Project Presentation.ppt
Download
Report
Transcript Project Presentation.ppt
Improved Precision Leading to
Improved Energy Efficiency
Edward Decker
AE 790 – Intelligent Buildings
June 6, 2006
Why is Ventilation Air Needed?
The health and comfort of the building
occupants
The removal of internally generated
contaminants
To maintain certain pressure differentials
between the indoor and outdoor
environments
How to Ensure Proper Ventilation
Use a dedicated OA system
– Provides 100% OA
– Ensures the minimum ventilation requirements are met
Why Not?
– No mixing of Airstreams
100% of the SA must be conditioned
Increased energy use
– Increased energy cost
– Best to maximize return air
How is RA & OA Mixed
Dampers are modulated to allow for air to be
directed
– Back in to the AHU as RA
– Out of the building into the atmosphere as EA
Mass Balance
– The amount of EA needs to be replaced
OA is introduced to the system via an OA damper
The amount of OA must meet the minimum requirements
– The first step is to quantify the required and actual
amounts of SA, RA, EA, and OA
What are the Methods to Measure
Ventilation Air?
Direct
– Measures the airflow
directly, using a
devise such as an
anemometer.
– Require regular flow
profiles for accurate
readings.
Indirect
– Measures other
parameters that are
dependant upon the
airflow, as in the
energy balance
method
– Typically for low rates
that are difficult to
measure
What are the Ways to Measure
Ventilation Air?
Direct
– Averaging Pitot-Tube
Array
– Electronic Thermal
Anemometry
– Fan Inlet
– Rotating vane and propeller
anemometers
– Swinging vane anemometers
– Vortex shedding meters
– Integrated damper and
measuring devises
– Laser doppler anemometry
(LDA)
– Orifice Meters
Indirect
– Enthalpy Balance
– Concentration Balance
Measuring Ventilation Air
Direct Method with Pitot-tube array
– Velocity must be high enough for sensor accuracy
– Regular flow profile is required, and often overlooked
Spacing of a minimum of 2D before a station and 1D behind
required
Development of flow devices
– Calculate properties of fully developed flow profile
Less space required
– Device to ‘trip’ the velocity profile
Achieve accurate readings
Less space required
– Comfortable Methods
Current Industry Standard without inherent problems
What are the Common ways to
Control Ventilation Air?
Flow monitoring using:
– Hot wire anemometers
– Thermistor sensors
– Velocity pressure sensing (pitot-tubes)
Differential Static Pressure Control
– across fixed duct elements or with respect to OA pressure
Use of commissioning data to relate system flow at various
fan-operating points with OA damper actuator signal
position
Volumetric Fan tracking
– Measuring SA and RA and assuming that the difference is the
amount of OA
CO2 surrogate sensing
Outside Air Injection Fan
Differential Static Pressure Control
Involves maintaining a constant pressure
in the mixed air plenum or other
reference point in the duct.
– With constant pressure in the mixed air
plenum and a fixed minimum damper, the
minimum OA quantity remains constant as
the supply air fan modulates.
Static pressure sensors are simple,
reliable, and require little space.
Modulating minimum OA damper
New product such as flow sensing built
into dampers may be the best
– Velocity pressure is calculated and
maintained constant by modulating the
minimum OA blades themselves
Mixed Air Temperature
Comparison Method
Method is still being used, but is not
recommended
– When OA and RA are within 10-20 °F,
readings are not trustworthy
Accuracy degrades as Toa approaches Tra
– Balancers sometimes use this method when
there isn’t room for pitot tube traverses
Mixed Air Temperature
Comparison Method
Better Sensors can Improve this
Technique
– Cheaper Sensors
More sensors
– Redundancy in readings
– More Precise Sensors
Less errors in readings
Close OA and RA temperatures can be distinguished
better
Concentration Balance
Provides adequate control
– Exceptions
Low occupancy
When OA represents a small fraction of SA
Problems
– Only accounts for contaminants generated by
people in space, but not other contaminants
i.e.-VOCs from carpets, paints, etc
Concentration Balance
Better Sensors for measurement of all
contaminants
– OA might be polluted
Determine the airstream with the ‘best’ quality of air
Leads to improved overall IAQ
– Multiple readings with improved precision
Can measure the air requirements of a given space
Design on an individual zone basis
Concentration Balance
Design on an Individual Zone Basis
– Occupied modes for each zone
– Ventilation requirements for individual room
– Improved IAQ
– Decreased energy consumption
– Decreased energy bills
Conclusion
Accurate measurement and control of outside air
intake is possible
– Proper installation and operation
Intelligent Design
– Improve accuracy of readings and control
– More precise control
Better zone conditions
– Improved overall IAQ
– Energy savings
– Cost Savings
QUESTIONS?
?