availability,
and accuracy of results
Magnetic circuit data essential to treatment of
saturation given by the open-circuit characteristic
(OCC)
SM - 32
1539pk
Assumptions Normally Made in the
Representation of Saturation
Leakage inductances are independent of saturation
Saturation under loaded conditions is the same as
under no-load conditions
Leakage fluxes do not contribute to iron saturation
degree of saturation determined by the air-gap
flux
For salient pole machines, there is no saturation in
the q-axis
flux is largely in air
For round rotor machines, q-axis saturation
assumed to be given by OCC
reluctance of magnetic path assumed
homogeneous around rotor periphery
SM - 33
1539pk
The effects of saturation is represented as
L ad K sd L adu
(3.182)
(3.183)
L aq K sq L aqu
Ladu and Laqu are unsaturated values. The saturation
factors Ksd and Ksq identify the degrees of
saturation.
As illustrated in Figure 3.29, the d-axis saturation is
given by The OCC.
Referring to Figure 3.29,
I at 0 at
K sd
(3.186)
at
(3.187)
at I
For the nonlinear segment of OCC, I can be
expressed by a suitable mathematical function:
I A sat e
B sat
at
SM - 34
TI
(3.189)
1539pk
Open-Circuit Characteristic (OCC)
Under no load rated speed conditions
id iq q e d 0
E t e q d L ad i fd
Hence, OCC relating to terminal voltage and field
current gives saturation characteristic of the d-axis
Figure 3.29: Open-circuit characteristic showing effects of
saturation
SM - 35
1539pk
For salient pole machines, since q-axis flux is
largely in air, Laq does not vary significantly with
saturation
Ksq=1 for all loading conditions
For round rotor machines, there is saturation in
both axes
q-axis saturation characteristic not usually
available
the general industry practice is to assume
Ksq = Ksd
For a more accurate representation, it may be
desirable to better account for q-axis saturation of
round rotor machines
q-axis saturates appreciably more than the daxis, due to the presence of rotor teeth in the
magnetic path
Figure 3.32 shows the errors introduced by
assuming q-axis saturation to be same as that of
d-axis, based on actual measurements on a 500
MW unit at Lambton GS in Ontario
Figure shows differences between measured
and computed values of rotor angle and field
current
the error in rotor angle is as high as 10%, being
higher in the underexcited region
the error in the field current is as high as 4%,
being greater in the overexcited region
SM - 36
1539pk
The q-axis saturation characteristic is not readily
available
It can, however, be fairly easily determined from
steady-state measurements of field current and
rotor angle at different values of terminal
voltage, active and reactive power output
Such measurements also provide d-axis
saturation characteristics under load
Figure 3.33 shows the d- and q-axis saturation
characteristics derived from steady-state
measurements on the 500 MW Lambton unit
Figure 3.33: Lambton saturation curves derived from
steady-state field current and rotor angle measurements
SM - 37
1539pk
Example 3.3
Considers the 555 MVA unit at Lambton GS and
examines
the effect of representing q-axis saturation
characteristic distinct from that of d-axis
the effect of reactive power output on rotor angle
Table E3.1 shows results with q-axis saturation assumed
same as d-axis saturation
Table E3.1
Pt
Qt
Ea (pu)
Ksd
δi (deg)
ifd (pu)
0
0
1.0
0.889
0
0.678
0.4
0.2
1.033
0.868
25.3
1.016
0.9
0.436
1.076
0.835
39.1
1.565
0.9
0
1.012
0.882
54.6
1.206
0.9
-0.2
0.982
0.899
64.6
1.089
Table E3.2 shows results with distinct d- and q-axis
saturation representation
Table E3.2
Pt
Qt
Ksq
Ksd
δi (deg)
ifd (pu)
0
0
0.667
0.889
0
0.678
0.4
0.2
0.648
0.868
21.0
1.013
0.9
0.436
0.623
0.835
34.6
1.559
0.9
0
0.660
0.882
47.5
1.194
0.9
-0.2
0.676
0.899
55.9
1.074
SM - 38
1539pk
Simplified Models for Synchronous
Machines
Neglect of Amortisseurs
first order of simplification
data often not readily available
Classical Model (transient performance)
constant field flux linkage
neglect transient saliency (x'd = x'q)
E´
Et
x d
Steady-state Model
constant field current
neglect saliency (xd = xq = xs)
Et
Eq
xs
Eq = Xadifd
SM - 39
1539pk
Reactive Capability Limits of Synchronous
Machines
In voltage stability and long-term stability studies,
it is important to consider the reactive capability
limits of synchronous machines
Synchronous generators are rated in terms of
maximum MVA output at a specified voltage and
power factor which can be carried continuously
without overheating
The active power output is limited by the prime
mover capability
The continuous reactive power output capability is
limited by three considerations
armature current limit
field current limit
end region heating limit
SM - 40
1539pk
Armature Current Limit
Armature current results in power loss, and the
resulting heat imposes a limit on the output
The per unit complex output power is
~ *
S P jQ E t ~I t E t I t cos j sin
where Φ is the power factor angle
In a P-Q plane the armature current limit, as shown
in Fig. 5.12, appears as a circle with centre at the
origin and radius equal to the MVA rating
Fig 5.12: Armature current heating limit
SM - 41
1539pk
Field Current Limit
Because of the heating resulting from RfdI2fd power
loss, the field current imposes the second limit
The phasor diagram relating Et, It and Eq (with Ra
neglected) is shown in Fig. 5.13
Equating the components along and perpendicular to
the phasor E t
X ad i fd sin i X s l t cos
X ad i fd cos i E t X s l t sin
Therefore
P E t l t cos
Q E t l t sin
X ad
Xs
X ad
Xs
E t i fd sin i
2
E t i fd cos i
Et
Xs
The relationship between P and Q for a given field
current is a circle centered at on the Q-axis and with
as the radius. The effect of the maximum field current
on the capability of the machine is shown in Fig. 5.14
In any balanced design, the thermal limits for the field
and armature intersect at a point (A) which represents
the machine name-plate MVA and power factor rating
SM - 42
1539pk
Field Current Limit
Fig. 5.13: Steady state phasor diagram
Fig. 5.14: Field current heating limit
SM - 43
1539pk
End Region Heating Limit
The localized heating in the end region of the armature
affects the capability of the machine in the underexcited
condition
The end-turn leakage flux, as shown in Fig. 5.15, enters
and leaves in a direction perpendicular (axial) to the
stator lamination. This causes eddy currents in the
laminations resulting in localized heating in the end
region
The high field currents corresponding to the
overexcited condition keep the retaining ring saturated,
so that end leakage flux is small. However, in the
underexcited region the field current is low and the
retaining ring is not saturated; this permits an increase
in armature end leakage flux
Also, in the underexcited condition, the flux produced
by the armature current adds to the flux produced by
the field current. Therefore, the end-turn flux enhances
the axial flux in the end region and the resulting heating
effect may severely limit the generator output,
particularly in the case of a round rotor machine
Fig. 5.16 shows the locus of end region heating limit on
a P-Q plane
SM - 44
1539pk
End Region Heating Limit
Fig. 5.15: Sectional view end region of a generator
Fig. 5.16: End region heating limit
SM - 45
1539pk
Reactive Capability Limit of a 400 MVA
Hydrogen Cooled Steam Turbine Generator
Fig. 5.18 shows the reactive capability curves of a 400
MVA hydrogen cooled steam turbine driven generator
at rated armature voltage
the effectiveness of cooling and hence the
allowable machine loading depends on hydrogen
pressure
for each pressure, the segment AB represents the
field heating limit, the segment BC armature heating
limit, and the segment CD the end region heating
limit
Fig. 5.18: Reactive capability curves of a hydrogen cooled
generator at rated voltage
SM - 46
1539pk
Effect of Changes in Terminal Voltage Et
Fig. 5.17: Effect of reducing the armature voltage on the
generator capability curve
SM - 47